WEINTEK cMT2166X Series 15.6 Inch Touch HMI Screen Operator Interfaces Instruction Manual
- June 8, 2024
- WEINTEK
Table of Contents
- Installation and Startup Guide
- Unpacking the Unit
- Installation Instructions
- Power Connections
- System Settings
- EasyBuilder Pro Software Settings
- Communication Connections
- DIP SW Settings & Restore Factory Default
- Battery Replacement
- Limited Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
cMT2166X Series 15.6 Inch Touch
HMI Screen Operator Interfaces
Instruction Manual
Installation and Startup Guide
This document covers the installation of cMT2166X Series HMI, for the detailed specifications and operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all warnings, precautions, and instructions on the device carefully before use.
Install Environment:
NEMA Rating | The HMI product is NEMA 4 rated (Indoor Only). |
---|---|
Electrical Environment | The HMI product has been tested to conform to European |
CE requirements. This means that the circuitry is designed to resist the
effects of electrical noise. This does not guarantee noise immunity in severe
cases. Proper wire routing and grounding will insure proper operation.
Environmental Considerations| (1)Make sure that the displays are installed
correctly and that the operating limits are followed. Avoid installing units
in environments where severe mechanical vibration or shocks are present.
(2)Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3)Do not install the unit where acid gas, such as SO2 exists.
(4)This device should be mounted in the vertical position and for use on the
flat surface enclosure.
(5)For use in Pollution Degree 2 Environment and dry location.
(6)Relative Humidity: 10% — 90% (non-condensing)
Cleaning Considerations| Clean the device using dry cloths. Do not use liquid
or spray detergents for cleaning.
IP rating| IP 66
%Naming| Protection impairment if used in a manner not specified by the
manufacturer Deficit de protection si utilise d’une maniere non specifiee par
le fabricant.
Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the
supplier.
NOTE: Place the operator panel on a stable surface during installation.
Dropping it or letting it fall may cause damage.
The package includes:
(1) Installation Instruction, 2-sided A4 1 (2) Human Machine Interface 1 (3)
Power Connector 1 (4) Brackets & Screws 1 pack
Installation Instructions
Use a
control box that provides enough stiffness.
Cutout Dimension: 384 mm x 247 mm. Secure the operator panel in position,
using all the fastening holes and the provided brackets and screws.
Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and preventing
the panel from being deformed.)
Plan for adequate space around the unit and inside the enclosure, for
ventilation and cables. Consider the heat from other devices inside the
enclosure.
The ambient temperature around the unit must be 0 ~ 50°C
Minimum required clearances (along the overlay): Top / Bottom / Sides 15 mm
Maximum panel thickness: 4 mm
Power Connections
Power Connector Specifications:
Wire AWG: 24~12
Wiring Conductor Minimum Temperature: 75°C
Screw Torque: 4.5 lbf-in (max.)
Copper conduct only.
NOTE:
- Connect positive DC line to the ‘+’ terminal and the DC ground to the ‘-’ terminal.
- When downloading project using a USB cable, do not connect HMI with PLC and PC simultaneously, for electric potential difference may result in damage to HMI or PC.
System Settings
When HMI is powered up and displays image, press the round Start Button in the
upper-left corner of the screen to open the Setting dialog box. Tap the lock
icon and log in. (Default System Password: 111111)
Go to the Network tab, and setup your network.
In Setting dialog box you can see device information, configure general
settings, set HMI Time/Date/Name, and more.
EasyBuilder Pro Software Settings
Launch EasyBuilder Pro software, select your project file, press F7 shortcut
key to open the download dialog box: Select Ethernet > IP tab > Enter your HMI
IP > Click Download to download this project file to HMI.
Using screensaver and backlight saver is recommended in order to avoid image
persistence caused by displaying the same image on HMI for a long time.
( Please refer to EasyBuilder Pro User Manual for software operation details.
)
Communication Connections
NOTE:
- Only Tx & Rx (no RTS/CTS) may be used for COM1 RS-232 when COM3 RS-232 is also used.
- COM1 RS-485 / COM3 RS-485 are not isolated.
DIP SW Settings & Restore Factory Default
SW1 | SW2 | SW3 | SW4 | Mode |
---|---|---|---|---|
ON | OFF | OFF | OFF | Reset Factory Default at Startup |
OFF | ON | OFF | OFF | Hide HMI System Setting Bar |
OFF | OFF | ON | OFF | Update OS |
OFF | OFF | OFF | ON | Reserved |
OFF | OFF | OFF | OFF | Normal |
Restore Factory Default from System Settings:
Follow Step 5 to open the Setting dialog box. Go to “Reset options” tab, press
the button of “Reset HMI to default”. An Attention window shows, enter “yes”.
Another way to restore factory default is entering “default111111” when
logging in. An Attention window shows, enter “yes”.
Please note that the projects and data stored in the unit are all cleared
after pressing this button.
Battery Replacement
Battery replacement shall be performed by qualified personnel only and care must be taken when handling lithium batteries. For more information on battery replacement and disposal considerations, please refer to the following link: http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf
CAUTION
NOTE: Make sure that all local and national electrical standards are met
when installing the unit. Contact your local authorities to determine which
codes apply.
Power| Use power output that meets SELV (Safety Extra-Low Voltage)
requirements. The unit can be powered by DC power only, voltage range: 24±20%,
compatible with most controller DC systems. The power conditioning circuitry
inside the unit is accomplished by a switching power supply. The peak starting
current can be as high as 2A.
---|---
Fusing Requirements| If the display does not come on within 5 seconds of power
up, remove power. An internal fuse will prevent damage if the polarity of the
DC power is incorrect. Check wiring for proper connections and try to power up
again.
High Voltage| An Internal fuse will prevent damage for overcurrent condition
however it isn’t guaranteed. DC voltage sources should provide proper
isolation from main AC power and similar hazards.
Emergency Stop| A Hard-wired EMERGENCY STOP should be fitted in any system
using an HMI to comply with ICS Safety Recommendations.
Supply Voltage
Condition| Do not power the unit and inductive DC loads, or input circuitry to
the controller, with the same power supply. Note: The 24 VDC output from some
controllers may not have enough current to power the unit.
Wire Routing| a. Power wire length should be minimized (Max: 500m shielded,
300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform
to the impedance matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge
suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from
signal wires.
e. Add a resistor and capacitor in the parallel connection between the
ungrounded DC power supply and the frame ground. This provides a path for
static and high frequency dissipation. Typical values to use are 1M Ohm and
4700pF.
DANGER
Hardware
Considerations| The system designer should be aware that devices in Controller
systems could fail and thereby create an unsafe condition. Furthermore,
electrical interference in an operator interface can lead to equipment start-
up, which could result in property damage and/or physical injury to the
operator.
If you use any programmable control systems that require an operator, be aware
that this potential safety hazard exists and take appropriate precautions.
Although the specific design steps depend on your particular application, the
following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation
of Controllers recommended in NEMA ICS 3-304 Control Standards.
---|---
Programming
Considerations| To conform to ICS Safety Recommendations, checks should be
placed in the controller to ensure that all writable registers that control
critical parts of plant or machinery have limit checks built into the program,
with an out-of-limit safe shut down procedure to ensure safety of personnel.
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s
discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of
the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper
installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
References