novus N323R Temperature Controller Instruction Manual
- June 8, 2024
- Novus
Table of Contents
TEMPERATURE CONTROLLER
N323R
OPERATING MANUAL V1.8x L
N323R Temperature Controller
The N323R is a Refrigeration controller designed to control the temperature of
refrigeration cases and coldrooms, embedding several specialized functions for
best system performance. The N323R can read two temperature probes (controller
and defrost probes) and has three relay outputs for controlling the
compressor, the defrost and the fan.
The controller can be ordered with optional features such as to comply with
the application’s requirements. The label on the instrument housing shows the
complete instrument configuration.
SPECIFICATIONS
PROBE INPUT: ………………….. 2 Thermistor NTC
…………………………………………………. Type 10 kΩ @ 25 °C
…………………………………………………. Range: -50 to 120 °C (-58 to 248°F)
………………………………………………… Accuracy: 0.6 °C (1.1 °F)
Note: The sensors come with the equipment. Its operating range is limited
to -30 to +105 °C (–222 to +221 °F). It has cable of 3 m in length, 2 x 0.5
mm², and can be extended up to 200 meters. Maximum error in the
interchangeability of original NTC sensors: 0.75 °C (33.35 °F). This error can
be eliminated through the offset parameter of the equipment.
Measurement Resolution: ……………….. 0.1° from -19.9º to 199.9°
…………………………………………………………….. 1° elsewhere
Note: The equipment keeps its precision all over the range, despite the
lack of display resolution in a part of the range does not allow its
visualization.
OUTPUT1: ………………….. Relay SPDT; 1 HP 250 Vac / 1/3 HP 125 Vac (16 A
Resistive)
……………………………………….. Optionally: Pulse, 5 Vdc, 25 mA max.
OUTPUT2: …….. Relay SPST-NA, 3 A / 250 Vac (General use); 5 A / 250 Vac
(Resistive)
OUTPUT3: ………………. SPST-NA, 3 A / 250 Vac (General use); 5 A / 250 Vac
(Resistive)
POWER SUPPLY:
Voltage: ………………………………… 100 to 240 Vca/dc ±10 %
Optionally:…………………………….. 24 V (12 to 30 Vdc)
Mains frequency: ………………….. 50~60 Hz
Power consumption: ……………..5 VA
DIMENSIONS:
Width x Height x Depth: ……… 75 x 33 x 75 mm
Panel cut-out: ……………………….. 70 x 29 mm
Weight: …………………………………. 100 g
ENVIRONMENT:
Operating temperature: ………… 0 to 40 ºC (32 to 104 ºF)
Storage temperature: …………….-20 to 60 ºC (-4 to 140 ºF)
Relative humidity: ………………… 20 to 85 %RH
Housing: Polycarbonate UL94 V-2;
Protection: Front panel: IP65, Box: IP42
Suitable wiring: Up to 4.0 mm²
RS-485 digital communication, RTU MODBUS protocol (optional)
Serial interface not isolated from input circuitry.
Serial interface isolated from input circuitry, except in 24 V powered model.
INSTALLATION
It is important to follow the recommendations below:
- Signal wires should be installed in grounded conduits and away from power or contactor wires.
- The instrument should have its own power supply wires that should not be shared with electrical motors, coils, contactors, etc.
- Installing RC filters (47 R and 100 nF, series combination) is strongly recommended at contactor coils or any other inductor.
- Use protection devices like circuit breakers and fuses.
ELECTRICAL WIRING
Fig. 1 below shows the controller connections to sensor, mains and outputs.
- The serial communication interface is optional.
OPERATION
The controller requires the internal parameters to be configured according to the intended use for the instrument. The parameters are organized in 4 groups or levels:
Level | Function |
---|---|
0 | Temperature measurement |
1 | Setpoint Adjustment |
2 | Configuration |
3 | Calibration |
Upon power-up, the N323R display shows for 1 second its firmware version. This
information is useful when consulting the factory.
Then, the temperature measured by the sensor is shown on the display. This is
the parameter level 0 (temperature measurement level).
To access level 1, press for 1 second until the “ ” message shows up. Pressing
again to go back to level 0.
To access level 2 of parameters, press for 2 seconds until the “ ” message is
shown. Release the key to remain in this level. Each new pressing on the key
will advance to the next parameter in that level. At the end of the level, the
controller returns to the first level (0). Use the and keys to alter a
parameter value.
Notes:
- A parameter configuration is saved when the key is pressed to advance to the next parameter in the cycle. The configuration is stored in a non-volatile memory, retaining its value when the controller is de- energized.
- If no keyboard activity is detected for over 20 seconds, the controller saves the current parameter value and returns to the measurement level.
- While in the temperature measurement level, a momentary pressing on the key will show the Probe 2 temperature (evaporator temperature)
Level 1 – Setpoint Adjustment
In this level only the Setpoint ( ) parameters are available, alternating the
names with their respective values. Adjust the desired temperature for each
setpoint clicking on the and keys.
Set Point| Case of coldroom temperate adjustment. value is limited to the
values programmed in and SPk in the programming level (Parameter
configuration, level 2).
---|---
Level 2 – Configuration – Parameters configuration Level
Contains the configuration parameters to be defined by the user, according to
the system’s requirements. Use and keys to set the value. The display
alternates the parameter name and respective value.
Unit| Temperature Unit. Selects display indication for degrees Celsius or
Fahrenheit
Temperature Celsius. (factory default)
Temperature in degrees Fahrenheit.
---|---
Offset Probe 1| Probe 1 Offset – Offset value to be added to the sensor 1
measured temperature such as to perform fine adjustments to the value showed
on the display (after sensor replacement, for instance, if required).
Range: ± 0.1 to 10.0 degrees.
Offset sensor 2| Probe 2 Offset – Offset value to be added to the sensor 2
measured temperature to perform fine adjustments to the value showed on the
display (after sensor replacement, for instance, if required).
Range: ± 0.1 to 10.0 degrees.
SP Low Limit| SP Low Limit – Lower range for . must be programmed with a lower
value than .
SP High Limit| SP High Limit – Upper range for . must be greater than .
Histeresis| OUTPUT 1 Hysteresis: defines the differential range between the
temperature value at which the OUTPUT is turned on and the value at
which it is turned off. In degrees.
Control| Defines the output position for the refrigeration relay.
Refrigeration at OUTPUT1 / Defrost at OUTPUT2. (factory default)
Refrigeration at OUTPUT2 / Defrost at OUTPUT1.
Delay| Delay time to start control. Upon power-on, control OUTPUT 1 is kept
off until the time programmed in is elapsed. Its usage is intended to prevent
multiple compressors to start simultaneously after the turn-on of a system
with several controllers. Value in seconds, 0 to 250 s.
on time| On time – Defines the minimum on time for refrigeration output. Once
turned on, OUTPUT 1 remains so for at least the time programmed in . This
parameter is intended for refrigeration systems where increased compressor
life is desired. Value in seconds, 0 to 999 s.
Off time| Off time – Defines the minimum off time for control OUTPUT 1. Once
OUTPUT 1 is turned off, it remains so for at least the time programmed in .
This parameter is intended for refrigeration systems where longer compressor
life is desired. Value in seconds, 0 to 999 s.
Defrost Interval| Interval time between defrost cycles. Adjustable from 0 to
999 minutes. During this time, the defrost output remains off.
disables this function (no defrost cycles)
Defrost time| Defrost duration. Interval time during which the defrost output
remains on.
Value in minutes, 1 to 999.
defrost Compressor| Compressor output behavior during the defrost cycle:
Always off;
Always on ;
Compressor output works normally, turning on and off to maintain the
temperature.
| Temperature for finalizing the defrost cycle – evaporator temperature value
as measured by sensor 2 which terminates the defrost cycle, regardless of the
time configured in .
Range:–50 to +120 degrees (-58 to 248°F).
NOTE: the defrost cycle will not initiate if the evaporator temperature
is the value defined in this parameter.
| Drain down time – This parameter sets the time interval for keeping the
outputs off to allow optimum drying of the evaporator.
Value in minutes, 0 to 999.
| Evaporator temperature for liberating the fan – after defrost and water
draining, the refrigeration is turned on. To keep warm air from circulating in
the system, demanding more energy to lower the temperature, the N323R can be
configured to maintain the fan output off until the temperature cools below
the value defined in .
Range: : –50 to 120 °C (-58 to 248°F)
| Fan maximum delay after draining – to assure product integrity, the fan
output will be unconditionally turned on after the time programmed in ,
regardless of the fact that the evaporator temperature may not have reached
the temperature value defined in .
Value in minutes, 0 to 999.
| Fan behavior during refrigeration.
Fan is active only when the compressor is on.
Fan is active during the complete refrigeration cycle, even when the
compressor is turned off.
| Fan behavior during defrost.
Fan is off during the defrost cycle.
Fan is active during the defrost cycle.
| Fan deactivation due to evaporator heating – evaporator temperature that
turns the Fan off when the evaporator heats up (above temperature defined in
), improving system efficiency and protecting the compressor. The fan is
allowed to turn on again when the temperature drops 2 degrees below the value
defined in this parameter.
| Compressor function during a probe failure: This parameter fixes the
compressor operating mode in the event of the main probe failure.
Compressor is deactivated when probe 1 is in error.
Compressor is activated when probe 1 is in error
defrost hold| Defrost hold time (temperature indication hold): This is the
time interval following the end of the defrost cycle for the controller to
display actual control temperature. During the defrost cycle and the time
defined by , the display will be showing the last measured temperature prior
to the start of the defrost cycle.
: function disabled (shows actual temperature during the defrost cycle);
1 to 250 : Time interval after the end of defrost for the display to show the
actual control temperature. In minutes.
Address| Address – Controllers with the optional RS485 Modbus RTU
communication interface have the parameter at the Configuration
level. Set a unique Modbus address for each equipment connected to the
network. Address range is from 1 to 247.
Level 3 – Calibration level
The controller is factory calibrated. The following parameters should be
accessed only by experienced personnel. To enter this cycle, the key must be
kept pressed for 4 seconds.
Don’t press the and keys if you are not sure of the calibration procedures.
Just press the key a few times until the temperature measurement level is
reached again.
| Password – Enter the correct password to unlock write operations for the
parameters in the following levels.
---|---
| Calibration low input 1 – Zero value of the input 1. It adjusts the lower
measurement range of Probe 1.
| Calibration High input 1 – Gain calibration. It adjusts the full scale
measurement range of the Probe 1.
| Calibration low input 2 – Zero value of the input 2. It adjusts the lower
measurement range of the Probe 2.
| Calibration High input 2 – Gain calibration. It adjusts the full scale
measurement range of the Probe 2.
| Factory Calibration – Restores factory calibration parameters. The value 1
restores the calibration parameters to the factory values.
| Protection – Defines the levels of parameters that will be password
protected. See “Configuration Protection Usage” for details.
| Password Change – Allows changing the current password to a new one. Values
from 1 to 999.
| Serial number – First part of the instrument serial number.
| Serial number – Second part of the instrument serial number.
| Serial number – Third part of the instrument serial number.
CONTROLLER OPERATION
The controller turns on and off the compressor output such as to maintain the
temperature at the selected Setpoint. The front panel display shows the symbol
whenever the compressor is active.
Defrost
Function to eliminate the ice accumulated on the evaporator, for improving
system efficiency. The duration and interval of the defrost cycles are user
configurable. However, it may be unconditionally terminated depending on the
evaporator temperature as measured by Probe 2 (refer to the parameter)
The defrost can be achieved by: 1) compressor deactivation; 2) electrical
heater or 3) heat pump inversion.
In the first case, the refrigeration is turned off and the defrost happens
naturally. In the second case the defrost output drives an electrical
resistance to generate heat and so melt the ice. In this mode, the compressor
output is also deactivated. In the third case, heat pump inversion, the
compressor is kept active and the defrost output commands the valve that
inverts the heat cycle.
During defrost, the case of coldroom temperature may be forced to reflect the
last temperature measured prior to entering the defrost cycle (refer to the
parameter).
The and parameters define, respectively, the time interval between defrosts
and the duration of the defrost cycle. The controller display shows the symbol
to indicate that a defrost cycle is in progress.
Manual defrost: The key allows that a defrost cycle be initiated of
terminated immediately. Pressing this key for 3 seconds will toggle the
current defrost status.
Definition of the evaporator temperature that terminates the defrost. (
parameter)
- Wait for ice building on the evaporator;
- Start a defrost cycle manually;
- Visually monitor the evaporator until there is no more ice on it.
- Check the Probe 2 temperature (momentary press on the key). This is the correct temperature setting for the parameter.
CONFIGURATION PROTECTION
A protection system to avoid unwanted changes to the controller parameters is implemented. The level of protection can be selected from partial to full. The following parameters are part of the protection system:
| When this parameter is presented, the correct password must be entered to
allow changes of parameters in the following levels.
---|---
| Defines the level of parameters that will be password protected:
1 – Only calibration level is protected (factory configuration);
2 – Calibration and Configuration levels are protected;
3 – All levels are protected – calibration, Configuration and setpoints.
| Parameter for definition of a new password. Since it is located in the
calibration level, can only be changed by a user that knows the current
password. Valid passwords are in the range 1 to 999.
CONFIGURATION PROTECTION USAGE
The parameter is displayed before entering a protected level. If the correct
password is entered, parameters in all following levels can be changed. If
wrong or no password is entered, parameters in the following levels will be
read only.
Important notes:
- After five consecutive attempts to enter a wrong password, new tentative will be blocked for the next 10 minutes. If the current valid password is unknown, the master password can be used only to define a new password for the controller.
- The password for a brand new device is 111.
MASTER PASSWORD
The master password allows user to define a new password for the controller,
even if the current password is unknown. The master password is based in the
serial number of the controller, and calculated as following:
[ 1 ] + [ higher digit of SN2 ] + [ higher digit of SN1 ] + [ higher digit of
SN0 ] for example the master password for the device with serial number 97123
465 is: 1 9 3 6 as follows: 1 + = 97; = 123; = 465 = 1 9 3 6
How to use the master password:
- Enter the master password value at prompt.
- Go to parameter and enter the new password, which must not be zero (0).
- Now you can use this new password to access all controller parameters with modify rights.
ERROR MESSAGES
Probe measurement errors force the controller outputs to be turned off. The cause for these errors may have origin in a bad connection, sensor defect (cable or element) or system temperature outside the sensor working range. The display signs related to measurement errors are shown below
| Measured temperature exceeded maximum allowed range for the sensor. Broken
Pt100 or T/C. Short circuited NTC sensor.
---|---
| Measured temperature is below minimum measurement range of the sensor. Short
circuited Pt100 or T/C. Broken NTC.
WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.