Simon S100 IO Socket 16A (India) 10002082-y3x Manual

June 8, 2024
Simon

Simon

S100 IO Socket 16A (India)

SKU: 10002082-y3x

Quickstart

This is a ****

On/Off Power Switch
for
.

To run this device please connect it to your mains power supply.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

Socket iO is ready to operate with Z-Wave controllers and configured to be managed by Simon100 iO APP using the HUB plug iO for getting a better user experience. allowing the control of the socket and LEDs integrated.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 3| Z-Wave Plus LifelineCOMMAND_CLASS_BASIC_REPORTIt is sent to the associated nodes when the loadchanges state:ON-> 0xFFOFF-> 0x00COMMAND_CLASS_METER_REPORT_V4It is sent to the associated nodes when the powerconsumed varies more than 10%Electric meter, Consumed, Watts, Size 4, Precision 1, Value (W)COMMAND_CLASS_DEVICE_RESET_LOCALLY_NOTIFICATIONThe associated nodes are sent when the device isremoved from the Z-Wave network
---|---|---
2| 20| CtrlCOMMAND_CLASS_BASIC_REPORTIt is sent to the associated nodes when the loadchanges state:ON-> 0xFFOFF-> 0x00

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Central LED

Allows to turn ON or OFF the central LED
Size: 1 Byte, Default Value: 0

SettingDescription

0 Turns the LED OFF
255 Turns the LED ON

Parameter 10: On Timed

Sets the delay time to turn on the device
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disables timing
1 – 127 1 second (0x01) to 127 seconds (0x7F) in 1 second resolution
128 – 254 1 minute (0x80) to 127 minutes (0xFE) in 1 minute resolution

Parameter 11: OFF Timed

Sets the time the device stays on
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disables timing
1 – 127 1 second (0x01) to 127 seconds (0x7F) in 1 second resolution
128 – 254 1 minute (0x80) to 127 minutes (0xFE) in 1 minute resolution

Parameter 13: Load Lock

Locks or Unlocks the direct control of the load
Size: 1 Byte, Default Value: 0

SettingDescription

0 Enables the push button to control the load
255 Disables the action of the push button of the load

Parameter 15: Reset default

Resets groups, Z-Wave status, and some or all configurations depending on the configuration value (write only)
Size: 2 Byte, Default Value: 0

SettingDescription

17170 Parameters, except Lock long press are restored to default
39015 Parameters, Groups, and Z-Wave status are restored to default

Parameter 16: Delayed OFF

Sets the delay time to turn off the device
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disables timing
1 – 127 1 second (0x01) to 127 seconds (0x7F) in 1 second resolution
128 – 254 1 minute (0x80) to 127 minutes (0xFE) in 1 minute resolution

Parameter 17: Post Reset State

Controls the state of the load after a reset action
Size: 1 Byte, Default Value: 255

SettingDescription

0 Restart with the relay disabled.
255 Recover the previous state.

Parameter 19: Action when pressing

Controls the behavior of the product when the key is pressed
Size: 1 Byte, Default Value: 0

SettingDescription

0 When short press, device toggles the load
1 When short press, device turns ON the load
2 When short press, device turns OFF the load

Parameter 2: Custom Consumption Limit

Allows to set a power consumption limit in Watts
Size: 2 Byte, Default Value: 0

SettingDescription

0 Disables custom consumption limit
1 – 65535 Sets the power in Watts that is supported

Parameter 20: Identify

Allows to identify a product using its central LED (write only)
Size: 1 Byte, Default Value: 0

SettingDescription

255 the central LED blinks for 5 seconds in order to identify the device

Parameter 21: Charge status

Reports the state of the charge (read only)
Size: 1 Byte, Default Value: 0

SettingDescription

45056 Load is OFF
45057 Load is ON
45312 Load is OFF
45567 Load is ON

Parameter 27: Lock key press

Locks or unlocks the long press on the key
Size: 1 Byte, Default Value: 0

SettingDescription

0 Long press works as described previously
255 Long press from 2 seconds to 30 seconds does not send a Node info. With a

long press above 30 seconds, all parameters except Lock long press are restored to default and device sends a Node info

Parameter 3: Beacon

Enables or disables the beacon function
Size: 1 Byte, Default Value: 0

SettingDescription

0 Disables the beacon function
1 – 99 Sets the intensity of the beacon LEDs

Technical Data

Hardware Platform ZM5202
Device Type On/Off Power Switch
Network Operation Always On Slave
Firmware Version HW: 1 FW: 4.24:68.49
Z-Wave Version 6.51.07
Certification ID ZC10-20016837
Z-Wave Product Id 0x0267.0x0009.0x0000
Neutral Wire Required ok
Supported Meter Type Electric Energy
Switch Type Push Button with Indicator
Firmware Updatable Updatable by Professional/Technician
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info V3
  • Association V2
  • Basic
  • Configuration V2
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Meter V4
  • Powerlevel
  • Switch Binary
  • Version V2
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals