WEINTEK cMT3072XHT HMI Operator Panel Instruction Manual
Installation and Startup Guide
This document covers the installation of cMT3072XHT Series HMI, for the detailed specifications and operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all warnings, precautions, and instructions on the device carefully before use.
Install Environment:
NEMA Rating | The HMI product is NEMA 4 rated (Indoor Only). |
---|---|
Electrical Environment | The HMI product has been tested to conform to European |
CE requirements. This means that the circuitry is designed to resist the
effects of electrical noise. This does not guarantee noise immunity in severe
cases. Proper wire routing and grounding will insure proper operation.
Environmental Considerations|
- Make sure that the displays are installed correctly and that the operating limits are followed. Avoid installing units in environments where severe mechanical vibration or shocks are present.
- Do not operate the unit in areas subject to explosion hazards due to flammable gases, vapors or dusts.
- Do not install the unit where acid gas, such as SO2 exists.
- This device should be mounted in the vertical position and for use on the flat surface enclosure.
- For use in Pollution Degree 2 Environment and dry location.
- Relative Humidity: 10% — 90% (non-condensing)
Cleaning Considerations| Clean the device using dry cloths. Do not use liquid
or spray detergents for cleaning.
IP Rating| IP 66
Warning| Protection impairment if used in a manner not specified by the
manufacturer. de Deficit protection si utilise d’une maniere non specifiee par
le fabricant.
Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it fall may cause damage.
The package includes:
(1) Installation Instruction, 2-sided A4 1 (2) Human Machine Interface 1 (3)
Power Connector 1
(4) Brackets & Screws 1 pack
Installation Instructions
Use a control box that provides enough stiffness.
Cutout Dimension: 192 mm x 138 mm. Secure the operator panel in position,
using all the fastening holes and the provided brackets and screws.
Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and
preventing the panel from being deformed.) Plan for adequate space around the
unit and inside the enclosure, for ventilation and cables. Consider the heat
from other devices inside the enclosure. The ambient temperature around the
unit must be -20 ~ 55°C
Minimum required clearances (along the overlay): Top / Bottom / Sides 15
mm
Maximum panel thickness: 4.5 mm
The aluminum flat-sheet at the back of the unit is a heat sink. Please be careful not to touch the heat sink since its heat can rise to 70°C in maximum when the unit is running. Planning for a 3cm space between the back of the unit and other devices is recommended.
Power Connections
Power Connector Specifications: Wire AWG: 24~12
Wiring Conductor Minimum Temperature: 75°C
Screw Torque: 4.5 lbf-in (max.)
Copper conduct only.
NOTE:
- Connect positive DC line to the ‘+’ terminal and the DC ground to the ‘-’ terminal.
- When downloading project using a USB cable, do not connect HMI with PLC and PC simultaneously, for electric potential difference may result in damage to HMI or PC.
System Settings
When HMI is powered up and displays image, press the round Start Button in the
upper-left corner of the screen to open the Setting dialog box. Tap the lock
icon and log in. (Default System Password: 111111)
Go to the Network tab, and setup your network.
In Setting dialog box you can see device information, configure general
settings, set HMI Time/Date/Name, and more.
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your project file, press F7 shortcut
key to open the download dialog box: Select Ethernet > IP tab > Enter your HMI
IP > Click Download to download this project fileto HMI.
Using screensaver and backlight saver is recommended in order to avoid image
persistence caused by displaying the same image on HMI for a long time.
(Please refer to EasyBuilder Pro User Manual for software operation details.)
Communication Connections
NOTE:
- COM2 and COM3 [RS485] 2W support MPI 187.5K, please use one at a time.
- Only Tx & Rx (no RTS/CTS) may be used for COM1 RS232 when COM3 RS-232 is also used.
COM1/COM3 [RS232] 9 Pin, Male, D-sub
PIN# | COM1[RS232]4W | COM3[RS232]2W |
---|---|---|
1 | ||
2 | RxD | |
3 | TxD | |
4 | ||
5 | GND | |
6 | ||
7 | RTS | TxD |
8 | CTS | RxD |
9 | GND |
**COM2/COM3 [RS485]/CAN Bus 9 Pin, Female, D-sub
**
PIN#| COM2[RS485]2W| COM2[RS485]4W| COM3[RS485]2W|
CANBus
---|---|---|---|---
1| Data-| Rx-| |
2| Data+| Rx+| |
3| | Tx-| |
4| | Tx+| |
5| GND
6| | | Data-|
7| | | | CAN_L
8| | | | CAN_H
9| | | Data+|
Touchscreen Calibration & Restore Factory Default
SW1 | SW2 | SW3 | SW4 | Mode |
---|---|---|---|---|
ON | OFF | OFF | OFF | Touch Screen Calibration Mode & Reset HMI to Default |
OFF | ON | OFF | OFF | Hide Start Button |
OFF | OFF | ON | OFF | Update OS |
OFF | OFF | OFF | ON | Reserved |
OFF | OFF | OFF | OFF | Normal |
Restore Factory Default:
Follow Step 5 to open the Setting dialog box. After login, press the button of
“Reset HMI to default”. Another way to restore factory default is entering
“default111111” when loggingin. An Attention window shows, enter “yes’.
Please note that the projects and data stored in the unit are all cleared
after restoring factory default. Another way to enter touch screen calibration
mode: Press and hold anywhere on the screen until HMI starts.
Battery Replacement
Battery Specification: Type CR2032, Rated 3V
Battery replacement shall be performed by qualified personnel (engineer) only
and care must be taken when handling lithium batteries. For more information
on battery replacement and disposal considerations, please refer to the
following link:
http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf
CAUTION
Power
Power| NOTE: Make sure that all local and national electrical standards
are met when installing the unit. Contact your local authorities to determine
which codes apply. power output that meets
Use powered systems. supply SELV (Safety Extra-Low Voltage) requirements. The
unit can be by DC power only, voltage range: 24±20%, compatible with most
controller DC The power conditioning circuitry inside the unit is accomplished
by a switching power
The peak starting current can be as high as 2A.
---|---
Fusing Require- meets| If the display does not come on within 5 seconds of
power up, remove power. A resettable fuse will protect against overcurrent
faults in DC circuit and the resetting will take place after a period of time.
Check wiring for proper connections and try to power up again.
High Voltage| A resettable fuse will prevent damage for overcurrent condition
however it isn’t guaranteed. DC voltage sources should provide proper
isolation from main AC power and similar hazards.
Emergency Stop| A Hard-wired EMERGENCY STOP should be fitted in any system
using an HMI to comply with ICS Safety Recommendations.
Supply Voltage Condition| Do not power the unit and inductive DC loads, or
input circuitry to the controller, with the same power supply. Note: The 24
VDC output from some controllers may not have enough current to power the
unit.
Wire Routing|
- a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
- b. Please use twisted pair cables for power wire and signal wire and conform to the impedance matching.
- c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
- d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
- e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power supply and the frame ground. This provides a path for static and high frequency dissipation. Typical values to use are 1M Ohm and 4700pF.
DANGER
Hardware Considerations| The system designer should be aware that devices in
Controller systems could fail and thereby create an unsafe condition.
Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical
injury to the operator. If you use any programmable control systems that
require an operator, be aware that this potential safety hazard exists and
take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the
guidelines for installation of Controllers recommended in NEMA ICS 3-304
Control Standards
---|---
Programming Considerations| To conform to ICS Safety Recommendations, checks
should be placed in the controller to ensure that all writable registers that
control critical parts of plant or machinery have limit checks built into the
program, with an out-of-limit safe shut down procedure to ensure safety of
personnel.
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s
discretion.
This warranty shall not cover any product which is:
- (a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
- (b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
- (c) Product has been repaired or taken apart by unauthorized technicians.
- (d) Products whose identification markings have been removed or damaged.