QUBINO Qubino Flush Dimmer 0-10V ZMNHVD3 Manual

June 8, 2024
QUBINO

Table of Contents

QUBINO

Qubino Flush Dimmer 0-10V

SKU: ZMNHVD3

Quickstart

This is a
secure
Light Dimmer
for
U.S. / Canada / Mexico
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
Connect module to power supply (with temperature sensor connected – if purchased),enable add/remove mode on main controllerauto-inclusion (works for about 5 seconds after connected to power supply) orpress service button S for more than 2 second orpress push button I1 three times within 3s (3 times change switch state within 3 seconds).NOTE1: For auto-inclusion procedure, first set main controller into inclusion mode and then connect module to power supply.NOTE2: When connecting temperature sensor to module that has already been included, you have to exclude module first. Switch off power supply, connect the sensor and re-include the module.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The Qubino Flush Dimmer 0-10V is a universal dimmer with a standard 0-10V output and a multi-function input, which may be a push button or switch, a potentiometer or a 0-10V signal. It also measures power consumption and supports the connection of a digital temperature sensor.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Press push button I1 five times within 3s (5 times change switch state within 3 seconds) in the first 60 seconds after the module is connected to the power supply orpress service button S (only applicable for 24 V SELV supply voltage)for more than 6 second.Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

Connect module to power supply (with temperature sensor connected – if purchased),enable add/remove mode on main controllerauto-inclusion (works for about 5 seconds after connected to power supply) orpress service button S for more than 2 second orpress push button I1 three times within 3s (3 times change switch state within 3 seconds).NOTE1: For auto-inclusion procedure, first set main controller into inclusion mode and then connect module to power supply.NOTE2: When connecting temperature sensor to module that has already been included, you have to exclude module first. Switch off power supply, connect the sensor and re-include the module.

Exclusion

Connect module to power supply bring module within maximum 1 meter (3 feet) of the main controller,enable add/remove mode on main controller,press push button I1 five times within 3s (5 times change switch state within 3 seconds) in the first 60 seconds after the module is connected to the power supply orpress service button S (only applicable for 24 V SELV supply voltage)for more than 6 second.By this function all parameters of the module are set to default values and own ID is deleted.If push button I1 is pressed three times within 3s (or service button S is pressed more than 2 and less than 6 seconds) module is excluded, but configuration parameters are not set to default values. NOTE 1: If the module is included with parameter 1 value 3, 4 or 5 and module reset is done, wait at least 30s before next inclusion.NOTE 2: Please use this procedure only when the network primary controller is missing or otherwise inoperable.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1 1 Z-Wave Plus Lifeline
2 16 Basic On/Off
3 16 Start Level Change/Stop Level Change
4 16 Multilevel Set
5 16 Multilevel Sensor Report (triggered at change of analogue sensor)
6 16 Multilevel Sensor Report (triggered at change of temperature sensor)

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Input 1 switch type

By this parameter the user can set input based on device type (switch, potentiometer, 0-10V sensor,..). NOTE: After parameter change to value 3, 4 or 5 first exclude module (without setting parameters to default value) then wait at least 30s and then re include the module!
Size: 1 Byte, Default Value: 0

SettingDescription

1 Bi-stable switch type
3 0-10V Temperature sensor (regulated output)
4 0-10V Illumination sensor (regulated output)
2 Potentiometer (Flush Dimmer 0-10Vis using set value the last received from

potentiometer or from z-wave controller)
0| Default value – Mono- stable switch type (push button)button quick press turns between previous set dimmer value and zero)
5| 0-10V General purpose sensor (regulated output)

Parameter 10: Activate / deactivate functions ALL ON / ALL OFF

Flush Dimmer 0-10V module responds to commands ALL ON / ALL OFF that may be sent by the main controller or by other controller belonging to the system.
Size: 2 Byte, Default Value: 255

SettingDescription

2 ALL ON active, ALL OFF is not active
255 Default value – ALL ON active, ALL OFF active
0 ALL ON is not active, ALL OFF is not active
1 ALL ON is not active, ALL OFF active

Parameter 11: Automatic turning off output after set time

Turns off the output after set time.
Size: 2 Byte, Default Value: 0

SettingDescription

0 Default value – Auto OFF disabled
1 – 32536 = 1second – 32536 seconds Auto OFF enabled with define time, step

is 1 second

Parameter 110: Temperature sensor offset settings

Set value is added or subtracted to actual measured value by sensor.
Size: 2 Byte, Default Value: 32536

SettingDescription

32536 Default value – offset is 0.0 degrees celsius
1 – 100 Value from 0.1 degrees celsius to 10.0 degrees celsius is added to

actual measured temperature
1001 – 1100| Value from -0.1 degrees celsius to -10.0 degrees celsius is subtracted to actual measured temperature

Parameter 12: Automatic turning on output after set time

Turns on the output after set time.
Size: 2 Byte, Default Value: 0

SettingDescription

0 Default value – Auto ON disabled
1 – 32535 = 1second – 32535 seconds Auto ON enabled with define time, step is

1 second

Parameter 120: Digital temperature sensor reporting

Digital temperature sensor reportingIf digital temperature sensor is connected, module reports measured temperature on temperature change defined by this parameter. Available configuration parameters (data type is 1 Byte DEC):default value 5 = 0,5C change0 – Reporting disabled1 – 127 = 0,1C – 12,7C, step is 0,1C
Size: 1 Byte, Default Value: 5

SettingDescription

5 Default value = 0,5 degrees celsius change
0 Reporting disabled
1 – 127 0,1 degrees celsius – 12,7 degrees celsius, step is 0,1 degrees

celsius

Parameter 140: Input I1 Sensor reporting

Input I1 Sensor reportingIf analogue sensor is connected, module reports measured value on change defined by this parameter.
Size: 2 Byte, Default Value: 5

SettingDescription

5 Default value = 0,5 change
0 Reporting disabled
1 – 10000 = 0,1 – 1000 step is 0,1

Parameter 141: Input I1 0-10V reporting threshold

Parameter is associated with Association group No. 2. Below this value, the Association No. 2 will report Basic Set 0xFF and above this value will report Basic Set 0xFF. Basic Set is reported only, when the input value changes for more than 10% (1V).
Size: 1 Byte, Default Value: 5

SettingDescription

5 Default value = 5 (0,5V)
1 – 100 0,1 – 10V

Parameter 143: Minimum sensor range value

Value that must correspond to minimum sensor range value. Valid only if parameter 1 is set to values 3, 4 or 5). Available configuration parameters (data type is 2 Byte DEC):default value 0 = 0.0C / 0Lux / 0.0%rh0 – 10000value from 0 to 1000(resolution 0,1)1000120000value from -0,1 to-1000(resolution 0,1)NOTE: Minimum value must not be higher than maximum value!
Size: 2 Byte, Default Value: 0

SettingDescription

0 Default value 0 = 0.0 degrees celsius / 0Lux / 0.0%rh
0 – 10000 Value from 0 to 1000(resolution 0,1)
10001 – 20000 Value from -0,1 to-1000(resolution 0,1)alue from -0,1

to-1000(resolution 0,1)

Parameter 144: Maximum sensor range value

Value that must correspond to maximum sensor range value. Valid only if parameter 1 is set to values 3, 4 or 5). NOTE: Maximum value must not be lower than minimum value!
Size: 2 Byte, Default Value: 1000

SettingDescription

10001 – 20000 Value from -0,1 to-1000(resolution 0,1)
1000 Default value – 1000 = 100.0 degrees celsius / 100Lux / 100%rh
0 – 10000 Value from 0 to 1000(resolution 0,1)

Parameter 21: Enable/Disable Double click function

If Double click function is enabled, a fast double click on the push button will set dimming power at maximum dimming value. Valid only if input is set as mono-stable (push button).
Size: 1 Byte, Default Value: 0

SettingDescription

0 Default value – Double click disabled
1 Double click enabled

Parameter 250: Unsecure / Secure Inclusion

A Flush dimmer supports secure and unsecure inclusion. Even if the controller does not support security command classes, a dimmer could be included as unsecure and keep all the functionality.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Default value – Unsecure Inclusion
1 Secure Inclusion

Parameter 30: Saving the state of the device after a power failure

Based on the parameter settings the stores/does not store the last value of the output after power failure.
Size: 1 Byte, Default Value: 0

SettingDescription

0| Default value – Flush Dimmer 0-10V module saves its state before power failure (it returns to the last position saved before a power failure)
---|---
1| Flush Dimmer 0-10V module does not save the state after a power failure, it returns to "off" position

Parameter 52: Auto or manual selection

This parameter is influencing on the software only when the value of parameter number 1 is set to value 3, 4 or 5. In manual mode regulation (how the input influence on output) is disabled.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Default value – Manual
1 Auto

Parameter 53: PID value inside deadband

NOTE: When ZERO PID inside deadband is forced to zero. LASTVALUE means that PID remains on same level as was before entering into deadband.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Default value – PID value equal ZERO
1 PID value set to LAST VALUE

Parameter 54: PID deadband

This parameter defines the zone where PID is not active. If the temperature difference between actual and setpoint is bigger than PID deadband, then the PID will start to regulate the system, otherwise the PID is zero or fixed.
Size: 1 Byte, Default Value: 1

SettingDescription

1 Default value 1 (1%)
0 – 100 0 – 100%, step is 1%

Parameter 55: Integral sampling time

Parameter defines the time between samples. On each sample the controller capture difference between SP-act.
Size: 1 Byte, Default Value: 5

SettingDescription

5 Default value 5 (5s)
0 – 127 = 0s to 127s, step is 1s

Parameter 56: P parameter

The error is multiplied by a negative (for reverse action) proportional constant P, and added to the current output. P represents the band over which a controller’s output is proportional to the error of the system. E.g. for a heater, a controller with a proportional band of 10 deg C and a setpoint of 100 deg C would have an output of 100% up to 90 deg C, 50% at 95 Deg C and 10% at 99 deg C. If the temperature overshoots the setpoint value, the heating power would be cut back further. Proportional only control can provide a stable process temperature but there will always be an error between the required setpoint and the actual process temperature.
Size: 2 Byte, Default Value: 100

SettingDescription

0 – 1000 P value, step is 1
100 Default value

Parameter 57: I parameter

The error is integrated (averaged) over a period of time, and then multiplied by a constant I, and added to the current control output. I represents the steady state error of the system and will remove setpoint / measured value errors. For many applications Proportional + Integral control will be satisfactory with good stability and at the desired setpoint.
Size: 2 Byte, Default Value: 1

SettingDescription

1 Default value
0 – 1000 I value, step is 1

Parameter 58: D parameter

The rate of change of the error is calculated with respect to time, multiplied by another constant D, and added to the output. The derivative term is used to determine a controller’s response to a change or disturbance of the process temperature (e.g. openingan oven door). The larger the derivative term, the more rapidly the controller will respond to changes in theprocess value.
Size: 2 Byte, Default Value: 1

SettingDescription

1 Default value
0 – 1000 D value, step is 1

Parameter 60: Minimum dimming value

_NOTE: The minimum level may not be higher than the maximum level! 1% min. dimming value is defined by Z-Wave multilevel device class. When the switch type is selected as Bi-stable, it is not possible to dim the value between min and max. If Switch_multilevel_set is set to the value 0, the output is turned OFF. If Switch_multilevelset is set to the value 1, the output is set to the minimum diming value.
Size: 1 Byte, Default Value: 1

SettingDescription

1 Default value= 1% (minimum dimming value)
1 – 98 = 1% – 98%, step is 1%. Minimum dimming values is set by entered value

Parameter 61: Maximum dimming value

NOTE: The maximum level may not be lower than the minimum level! 99% max. dimming value is defined by Z-Wave multilevel device class. When the switch type is selected as Bi-stable, it is not possible to dim the value between min and max.
Size: 1 Byte, Default Value: 99

SettingDescription

2 – 99| = 2% – 99%, step is 1%. Maximum dimming values is set by entered value.
---|---
99| Default value = 99% (Maximum dimming value)

Parameter 65: Dimming time (soft on/off)

Set value means time of moving the Flush Dimmer 0-10V between min. and max. dimming values by short press of push button I1 or controlled through UI (BasicSet).
Size: 2 Byte, Default Value: 100

SettingDescription

100 Default value 100 = 1s
50 – 255 = 500 mseconds – 2550 mseconds (2,55s), step is 10 mseconds

Parameter 66: Dimming time when key pressed

Time of moving the Flush Dimmer 0-10V between min. and max dimming values by continues hold of push button I1 or associated device.
Size: 2 Byte, Default Value: 3

SettingDescription

3 Default value 3 = 3s
1 – 255 = 1 second – 255 seconds

Parameter 67: Ignore start level

This parameter is used with association group 3.A receiving device SHOULD respect the start level if the Ignore Start Level bit is 0. A receiving device MUST ignore the start level if the Ignore Start Level bit is 1.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Default value – Respect start level
1 Ignore start level

Parameter 68: Dimming duration

This parameter is used with association group 3.The Duration field MUST specify the time that the transition should take from the current value to the new target value. A supporting device SHOULD respect the specified Duration value.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Default value – dimming duration according to parameter 66
1 – 127 From 1 to 127 seconds

Technical Data

Hardware Platform ZM5202
Device Type Light Dimmer Switch
Network Operation Always On Slave
Firmware Version HW: 1 FW: 2.03:02.03
Z-Wave Version 6.51.08
Certification ID ZC10-17025448
Z-Wave Product Id 0x0159.0x0001.0x0053
Supported Meter Type Electric Energy
Sensors Air Temperature
Electric Load Type Dimmable LEDELV (Electronic)Incandescent
Switch Type Push Button
Color Light Blue
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info V2
  • Association V2
  • Basic
  • Configuration
  • Device Reset Locally
  • Manufacturer Specific V2
  • Multi Channel Association V3
  • Multi Channel V4
  • Powerlevel
  • Security
  • Sensor Multilevel V7
  • Switch All
  • Switch Binary
  • Switch Multilevel V3
  • Version V2
  • Zwaveplus Info V2

Controlled Command Classes

  • Basic
  • Switch Multilevel V3

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals