Munters RSLC Silo Weighing Scale-Junction Box Instruction Manual
- June 9, 2024
- Munters
Table of Contents
- Munters RSLC Silo Weighing Scale-Junction Box Instruction Manual
- Manual for use and maintenance
- RSLC and RJB-6
- RSLC Load Cell and RJB-6Junction Box Manual for use and maintenance
- 1 Introduction
- 1.1 Disclaimer
- 1.2 Introduction
- 1.3 Notes
- 2 RJB-6 Installation
- 3 RSLC Installation
- Figure 6: Silo Legs and Load Cells
- Figure 8: RSLC-4 Unit
- 3.1.1 RSLC-4 Installation
- Figure 9: RSLC-4 Plate Dimensions
- 1.1 RSLC-10
- 3.2.1 RSLC-10 Installation
- 3.3 RSLC-25\
- 3.4 Environmental Protection
- 4.2 Load Cell Test Procedure
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Munters RSLC Silo Weighing Scale-Junction Box Instruction Manual
Manual for use and maintenance
RSLC and RJB-6
Silo Weighing Scale/Junction Box
RSLC Load Cell and RJB-6Junction Box Manual for use and maintenance
Revision: N.1.4 of 09/2022 Product Software: N/A
This manual for use and maintenance is an integral part of the apparatus
together with the attached technical documentation.
This document is destined for the user of the apparatus: it may not be
reproduced in whole or in part,
committed to computer memory as a file or delivered to third parties without
the prior authorization of
the assembler of the system.
Munters reserves the right to effect modifications to the apparatus in
accordance with technical and legal developments
1 Introduction
1.1 Disclaimer
Munters reserves the right to make alterations to specifications, quantities,
dimensions etc. for production or other reasons, subsequent to publication.
The information contained herein has been
prepared by qualified experts within Munters. While we believe the information
is accurate and complete, we make no warranty or representation for any
particular purposes. The information is
offered in good faith and with the understanding that any use of the units or
accessories in breach ofthe directions and warnings in this document is at the
sole discretion and risk of the user.
1.2 Introduction
Congratulations on your excellent choice of purchasing an RSLC Load Cell and RJB-6 Junction Box! In order to realize the full benefit from this product it is important that it is installed, commissioned and operated correctly. Before installation or using the units, this manual should be studied carefully. It is also recommended that it is kept safely for future reference. The manual is intended as a reference for installation, commissioning and day-to-day operation of the Munters equipment.
1.3 Notes
Date of release: July 2010
Munters cannot guarantee to inform users about the changes or to distribute
new manuals to them.
NOTE All rights reserved. No part of this manual may be reproduced in any
manner whatsoever without the expressed written permission of Munters. The
contents of this manual are subject to change without notice. © Munters AB,
2018 5
2 RJB-6 Installation
Munters RJB-6 enables connecting up to eight load cells to a single
controller. This section details
how to mount and wire the RJB-6.
-
Figure 1: Opening the RJB-6 Cover
-
Using a drill and the supplied screws, attach the RJB-6 to a silo leg
Figure 2: RJB-6 Mounting -
Close the unit.
- Cable: Board
o White – White
o Red – Red
o Black – Black
o Green – Green
o Connect the shield wire to the GND(SHD) port
Figure 5: RJB – Six RSLCs Wiring Figure 5 key
1 If there are eight load cells, add the two remaining cells along with load
cells 1 and 2
6. Connect the relevant controller cables to the “Controller” terminal block
within the RJB
junction box. The connection colors of this cable are direct connection.
NOTE Refer to the specific controller manual for details on wiring the RJB-6
to the controller.
• Cable: Board
o White – White
o Red – Red
o Black– Black
o Green – Green
3 RSLC Installation
The following sections detail how to install the:
- RSLC-4 supports up to 4,000 pounds (per leg)
- RSLC-10 supports up to 10,000 pounds (per leg)
- RSLC-25 supports up to 25,000 pounds (per leg) Place load cells under each silo leg.
Figure 6: Silo Legs and Load Cells
The RSLC units comes with a grounding cable that, if required, can be run from one silo leg to a grounding rod.
Figure 7: Grounding cable
3.1 RSLC-4
Figure 8: RSLC-4 Unit
- RSLC-4 Installation
- RSLC-4 Specifications
3.1.1 RSLC-4 Installation
Figure 9: RSLC-4 Plate Dimensions
- Figure 9 illustrates the RSLC-4 plate. Drill four holes into the concrete base as indicated (A).
- Wire the Load Cells to the RJB-6.
- 1.2 RSLC-4 Specification
Table 1: RSLC-4 Specifications
Parameter | Value |
---|---|
Full Scale Output | 3.0 mV/V±0.25% |
Zero Balance | ±0.02 mV/V |
Input Resistance | 400Ω±20 for kg; 350Ω±7 for lb. |
Output Resistance | 350Ω±3 |
Parameter | Value |
--- | --- |
Element Material | Alloy Steel, Nickel Plated |
Recommended Excitation | 10V (15V Maximum) |
Insulation Resistance | >2[50V DC]GΩ |
Compensated Temperature Range | -10oC to 50oC / 14oF to 122oF |
Safe Overload | 150% of full scale |
Breaking Overload | 300% of full scale |
Seal Type / IP Rating | Cap.≤300kg/500lb: Environmentally Sealed / IP66 |
Cap.≥500kg/1Klb: Environmentally Sealed / IP67
Figure 10and Table 2 detail the RSLC-4 Load Cell dimensions
Figure 10: RSLC-4 Load Cell Dimensions
Table 2: RSLC-4 Load Cell Dimensions Details
Letter| C1| C2| H| H1| L| L1| L2|
L3| L4| W
---|---|---|---|---|---|---|---|---|---|---
Dimensions (in)| 0.53| 0.81| 1.25| 0.60| 5.12| 2.25| 3.00| 1.00| 0.62|
1.25
Dimensions (mm)| 13.5| 20/6| 31.8| 15.2| 130| 57.2| 76.2| 25.4| 15.8|
31.8
1.1 RSLC-10
F i g u r e 11 : R SLC- 1 0 U n i t
- RSLC-10 Installation
- RSLC-10 Specifications
3.2.1 RSLC-10 Installation
3.3 RSLC-25\
Figure 13: RSLC-10 Load Cell Dimensions
Table 4: RSLC-10 Load Cell Dimensions Details
Letter| C1| C2| C3| C4| H| L| L1|
L2| L3
---|---|---|---|---|---|---|---|---|---
Dimensions (inches)| 0.66| 1.85| 1.48| 0.50| 1.12| 8.12| 6.87| 0.62| 1.44
Dimensions (mm)| 16.7| 49.5| 37.6| 12.7| 28.4| 206.2| 174.6| 15.8| 36.6
3.4 Environmental Protection
Recycle raw materials instead of disposing as waste. The controller, accessories and packaging should be sorted for environmental-friendly recycling. The plastic components are labeled for categorized recycling.
4.2 Load Cell Test Procedure
To perform a load-cell test procedure, disconnect the load cell from any load and test following points:
- Disconnect the white and green wires from each load cell at the Junction Box.
- Measure the voltage between the green and the white wires with a DC voltmeter, at each load cell.
o The voltage should be 0 to 30mV proportional to the silo weight.
o The voltage difference between load cells should not exceed 3mV.