Aeotec Z-Wave Clamp Power Meter 1st Edition – two clamps AEO_HEM2-G1 Manual

June 8, 2024
Aeotec

Table of Contents

Aeon Labs

Z-Wave Clamp Power Meter 1st Edition – two clamps

SKU: AEO_HEM2-G1

Quickstart

This is a ****

Measuring Sensor Device
for
Europe
.

To run this device please insert fresh *4 AA** batteries.

Please make sure the internal battery is fully charged.

Single click the little button behind the battery cover to include or exclude the device. The device is FLIRS.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The Aeon Labs Smart Energy Monitor is a low-cost energy monitor for the entire home. It can wirelessly report immediate wattage and kWh usage to central control point gateways and can be easily and safely installed by anyone. Ease and safety are paramount: Electricians are not required to install the Aeon Labs Smart Energy Monitor; the customer never needs to handle hot exposed wiring. Current transformer clamps clamp around the AC Mains to detect energy usage for the entire house. The main body is anchored using a back mount which can be opend easily for battery replacement (every year). Optionally it is possible to power the unit from an external mini USB power supply. The device reports W and kWH.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Safety Warning for Batteries

The product contains batteries. Please remove the batteries when the device is not used.
Do not mix batteries of different charging level or different brands.

Installation

The HEM can be placed on every dry place closed to the electric installation to be monitored. The current transformers need to be clamped around single wires. Attention: It is not possible to measure the current in cables that consist of more than one wire. Such a wire must be stripped and the CT has to be installed on the hot wire only. If there are less wires than the number of CTs this will not harm the operation of the device.

The device can be powered by batteries or by an external power supply that is connected to the HEM via mini USB connector. In case an external power supply is installed, remove the batteries inside!

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Single click the little button behind the battery one time to include or exclude the device.

Exclusion

Single click the little button behind the battery one time to include or exclude the device.

Product Usage

The device is able to report wattage and electric power consume on request or ? if configured correctly ? regularly without being polled. The reporting interval is limited to min 4 minutes if the device is battery operated. The device reports aggregated values and individual values of the clamp. Attention: The wattage value is very dynamic and is measured right at the moment of polling. If both the aggregated value and the values of the individual clamps are polled the result may differ because the values were just taken at different times. In order to operate correctly, a number of configuration settings need to be made.

Configuration parameter #1 defines the local voltage. Attention: It is not possible to set the precise voltage of your mains network, but 110 verus 240 V only. The current transformer clamps will always measure current only and use the set voltage value to calculate the wattage and electric power. If your local main voltage is e.g. 230 V only you will receive wrong wattage results simply by the fact that the wrong voltage is used for calculation.

Node Information Frame

The Node Information Frame (NIF) is the business card of a Z-Wave device. It contains
information about the device type and the technical capabilities. The inclusion and
exclusion of the device is confirmed by sending out a Node Information Frame.
Beside this it may be needed for certain network operations to send out a Node
Information Frame. To issue a NIF execute the following action:

A single click on the little button behind the battery sends a Node Information Frame.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1 5 Receiver of all Reports

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 2: If the reverse clamping pliers, negative power is detected.

__
Size: 1 Byte, Default Value: 00

SettingDescription

00 Disabled
01 Enabled

Parameter 3: Automated Report only when power is changed

__
Size: 1 Byte, Default Value: 00

SettingDescription

00 Disabled
01 Enabled

Parameter 4: Minimum Change to send Report (Watt) for the whole HEM

The value represents the minimum change in Wattage for a Report to be sent .
Size: 2 Byte, Default Value: 0032

SettingDescription

00 – 6000 Value in W

Parameter 5: Minimum Change to send Report (Watt) for clamp 1

The value represents the minimum change in Wattage for a Report to be sent .
Size: 2 Byte, Default Value: 0032

SettingDescription

00 – 6000 Value in W

Parameter 6: Minimum Change to send Report (Watt) for clamp 2

The value represents the minimum change in Wattage for a Report to be sent .
Size: 2 Byte, Default Value: 0032

SettingDescription

00 – 6000 Value in W

Parameter 7: Minimum Change to send Report (Watt) for clamp 3

The value represents the minimum change in Wattage for a Report to be sent .
Size: 2 Byte, Default Value: 0032

SettingDescription

00 – 6000 Value in W

Parameter 8: Minimum Change to send Report (%) for the whole HEM

The value represents the minimum change in Watage Percent for a report to be sent
Size: 1 Byte, Default Value: 0a

SettingDescription

00 – 100 Value in %

Parameter 9: Minimum Change to send Report (%) for clamp 1

The value represents the minimum change in Watage Percent for a report to be sent
Size: 1 Byte, Default Value: 0a

SettingDescription

00 – 100 Value in %

Parameter 10: Minimum Change to send Report (%) for clamp 2

The value represents the minimum change in Watage Percent for a report to be sent
Size: 1 Byte, Default Value: 0a

SettingDescription

00 – 100 Value in %

Parameter 11: Minimum Change to send Report (%) for clamp 3

The value represents the minimum change in Watage Percent for a report to be sent
Size: 1 Byte, Default Value: 0a

SettingDescription

00 – 100 Value in %

Parameter 13: Enable /disable reporting CRC-16 Encapsulation Command

__
Size: 1 Byte, Default Value: 00

SettingDescription

00 Disabled
01 Enabled

Parameter 101: Report type send in Reporting Group 1

Defines the type of report sent for the Reporting Group 1.
Size: 4 Byte, Default Value: 00000008

SettingDescription

Byte 1: 00000010 Battery Report
Byte 1: 00000100 MultiSensor Report for the whole device
Byte 1: 00001000 Meter Report for Watt for the whole device
Byte 1: 00010000 Meter Report for kWh for the whole device
Byte 2: 00000010 Meter Report for Watt for clamp 1
Byte 2: 00000100 Meter Report for Watt for clamp 2
Byte 2: 00001000 Meter Report for Watt for clamp 3
Byte 2: 00010000 Meter Report for kWh for clamp 1
Byte 2: 00100000 Meter Report for Watt for clamp 2
Byte 2: 01000000 Meter Report for kWh for clamp 3

Parameter 102: Report Type send in Reporting Group 2

Defines the type of report sent for the Reporting Group 2.
Size: 4 Byte, Default Value: 00000000

SettingDescription

Byte 1: 00000010 Battery Report
Byte 1: 00000100 MultiSensor Report for the whole device
Byte 1: 00001000 Meter Report for Watt for the whole device
Byte 1: 00010000 Meter Report for kWh for the whole device
Byte 2: 00000010 Meter Report for Watt for clamp 1
Byte 2: 00000100 Meter Report for Watt for clamp 2
Byte 2: 00001000 Meter Report for Watt for clamp 3
Byte 2: 00010000 Meter Report for kWh for clamp 1
Byte 2: 00100000 Meter Report for Watt for clamp 2
Byte 2: 01000000 Meter Report for kWh for clamp 3

Parameter 103: Report Type send in Reporting Group 3

Defines the type of report sent for the Reporting Group 3.
Size: 4 Byte, Default Value: 00000000

SettingDescription

Byte 1: 00000010 Battery Report
Byte 1: 00000100 MultiSensor Report for the whole device
Byte 1: 00001000 Meter Report for Watt for the whole device
Byte 1: 00010000 Meter Report for kWh for the whole device
Byte 2: 00000010 Meter Report for Watt for clamp 1
Byte 2: 00000100 Meter Report for Watt for clamp 2
Byte 2: 00001000 Meter Report for Watt for clamp 3
Byte 2: 00010000 Meter Report for kWh for clamp 1
Byte 2: 00100000 Meter Report for Watt for clamp 2
Byte 2: 01000000 Meter Report for kWh for clamp 3

Parameter 111: Send Interval for Reporting Group 1

Defines the time interval when the defined report of Reporting Group 1 is sent out.
Size: 1 Byte, Default Value: 01

SettingDescription

00 – 127 Value in s

Parameter 112: Send Interval for Reporting Group 2

Defines the time interval when the defined report of Reporting Group 2 is sent out.
Size: 1 Byte, Default Value: 01

SettingDescription

00 – 127 Value in s

Parameter 113: Send Interval for Reporting Group 3

Defines the time interval when the defined report of Reporting Group 3 is sent out.
Size: 1 Byte, Default Value: 01

SettingDescription

00 – 127 Value in s

Parameter 100: Set 101-103 to default

__
Size: 1 Byte, Default Value: 01

SettingDescription

Parameter 110: Set 111-113 to default

__
Size: 1 Byte, Default Value: 01

SettingDescription

Parameter 200: Partner ID

(0= Aeon Labs Standard Product, 1= AT &T).
Size: 1 Byte, Default Value: 01

SettingDescription

Parameter 252: Enable/disable Configuration Locked

0 =disable, 1 = enable
Size: 1 Byte, Default Value: 00

SettingDescription

00 0 = disabled
01 1 = enabled

Parameter 254: Device Tag

__
Size: 2 Byte, Default Value: 0000

SettingDescription

Parameter 255: Reset

Reset configuration set up to default setting
Size: 1 Byte, Default Value: 00

SettingDescription

Technical Data

Battery Type 4 * AA
Device Type Routing Multilevel Sensor
Generic Device Class Multilevel Sensor
Specific Device Class Routing Multilevel Sensor
Firmware Version 03.38
Z-Wave Version 02.61
Z-Wave Product Id 0086.0002.0009
Frequency Europe – 868,4 Mhz
Maximum transmission power 5 mW

Supported Command Classes

  • Basic
  • Battery
  • Wake Up
  • Association
  • Version
  • Multi Channel
  • Manufacturer Specific
  • Configuration
  • Sensor Multilevel
  • Meter

Controlled Command Classes

  • Wake Up

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals