FortrezZ LLC MIMO2+ MIMO2+ Manual
- June 8, 2024
- FortrezZ LLC
Table of Contents
- FortrezZ LLC
- MIMO2+
- SKU: MIMO2+
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: Relay 1 Configuration
- Parameter 10: SIG 2 Lower Threshold, High
- Parameter 11: SIG 2 Lower Threshold, Low
- Parameter 12: SIG 2 Upper Threshold, High
- Parameter 13: SIG 2 Upper Threshold, Low
- Parameter 2: Relay 2 Configuration
- Parameter 3: SIG 1 Multilevel Trigger Settings
- Parameter 4: SIG 1 Lower Threshold, High
- Parameter 5: SIG 1 Lower Threshold, Low
- Parameter 6: SIG 1 Upper Threshold, High
- Parameter 7: SIG 1 Upper Threshold, Low
- Parameter 9: SIG 2 Multilevel Trigger Settings
- Technical Data
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
FortrezZ LLC
MIMO2+
SKU: MIMO2+
Quickstart
This is a ****
Multilevel Sensor
for
U.S. / Canada / Mexico.
To run this device please connect it to your mains power supply.
To add this device to your network execute the following action:
- Activate inclusion mode on your Z-wave controller.2) Press the program button once.3) LED will blink 2 times quickly to indicate “in network” status.
Please refer to the
Manufacturers
Manual
for more information.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
The MIMO2+ module provides two voltage inputs and two relay outputs (either can be wired normally open or normally closed). Z-Wave messages can be used to read the inputs and control the outputs. The inputs are very configurable for different trigger conditions and can even be mapped to control the outputs. The module includes a button for Z-Wave inclusion/exclusion and an LED for various status indications. The functionality of the SIG1 and SIG2 inputs is:- Analog Triggering: Various trigger conditions can be set for high-to-low and low-to-high transitions. This provides great flexibility for capturing digital or analog events in a wide variety of applications. The trigger status can be automatically sent to the controller.- Associations: Each input can be associated with up to two other Z-Wave devices, so that, for example, an associated device will automatically turn on (or off) based on the occurrence of a trigger event.Voltage Reporting: The analog input voltage levels can also be sent to the controller.The physical outputs are relays that are typically activated by Z-Wave commands. However, the user can override Z-Wave control by configuring the input trigger conditions to be mapped to the output relays via logical AND/OR functions.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
Device Reset to Factory DefaultsPress and hold the program button for 15 seconds and then release. This can be done while the device is either in or out of a network. CAUTIONWhen this is done in-network, the device will no longer be in the network and all configurations and associations will be set to default. Please use this procedure only when your network primary controller is missing or otherwise inoperable.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
- Activate inclusion mode on your Z-wave controller.2) Press the program button once.3) LED will blink 2 times quickly to indicate “in network” status.
Exclusion
- Activate exclusion mode on your Z-wave controller.2) Press the program button once.3) LED will blink 4 times quickly to indicate “in network” status.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1 | 2 | Z-Wave Plus Lifeline |
---|---|---|
2 | 2 | SIG1 (Basic Set) – Upon change of trigger |
3 | 2 | SIG2 (Basic Set) – Upon change of trigger |
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: Relay 1 Configuration
This sets the configuration of Relay 1 to be latching, or to toggle back to
Off/Open after a specified amount of time.(Signed value in the range 0 to 255;
convert values over 127 to a signed 1 byte value, or if your controller
supports entering the value in hexadecimal you may use the hex value.)
Size: 1 Byte, Default Value: 0
SettingDescription
0| The relay will remain latched in the position it is commanded to (open/off
or closed/on)
---|---
-128 – 127| Set this value to the amount of time in 100ms increments for the relay to remain closed/on before automatically returning to the open/off state.For example, a value of 2 = 0.2 Seconds.
Parameter 10: SIG 2 Lower Threshold, High
(must be less than Upper Threshold Low and greater than Lower Threshold
Low)Reference technical appendix triggering notes for visual’s.(Signed value
in the range 0 to 255; convert values over 127 to a signed 1 byte value, or if
your controller supports entering the value in hexadecimal you may use the hex
value.)
Size: 1 Byte, Default Value: -112
SettingDescription
-128 – 127 | Set this value to set the lower threshold high number |
---|
Parameter 11: SIG 2 Lower Threshold, Low
SIG 2 Lower Threshold, LowReference technical appendix triggering notes for
visual’s.(Signed value in the range 0 to 255; convert values over 127 to a
signed 1 byte value, or if your controller supports entering the value in
hexadecimal you may use the hex value.)
Size: 1 Byte, Default Value: -128
SettingDescription
-128 – 127 | Set this to set the lower threshold low number. |
---|
Parameter 12: SIG 2 Upper Threshold, High
SIG 2 Upper Threshold, HighReference technical appendix triggering notes for
visual’s.(Signed value in the range 0 to 255; convert values over 127 to a
signed 1 byte value, or if your controller supports entering the value in
hexadecimal you may use the hex value.)
Size: 1 Byte, Default Value: -1
SettingDescription
-128 – 127 | Set this to set the upper threshold, high number |
---|
Parameter 13: SIG 2 Upper Threshold, Low
(Must be greater than lower Threshold High and less than Upper Threshold
High)Reference technical appendix triggering notes for visual’s.(Signed value
in the range 0 to 255; convert values over 127 to a signed 1 byte value, or if
your controller supports entering the value in hexadecimal you may use the hex
value.)
Size: 1 Byte, Default Value: -2
SettingDescription
-128 – 127 | Set this to set the upper threshold low number |
---|
Parameter 2: Relay 2 Configuration
This sets the configuration of Relay 2 to be latching, or to toggle back to
Off/Open after a specified amount of time.(Signed value in the range 0 to 255;
convert values over 127 to a signed 1 byte value, or if your controller
supports entering the value in hexadecimal you may use the hex value.)
Size: 1 Byte, Default Value: 5
SettingDescription
0| The relay will remain latched in the position it is commanded to (open/off
or closed/on)
---|---
-128 – 127| Set this value to the amount of time in 100ms increments for the relay to remain closed/on before automatically returning to the open/off state.For example, a value of 2 = 0.2 Seconds.
Parameter 3: SIG 1 Multilevel Trigger Settings
b7: Trigger Between Thresholds (1=true)b6: Periodic Sends (=0) or Send when
Change-of-Trigger (=1)b5-b0: Periodic Send Interval for Lifeline (30s
resolution, 0=no periodic sends)Reference technical appendix triggering notes
for visual’s.(Signed value in the range 0 to 255; convert values over 127 to a
signed 1 byte value, or if your controller supports entering the value in
hexadecimal you may use the hex value.)
Size: 1 Byte, Default Value: -88
SettingDescription
-128 – 127 | Set this value to trigger between thresholds |
---|
Parameter 4: SIG 1 Lower Threshold, High
(must be less than Upper Threshold Low and greater than Lower Threshold
Low)Reference technical appendix triggering notes for visual’s.(Signed value
in the range 0 to 255; convert values over 127 to a signed 1 byte value, or if
your controller supports entering the value in hexadecimal you may use the hex
value.)
Size: 1 Byte, Default Value: -112
SettingDescription
-128 – 127 | Set this value to set the lower threshold high number |
---|
Parameter 5: SIG 1 Lower Threshold, Low
SIG 1 Lower Threshold, LowReference technical appendix triggering notes for
visual’s.(Signed value in the range 0 to 255; convert values over 127 to a
signed 1 byte value, or if your controller supports entering the value in
hexadecimal you may use the hex value.)
Size: 1 Byte, Default Value: -128
SettingDescription
-128 – 127 | Set this to set the lower threshold low number. |
---|
Parameter 6: SIG 1 Upper Threshold, High
SIG1 Upper Threshold, HighUse this to set the upper threshold High
number.Reference technical appendix triggering notes for visual’s.(Signed
value in the range 0 to 255; convert values over 127 to a signed 1 byte value,
or if your controller supports entering the value in hexadecimal you may use
the hex value.)
Size: 1 Byte, Default Value: -1
SettingDescription
-128 – 127 | Set this to set the upper threshold, high number |
---|
Parameter 7: SIG 1 Upper Threshold, Low
(Must be greater than lower Threshold High and less than Upper Threshold
High)Reference technical appendix triggering notes for visual’s.(Signed value
in the range 0 to 255; convert values over 127 to a signed 1 byte value, or if
your controller supports entering the value in hexadecimal you may use the hex
value.)
Size: 1 Byte, Default Value: -2
SettingDescription
-128 – 127 | Set this to set the upper threshold low number |
---|
Parameter 9: SIG 2 Multilevel Trigger Settings
b7: Trigger Between Thresholds (1=true)b6: Periodic Sends (=0) or Send when
Change-of-Trigger (=1)b5-b0: Periodic Send Interval for Lifeline (30s
resolution, 0=no periodic sends)Reference technical appendix triggering notes
for visual’s.(Signed value in the range 0 to 255; convert values over 127 to a
signed 1 byte value, or if your controller supports entering the value in
hexadecimal you may use the hex value.)
Size: 1 Byte, Default Value: -88
SettingDescription
-128 – 127 | Set this value to trigger between thresholds |
---|
Technical Data
Hardware Platform | ZM5202 |
---|---|
Device Type | Multilevel Sensor |
Network Operation | Always On Slave |
Firmware Version | HW: 5 FW: 2.08 |
Z-Wave Version | 6.51.08 |
Certification ID | ZC10-16075155 |
Z-Wave Product Id | 0x0084.0x0463.0x0204 |
Sensors | Motion/No Motion (Binary)Open/Closed (Binary) |
Firmware Updatable | Updatable by Consumer by RF |
Switch Type | Dry Contact |
Frequency | XXfrequency |
Maximum transmission power | XXantenna |
Controlled Command Classes
- Basic
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>