AutomatikCentret TTH-6040-W Room Temperature Transmitter Instructions

June 9, 2024
AutomatikCentret

TTH-6040-W Room Temperature Transmitter
Instruction manual

TTH-6040-W is a Modbus-based temperature sensor for wall mounting supplied with a junction box for conversion from 4-core cable to modular Modbus cable. TTH-6040- W is used to measure room temperature for use by ventilation systems.

PRODUCT PROGRAMME

Type Product
TTH-6040-W  Temperature sensor with Modbus for wall mounting

CONTENTS

The box contains the following:
1 x Temperature sensor for wall mounting
1 x Junction box with modular connector
3 m QuickPlug™ cable
2 x Screws
1 x Adhesive pad 50×50 mm

FUNCTION

TTH-6040-W is a room temperature sensor with Modbus communication for use with an air handling unit equipped with an OJ Air2 Master (rotary selector in position 0).  The sensor can also be used with other controllers that support the Modbus protocol.
TTH-6040-W measures room temperature and communicates the result via Modbus. The temperature sensor should be mounted on a flat surface at a representative measuring point. Do not mount the sensor in direct sunlight or where draughts occur. Connect the sensor to the junction box using a 4-core cable (not supplied); see Figure  6. Connect the junction box to the OJ Air2 Master using RJ12 cable. As long as the total cable length is less than 50 metres, no special demands are made on cable type or  shielding. The cable should be connected to Modbus port A of the OJ Air2 Master.

MODBUS
TTH-6040-W uses Modbus RTU, 38400 baud, 1 start bit, 8 data bits, 2 stop bits and no parity.
Modbus addresses
See Table 1 on page 4.

TECHNICAL DATA

Supply voltage:  17-28 VDC via bus and terminals
Power consumption:  Temp. measuring 0.24 W @ 24 VDC
Temp. measuring accuracy: ±0.3K @ 25°C
Ambient temperature: -10 / +40°C
Dimensions: 86 x 86 x 25 mm
Enclosure rating: IP 20
Weight: 60 g

FIGURES

Fig. 1: Opening the temperature sensor
Fig. 2: Temperature sensor dimensions
Fig. 3: Opening the junction box
Fig. 4: Junction box dimensions
Fig. 5: Rotary selector
Fig. 6: Wiring diagram

SERVICE AND MAINTENANCE

TTH-6040-W contains no components which require service or maintenance. The ventilation holes in the temperature sensor must, however, be kept free of dust and dirt so  as to allow free and unrestricted passage.
Please contact your supplier if faults arise.

DISPOSAL AND ENVIRONMENTAL PROTECTION
Help protect the environment by disposing of the packaging and redundant products in an environmentally responsible manner.

Product disposal
Products marked with this symbol must not be disposed of together with household refuse but must be delivered to a waste collection centre in accordance with local  regulations.

Applied standards
EN 61000-6-2:2005 Electromagnetic compatibility (EMC)
EN 61000-6-3:2007
Electromagnetic compatibility (EMC)

CE MARKING
OJ Electronics A/S hereby declares that the product is manufactured in accordance with Council Directive 04/31/EEC (and subsequent amendments) on electromagnetic  compatibility.

Applied standards

EN 61000-6-2:2005  Electromagnetic compatibility (EMC)
EN 61000-6-3:2007  Electromagnetic compatibility (EMC)

OJ ELECTRONICS A/S
Stenager 13B · DK-6400 Sønderborg
Tel. +45 73 12 13 14 · Fax +45 73 12 13 13
oj@ojelectronics.com · www.ojelectronics.com

AutomatikCentret TTH-6040-W Room Temperature Transmitter - Figure
1AutomatikCentret TTH-6040-W Room
Temperature Transmitter - Figure 2AutomatikCentret TTH-6040-W Room Temperature
Transmitter - Figure 3

Position Modbus adr.
0 0x10 (hex) / 16 (dec.)
1 0x11 (hex) / 17 (dec.)
2 0x12 (hex) / 18 (dec.)
3 0x13 (hex) / 19 (dec.)
4 0x14 (hex) / 20 (dec.)
5 0x15 (hex) / 21 (dec.)
6 0x16 (hex) / 22 (dec.)
7 0x17 (hex) / 23 (dec.)
8 0x18 (hex) / 24 (dec.)
9 0x19 (hex) / 25 (dec.)
A 0x1A (hex) / 26 (dec.)
B 0x1B (hex) / 27 (dec.)
C 0x1C (hex) / 28 (dec.)
D 0x1D (hex) / 29 (dec.)
E 0x1E (hex) / 30 (dec.)
F 0x1F (hex) / 31 (dec.)

Tabel 1. Modbus adresses

OJ ELECTRONICS A/S
Stenager 13B
DK-6400 Sønderborg
Tel. +45 7312 1314
Fax +45 7312 1313
oj@ojelectronics.com
www.ojelectronics.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals