resideo FR124 Combustion Regulator Instruction Manual
- June 8, 2024
- resideo
Table of Contents
resideo FR124 Combustion Regulator
Safety Guidelines
- Follow the installation instructions.
- Use the appliance
- according to its intended use
- in good condition
- with due regard to safety and risk of danger.
- Note that the appliance is exclusively for use in the applications detailed in these installation instructions (see 2 Technical Data). Any other use will not be considered to comply with requirements and would invalidate the warranty.
- Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
- Immediately rectify any malfunctions which may influence safety.
Technical Data
Connections/Sizes
Connection size:| 3/4″
Nominal size:| DN20
Operating temperatures
Max. ambient temperature:| 70 °C
Max. sensor temperature:| 115 °C
Setting range:| 30 – 90 °C
Specifications
Chain length:| 1.2 m
Chain load:| 100 – 600 g (Standard version),
400 – 1000 g (Reinforced version)
Tube length:| 53 mm
| For solid fuel and multi-fuel heating installations to
EN 12828
Options
For Options visit homecomfort.resideo.com/europe
Assembly
Installation Guidelines
- Horizontal or vertical installation
- Install Combustion Regulator in the water cycle of the boiler
- Only install it in the screw socket intended for this purpose
Assembly instructions
- Seal threaded joint with hemp or Teflon tape.
- Screw immersion tube (thread T3/4) into the threaded socket of the boiler
- Secure the lever rod
- Secure chain to the lever rod and the inlet air flap
- The chain hangs free and the lever rod moves freely when the adjuster knob is turned
Start-up
Calibrating the Combustion Regulator
- Heat up the boiler with manually opened inlet air flap
- Set the adjuster knob on the Combustion Regulator to “60”
- Once the water temperature has reached and maintained 60 °C adjust the chain length so that door 2 remains open.
Disposal
Observe the local requirements regarding correct waste recycling/disposal!
Troubleshooting
Problem | Cause | Remedy |
---|---|---|
Temperature during stabilised operation is below the set value. | Too | |
little inlet air | Shorten chain | |
Other influences, e.g. too much ash in the boiler. | Irrespective of the FR124, |
check all other influences, e.g. fuel and ash quantities, position of the
admixed air flap, boiler inertia and the entire heating system
Temperature during stabilised operation is above the set value.| Too much
inlet air| Extend chain
Inlet air flap is jammed and does not shut| Oil inlet air flap
Other influences, e.g. too much ash in the boiler.| Irrespective of the FR124,
check all other influences, e.g. fuel and ash quantities, position of the
admixed air flap, boiler inertia and the entire heating system
Other faults| Call Technical Customer Service
Manufactured for and on behalf of Pittway Sàrl, Z.A., La Pièce 4, 1180 Rolle,
Switzerland by its authorised representative Ademco 1 GmbH
For more information
homecomfort.resideo.com/europe Ademco 1 GmbH,
Hardhofweg 40, 74821 MOSBACH, GERMANY
Phone : +49 6261 810
Fax : +49 6261 81309
© 2020 Resideo Technologies, Inc. All rights reserved.