Siterwell Technology Siterwell Power plug Sensor STW-W3350WU Manual

June 8, 2024
Siterwell Technology

Siterwell Technology

Siterwell Power plug Sensor

SKU: STW-W3350WU

Quickstart

This is a ****

On/Off Power Switch
for
CEPT (Europe)
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
Add the Device (Smart Plug) to ZWave Network1.Make sure the sensor is powered. 2.Set ZWave controller or ZWave gateway into inclusion mode (Refer to the controller or gateway operating manual) 3.Press the button three times within 1.5 second, the device will enter inclusion mode. And the LED will flash on and off with green alternately five times within 2 seconds.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

This product can be included and operated in any ZWave network with other ZWave certified devices from other manufacturers and/or other applications. All nonbattery operated nodes within the network will act as repeaters regardless of vendor to increase reliability of the network.In the front casing, there is button that is used to carry out include, exclude or reset factory default settings on PCB Board.When power is first supplied, the LED will flash on and off with yellow alternately every 1 second intervals within 5 seconds if the detector has not been added a ZWave network, otherwise the LED will flash on and off 5 times with cyan alternately every 300 millisecond. Please get familiar with the terms below before starting the operations.This Plug has function that remembers the relay states, the plug will turn on after power up next time if the plug is turn on before the power cutoff.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Note:to use the reset procedure only when the primary controller is missing or inoperable.Restore the Device (Smart Plug) to Factory Default SettingsReset procedure will delete all information on the ZWave network and ZWave controller or ZWave Gateway, and restore the sensor to factory default settings.1.Make sure the sensor is powered. 2.Press and hold the button more than 10 seconds until the LED blink with red color. 3.Release the button.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Add the Device (Smart Plug) to ZWave Network1.Make sure the sensor is powered. 2.Set ZWave controller or ZWave gateway into inclusion mode (Refer to the controller or gateway operating manual) 3.Press the button three times within 1.5 second, the device will enter inclusion mode. And the LED will flash on and off with green alternately five times within 2 seconds.

Exclusion

Delete the Device (Smart Plug) from ZWave Network1.Make sure the sensor is powered. 2.Set ZWave controller or ZWave gateway into exclusion mode (Refer to the controller or gateway operating manual) 3.Press the button three times within 1.5 second, the device will enter exclusion mode. And the LED will flash on and off with yellow alternately five times within 2 seconds.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1| 5| GROUP 1 is lifeline service that assigned to plug statusON/OFF. It enables the Plug to send reports and readings to ZWave Controller or ZWave Gateway. This Group Support:NOTIFICATION_REPORT_V4 METER_REPORT_V4 SWITCH_BINARY_REPORT DEVICE_RESET_LOCALLY_NOTIFICATION
---|---|---
2| 5| GROUP 2 allows for sending control commands to associated devices such as Siren, relay module, lighting, etc. If current load is over the max current defined in parameter #3, the Plug will send a BASIC_SET (0xFF) to associated devices. When current load is normal, plug will send a BASIC_SET (0x00) to associated devices. This Group Support:BASIC_SET
3| 5| GROUP 3 allows for Send Notification to associated devices in this group. This Group Support: NOTIFICATION_REPORT_V4

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Meter Report Enable

This parameter defines Disable/Enable meter report measure data to controller.
Size: 1 Byte, Default Value: 1

SettingDescription

0 Disable Report
1 Enable Report

Parameter 10: Enable Button On/Off

This parameter defines the button on/off function is enabled or not on the top of the wall plug. This parameter can be configured 0 and 1. If this parameter is set to 1, users can turn on and off the wall plug by pressing the button on the top of the wall plug. If this parameter is set to 0, the wall plug cannot be turned on and off by pressing the button.
Size: 1 Byte, Default Value: 1

SettingDescription

Parameter 2: Set Report Interval

This parameter defines interval time (in seconds) that Meter report data to main controller.
Size: 2 Byte, Default Value: 300

SettingDescription

1 – 65535 s

Parameter 3: Set the upper current threshold.

_This parameter defines maximum current the plug can provide to load that be connected to plug. If the current consumed by load is greater than maximum current, the plug will cut off power, and send NOTIFICATION_EVENT_POWER_MANAGEMENT_OVER_LOADDETECTED to associated devices in lifeline. Red Led will blink every seconds until current is normal (less than Parameter #3). You must remove the loader and turn on the Plug (press the button once) to enable current monitor and clear NOTIFICATION ALARM.This parameter value must be great than #4. If user set this parameter to default by Configure CC, the parameter #4 will be set to default value.
Size: 1 Byte, Default Value: 13

SettingDescription

1 – 16 Ampere

Parameter 4: Set Alarm upper current threshold

This parameter defines maximum current, if the current plug provide to load is great than this parameter, the plug will light yellow LED, but plug cannot cutoff power.This parameter value must be less than parameter #3. If user set this parameter to default by Configure CC, the parameter #3 will be set to default value.
Size: 1 Byte, Default Value: 12

SettingDescription

1 – 3 Ampere

Parameter 5: LED Enable/Disable

This parameter defines the LED indication Function ON/OFF. This parameter can be configured with 0 or 1, where 0 means disable LED indication Function and will always be turnoff, and 1 means enable LED Function.
Size: 1 Byte, Default Value: 1

SettingDescription

Parameter 6: Meter Reporting Setting

This parameter defines by how much current changed must change to be reported to the ZWave Controller or ZWave Gateway, in percents. If the rate of current change ratio is greater than this parameter, the plug will report the results, voltage, current, power and energy, that plug measure to ZWave Controller or ZWave Gateway.
Size: 1 Byte, Default Value: 5

SettingDescription

1 – 100 %

Parameter 7: Remember Relay Status

This parameter defined the relay status if remember or not. If remembered, the plug will restore the relay status last power off when the plug supply power next time.
Size: 1 Byte, Default Value: 1

SettingDescription

0 Dont Remember, the relay will keep OFF when Plug Supply Power
1 emember the Relay Status.

Parameter 8: Time switch Configure

This parameter defines the timer function Enable/Disable. This parameter can be configured with 0 or 1, where 0 means disable time switch function and 1 enable. The time period will be defined in parameter #9.If this parameter is Set to 1, and when turn the plug relay on, the timer in plug start run with time period defined in parameter #9 and the plug will turn the relay off.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Time switch Disable
1 Time switch Enable

Parameter 9: Time switch Configure

This parameter defines the time period that plug time switch off. This parameter can be configured 1 ~ 65535(in minutes). If Parameter #9 is set to 1, and relay is turnon, the relay will be turnoff after delay this parameter.
Size: 2 Byte, Default Value: 150

SettingDescription

1 – 65535 minutes

Technical Data

Hardware Platform ZM5202
Device Type On/Off Power Switch
Network Operation Always On Slave
Firmware Version HW: 65 FW: 3.70
Z-Wave Version 6.51.06
Certification ID ZC10-17085749
Z-Wave Product Id 0x0266.0x0003.0x0350
Supported Meter Type Electric Energy
Supported Notification Types Power Management
Color White
Firmware Updatable Updatable by Manufacturer
Switch Type Push Button
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Basic
  • Configuration
  • Device Reset Locally
  • Manufacturer Specific
  • Meter V4
  • Notification V4
  • Powerlevel
  • Switch All
  • Switch Binary
  • Version V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Siterwell Technology User Manuals

Related Manuals