VIESSMANN EM-P1 Pump Extension for DHW Secondary Pump or Pump Without Mixer Instruction Manual
- June 9, 2024
- VIESSMANN
Table of Contents
VIESSMANN EM-P1 Pump Extension for DHW Secondary Pump or Pump Without
Mixer
IMPORTANT
Read and save these instructions for future reference.
Safety
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
-
Product documentation
Read all applicable documentation before commencing installation. Store documentation near boiler in a readily accessible location for reference in the future by service personnel.- For a listing of applicable literature, please see section entitled “Important Regulatory and Safety Requirements”.
-
Licensed professional heating contractor
The installation, adjustment, service and maintenance of this equipment must be performed by a licensed professional heating contractor.- Please see section entitled Safety and “Important Regulatory and Installation Requirements”.
-
Advice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the heating season begins. -
Warranty
Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void.
Important Precautions
Important Regulatory and Installation Requirements
Approvals
Viessmann boilers, burners and controls are approved for sale in North America
by CSA International.
Codes
The installation of this unit shall be in accordance with local codes. In the
absence of local codes, use:
- CSA C22.1 Part 1 and/or local codes in Canada
- National Electrical Code ANSI/NFPA 70 in the U.S.
Always use latest editions of codes.
The heating contractor must comply with the Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/ASME CSD-1 where required by the
authority having jurisdiction.
Working on the equipment
The installation, adjustment, service, and maintenance
of this product must be done by a licensed professional heating contractor who
is qualified and experienced in the installation, service, and maintenance of
hot water boilers. There are no user-serviceable parts on the boiler, burner,
or control.
Power supply
Install power supply in accordance with the regulations of the authorities
having jurisdiction or, in absence of such requirements, in accordance with
National Codes. Viessmann recommends the installation of a disconnect switch
to the 120V power supply outside of the boiler room.
Ensure main power supply to equipment, the heating system, and all external
controls have been deactivated. Close main oil or gas supply valve. Take
precautions in both instances to avoid accidental activation of power during
service work.
-
Please carefully read this manual prior to attempting installation. Any warranty is null and void if these instructions are not followed.
For information regarding other Viessmann System Technology componentry, please reference documentation of the respective product.
We offer frequent installation and service seminars to familiarize our partners with our products. Please inquire. -
The completeness and functionality of field supplied electrical controls and components must be verified by the heating contractor. These include low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents, thermostats, etc.
WARNING
Turn off electric power supply before servicing. Contact with live electric
components can cause shock or loss of life.
About these Installation Instructions
Take note of all symbols and notations intended to draw attention to
potential hazards or important product information.
WARNING
Warnings draw your attention to the presence of potential hazards or important
product information.
- Indicates an imminently hazardous situation which, if not avoided, could result in death, serious injury or substantial product/property damage.
CAUTION
Cautions draw your attention to the presence of potential hazards or important
product information.
- Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product / property damage.
IMPORTANT
- Helpful hints for installation, operation or maintenance which pertain to the product.
- This symbol indicates to note additional information
- This symbol indicates that other instructions must be referenced.
Intended Use
The appliance is only intended to be installed and operated in sealed unvented
heating systems, with due attention paid to the associated installation,
service and operating instructions as well as the details in the datasheet.
It is only designed for the heating up of heating water. Commercial or
industrial usage for a purpose other than the heating up of heating water
shall be deemed inappropriate.
Intended use presupposes that a fixed installation in conjunction with
permissible components designed for this purpose has been carried out.
Every other use will be deemed to be inappropriate. Any resulting losses are
excluded from the manufacturer’s liability.
Any usage beyond this must be approved by the manufacturer for the individual
case.
Intended use also includes the adherence to maintenance and inspection
intervals.
Product Information
Spare parts lists
Information about spare parts can be found on the Viessmann spare parts app.
The following circulation pumps can be connected:
- Heating circuit pump for heating circuit without mixing valve
- DHW recirculation pump
Installation
Mounting the Extension
- Loosen the retaining screws from the extension kit enclosure (do not remove).
- Remove cover and set aside.
- Mount the extension module enclosure to the wall using the supplied hardware.
- Install the cover.
Overview of Electrical Connections
CAUTION
The electronic modules are static sensitive. To avoid damage caused by static
discharge, follow Electro-Static Discharge safety procedures.
Note: Apply strain relief to on-site cables.
Secure individual wires directly to each plug using cable ties.
Seal any unnecessary apertures with cable grommets (not cut open).
Connections
Connecting the DHW Recirculation Pump
Legend
- A DHW recirculation pump
- B Plug 46 to slot P3
-
If there is already a plug connected to the DHW recirculation pump:
Remove it and connect plug fH. -
Insert the plug into slot P3.
Specification
Rated current | 1A |
---|---|
Rated Voltage | 120VAC |
Connecting the Heating Circuit Pump
Legend
- A Heating circuit pump
- B Contactor/Relay
- C Power supply with disconnect and protection 20 To the extension kit
Heating circuit pump 120V~
Specification of the heating circuit pump 120V~
Rated current: >1A
Specification of the contactor:
Rated voltage: 120V~
Rated current: 1A
Legend
- A Heating circuit pump
- B Contactor/Relay
- C Power supply with disconnect and protection 20 To the extension kit
Heating circuit pump 240V~
Note: In underfloor heating circuits, integrate a temperature limiter on site for limiting the maximum temperature of underfloor heating systems.
Specification of the heating circuit pump 240V~
- Specification of the contactor:
- Rated voltage: 120V~
- Rated current: 1A
Legend
- A Heating circuit pump
- B Contactor/Relay
- C Power supply with disconnect and protection 20 To the extension kit
Heating circuit pump 208/460/575V~
- Specification of the heating circuit pump 208/460/575V~
- Specification switching the contactor:
- Rated voltage 120V~
- Rated current 1A
Rotary Switch S1
Rotary switch S1 on the EM-P1 extension and rotary switch S1 on the mixer extension kit must be set according to the following table.
Connecting the PlusBus to the Boiler
Legend
- A Extension (electronics module)
- B PlusBus to heat generator
For connection to heat generators with external plug, luster terminals or spring-loaded terminals: For the bus connection, disconnect plug jF. Connect the wires directly. The wires are interchangeable.
Boiler installation and service instructions
Power Supply
Direct power supply
Legend
- A Extension P1
WARNING
Incorrectly executed electrical installations can result in injuries from
electrical current and in equipment damage.
Connect the power supply (see page 4) and implement all grounding measures (e.g. RCD circuit) in accordance with the following regulations:
- In Canada all electrical wiring is to be done in accordance with the latest edition of CSA C22.1 Part 1 and/or local codes. In the U.S. use the National Electrical Code ANSI/NFPA 70. The heating contractor must also comply with both the Standard for Controls and Safety Devices for Automatically Fired Boilers,ANSI/ASME CSD-1, and the Installation Code for Hydronic Heating Systems, CSA B214-01, where required by the authority having jurisdiction.
- Connection requirements specified by your local power supply utility
- Protect the power cable with max. 15A
WARNING
- The absence of component grounding in the system can lead to serious injury from electrical current if an electrical fault occurs. Connect the appliance and pipework to the equipotential bonding of the building in question.
- Incorrect core allocation can result in serious injury and damage to the appliance. Never interchange cores “L” and “N”.
CAUTION
An incorrect phase sequence can cause damage to the appliance. Check for phase
equality with the power supply connection of the control unit.
Connecting Several Accessories
Some accessories with direct power supply
Legend
- A Boiler control unit
- B Mixing valve extension kit for heating circuit with mixing valve M2 (electronics module)
- C Mixing valve extension kit for heating circuit with mixing valve M3 (electronics module)
- D Further accessories
- 74 PlusBus
Power supply and PlusBus connection
- In the following circumstances, use the contact (output) of the accessories only to switch an on-site relay:
An actuator with a higher power demand than the fuse rating required for the accessories, e.g. a circulation pump, is connected to the contact (output) of the accessories.
Legend
- A1 PCB, EM-P1 extension (ADIO electronics module)
- A2 PCB
- F1 Fuse
- S1 Rotary switch
120V~ plugs
- P1 20 Heating circuit pump (on site)
- P3 46 DHW recirculation pump (on site)
- 40 Power supply 120VAC/60 Hz
- 40A Power supply for accessories
LV plug
- PWM1 No function
- TS1 No function
- TS2 No function
- TS3 ) 9 No function
- 74 PlusBus for connection to the boiler control unit and one other accessory
Specifications
Rated voltage | 120VAC |
---|---|
Rated frequency | 60 Hz |
Rated current | 2A |
Power consumption – electronics | 2 W |
Power consumption | 9 mA |
Permissible ambient temperature Operation
Storage and transport
|
32 to 104°F
(0 to +40°C)
-4 to 149°F (–20°C to +65°C)
Rated relay output breaking capacity
P 1 (heating circuit pump)
P 3 (DHW recirculation pump)
| 1A 120VAC
1A 120VAC
Scan for digital copy of this document
Viessmann Manufacturing Company Inc.
750 McMurray Road
Waterloo, Ontario N2V 2G5 Canada
Techlnfo Line 1-888-484-8643
1-800-387-7373 Fax
519-885-0887
www.viessmann.cainfo@viessmann.ca
Viessmann Manufacturing Company (U.S.) Inc.
45 Access Road
Warwick, Rhode Island 02886 USA
Techinfo Line 1-844-649-5886
1-800-288-0667 Fax