Aibase 4-in-1 Motion Sensor HA-ZW-5SABC Manual

June 8, 2024
Aibase

Aibase

4-in-1 Motion Sensor

SKU: HA-ZW-5SABC

Quickstart

This is a
secure
Alarm Sensor
for
U.S. / Canada / Mexico
.

Please make sure the internal battery is fully charged.

To add this device to your network execute the following action:
Add 4-in-1 Motion Sensorinto a Z-Wave network: a. Let the primary controller go into inclusion mode (If you dont know how to do this, refer to its manual).b. Short Press one time this Z-Button.c. The 4-in-1 Motion Sensor LED will blink, If the inclusion is successful, then LED will keep on 2 seconds. Otherwise, the LED will blink until timeout, in which case you need to repeat the process from step b.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The 4-in-1 motion sensor is designed for using with scenes in home automation systems, integrate motion, light, temperature and humidity sensors, powered by CR123A battery or MicroUSB cable. The Motion Sensor lets you know when movement is detected in a certain area and can trigger different actions in response to that movement (or lack of movement). It also lets you know the ambient temperature and humidity to trigger different actions to make you more comfort. This sensor integrated Z-Wave communication module to connect with Z-Wave gateway, and this device can be adapted to EU(868.42Mhz) or US(908.42MHz).

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Reset 4-in-1 Motion Sensorto factory Default:1. Press and hold the Z-Button for 5 seconds.2. If holding time is more than 5 seconds, the LED will blink fast at acceleration. If reset success 4-in-1 Motion Sensor LED will turn off. When the Z-Button is released, it will send Device Reset Locally Command. Otherwise please repeat step 2.Note:1, This procedure should only be used when the primary controller is inoperable.2, Reset 4-in-1 Motion Sensor to factory default settings.It will set the 4-in-1 Motion Sensor to not in Z-Wave network state; delete the Association setting and restore the Configuration setting to the default.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Add 4-in-1 Motion Sensorinto a Z-Wave network: a. Let the primary controller go into inclusion mode (If you dont know how to do this, refer to its manual).b. Short Press one time this Z-Button.c. The 4-in-1 Motion Sensor LED will blink, If the inclusion is successful, then LED will keep on 2 seconds. Otherwise, the LED will blink until timeout, in which case you need to repeat the process from step b.

Exclusion

Remove 4-in-1 Motion Sensorfrom a Z-Wave network: a. Let the primary controller go into exclusion mode (If you dont know how to do this, refer to its manual).b. Short Press one time this Z-Button.c. The 4-in-1 Motion Sensor LED will keep on, If the remove is successful, then LED will blink 2 seconds. Otherwise, the LED will keep on until timeout, in which case you need to repeat the process from step b.Note: 4-in-1 Motion Sensor will go away Z-Wave SmartStart Inclusion when it is removed from a Z-Wave network.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| Z-Wave Plus Lifeline1. Notification Report.Sensor will send Notification Report when Motion Detection Unknown Location and (Event inactive).2. Multilevel Sensor ReportSensor will send Multilevel Sensor Report (Temperature, humidity, luminance) interval of 2 hours.3. Battery Report.Sensor will send Battery Report when the battery level is low and the battery reports value is 0xFF.4. Device Reset Locally.
---|---|---
2| 5| Send Basic Set when PIR trigger

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 10: Low Battery Power Level

Low Battery Power Level of alarm threshold values: the value range are 10~50 for percentage, so the Battery Low Power level can setting 10%~50%.
Size: 1 Byte, Default Value: 10

SettingDescription

10 – 50 Low Battery Power Level of alarm threshold values

Parameter 100: Set 101 ~ 104 to default.

Set 101 ~ 104 to default.
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 255 Set 101 ~ 104 to default.

Parameter 101: The interval time of sending the temperature reporting

The interval time of sending the temperature reporting. if setting to 0 then the temperature reporting is disabled 1. Valid values: 0x00-0x28DE802. The minimum interval time is 1 minutes. For example, if the value is set to be more than 1 and less than 60, the interval time is 1 minutes, if the value is set to be more than 60 and less than 120, the interval time is 2 minutes.
Size: 4 Byte, Default Value: 7200

SettingDescription

0 the temperature reporting is disabled
1 – 2678400 The interval time of sending the temperature reporting is 31

days2678400 seconds

Parameter 102: The interval time of sending the humidity reporting.

The interval time of sending the humidity reporting. if setting to 0 then the humidity reporting is disabled 1. Valid values: 0x00-0x28DE802. The minimum interval time is 1 minutes. For example, if the value is set to be more than 1 and less than 60, the interval time is 1 minutes, if the value is set to be more than 60 and less than 120, the interval time is 2 minutes.
Size: 4 Byte, Default Value: 7200

SettingDescription

0 the luminance reporting is disabled
1 – 2678400 The interval time of sending the humidity reporting is 31

days2678400 seconds

Parameter 103: The interval time of sending the luminance reporting.

The interval time of sending the luminance reporting. if setting to 0 then the luminance reporting is disabled 1. Valid values: 0x00-0x28DE802. The minimum interval time is 1 minutes. For example, if the value is set to be more than 1 and less than 60, the interval time is 1 minutes, if the value is set to be more than 60 and less than 120, the interval time is 2 minutes.
Size: 4 Byte, Default Value: 7200

SettingDescription

0 the luminance reporting is disabled
1 – 2678400 The interval time of sending the luminance reporting is 31

days2678400 seconds

Parameter 104: The interval time of sending the battery level reporting.

The interval time of sending the battery level reporting. if setting to 0 then the battery level reporting is disabled 1. Valid values: 0x00-0x28DE802. The minimum interval time is 1 minutes. For example, if the value is set to be more than 1 and less than 60, the interval time is 1 minutes, if the value is set to be more than 60 and less than 120, the interval time is 2 minutes.
Size: 4 Byte, Default Value: 86400

SettingDescription

0 the battery level reporting is disabled
1 – 2678400 The interval time of sending the battery level reporting is 31

days2678400 seconds

Parameter 110: Enable 111 ~ 114 temperature/humidity/luminance/ battery

level change reporting.

Enable 111 ~ 114 temperature/humidity/luminance/ battery level change reporting.0 = Unable1 = Enable
Size: 1 Byte, Default Value: 0

SettingDescription

0 Unable
1 Enable

Parameter 111: Configuration temperature change threshold.

Configuration temperature change threshold.Valid values: 1-500(unit 0.1)
Size: 2 Byte, Default Value: 10

SettingDescription

1 – 500 the temperature change threshold value(unit 0.1)

Parameter 112: Configuration humidity change threshold.

Configuration humidity change threshold.Valid values: 1-32(unit %)
Size: 1 Byte, Default Value: 5

SettingDescription

1 – 32 humidity change threshold value(unit %)

Parameter 113: Configuration luminance change threshold.

Configuration luminance change threshold.Valid values: 1-65528(unit lx)
Size: 2 Byte, Default Value: 150

SettingDescription

-32767 – -1 luminance change threshold is 32767 to 65528
0 – 32766 luminance change threshold is 0 to 32766

Parameter 114: Configuration battery level change threshold.

Configuration battery level change threshold.Valid values: 1-100(unit %)
Size: 1 Byte, Default Value: 10

SettingDescription

1 – 100 battery level change threshold value(unit)%

Parameter 12: Turn on/off PIR

Turn on/off PIR 0x0A indicates the highest sensitivity, 0x00 means off PIR detection function.
Size: 1 Byte, Default Value: 10

SettingDescription

0 – 10| 0x0A indicates the highest sensitivity, 0x00 means off PIR detection function.
---|---

Parameter 13: PIR triggers the waiting time value

PIR triggers the waiting time value
Size: 2 Byte, Default Value: 30

SettingDescription

0 Unable
1 Enable

Parameter 14: Whether the BASIC SET command is sent after the PIR is

triggered

Whether the BASIC SET command is sent after the PIR is triggered
Size: 1 Byte, Default Value: 0

SettingDescription

0 Unable
1 Enable

Parameter 15: PIR triggers the correspondence between the value of the

Basic set and the PIR state

PIR triggers the correspondence between the value of the Basic set and the PIR state, When value is 0x00 PIR triggers Send the basic set command 0xff PIR alarm release send the basic set command 0x00, otherwise PIR triggers send the basic set command 0x00 PIR alarm release send the basic set command 0xff.
Size: 1 Byte, Default Value: 0

SettingDescription

0| PIR triggers Send the basic set command 0xff PIR alarm release send the basic set command 0x00
---|---
1| PIR triggers send the basic set command 0x00 PIR alarm release send the basic set command 0xff.

Technical Data

Hardware Platform ZM5101
Device Type Notification Sensor
Network Operation Reporting Sleeping Slave
Firmware Version HW: 3 FW: 0.10
Z-Wave Version 6.81.00
Certification ID ZC10-18066141
Z-Wave Product Id 0x0384.0x0200.0x0009
Supported Notification Types Access ControlLuminance
Sensors Air Temperature
Firmware Updatable Not Updatable
Security V2 S2_UNAUTHENTICATED
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Battery
  • Configuration
  • Device Reset Locally
  • Firmware Update Md V4
  • Manufacturer Specific V2
  • Notification V8
  • Powerlevel
  • Security
  • Security 2
  • Sensor Multilevel V5
  • Supervision
  • Transport Service V2
  • Version V2
  • Wake Up V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals