Testboy Schuki 1A Mains Outlet Tester Instruction Manual

June 3, 2024
Testboy

Schuki 1A Mains Outlet Tester
Instruction Manual
Testavit®Schuki® 1A
Version 2.4

Schuki 1A Mains Outlet Tester

Notes
Safety notes

WARNING
An additional source of danger is posed my mechanical parts which can cause severe personal injury.
Objects can also be damaged (e.g., the instrument itself can be damaged).
WARNING
An electric shock can result in death or severe injury.
It can also lead to property damage and damage to this instrument.
WARNING
Never point the laser beam directly or indirectly (on reflective surfaces) towards the eyes. Laser radiation can cause irreparable damage to the eyes. You must first deactivate the laser beam when measuring close to people.
General safety notes

WARNING
Unauthorized changes or modifications of the instrument are forbidden – such changes put the approval (CE) and safety of the instrument at risk. In order to operate the instrument safely, you must always observe the safety instructions, warnings and the information in the “Proper and Intended Use” Chapter.

WARNING
Please observe the following information before using the instrument:

  • Do not operate the instrument in the proximity of electrical welders, induction heaters and other electromagnetic fields.

  • After an abrupt temperature fluctuation, the instrument should be allowed to adjust to the new temperature for about 30 minutes before using it.
    This helps to stabilize the IR sensor.

  • Do not expose the instrument to high temperatures for a long period of time.

  • Avoid dusty and humid surroundings.

  • Measurement instruments and their accessories are not toys. Children should never be allowed access to them!

  • In industrial institutions, you must follow the accident prevention regulations for electrical facilities and equipment, as established by your employer’s liability insurance organization.

Please observe the following five safety rules:

  1. Disconnect.
  2. Ensure that the instrument cannot be turned back on again.
  3. Ensure isolation from the main supply voltage (check that there is no voltage on both poles).
  4. Earth and short-circuit.
  5. Cover neighboring parts that are under live electrical load.

Proper and intended use
This instrument is intended for use in applications described in the operation manual only. Any other usage is considered improper and non-approved us-age and can result in accidents or the destruction of the instrument. Any misuse will result in the expiry of all guarantee and warranty claims on the part of the operator against the manufacturer.
Remove the batteries during longer periods of inactivity in order to avoid damaging the instrument.
We assume no liability for damages to property or personal injury caused by improper handling or failure to observe safety instructions. Any warranty claim expires in such cases. An exclamation mark in a triangle indicates safety notices in the operating instructions. Read the instructions completely before beginning the initial commissioning. This instrument is CE approved and thus fulfils the required guidelines.
All rights reserved to alter specifications without prior notice
© 2014 Testboy GmbH, Germany.

Disclaimer and exclusion of liability

The warranty claim expires in cases of damages caused by failure to observe the instruction! We assume no liability for any resulting damage!

Testboy is not responsible for damage resulting from:

  • failure to observe the instructions,
  • changes in the product that have not been approved by Testboy,
  • the use of replacement parts that have not been approved or manufactured by Testboy,
  • the use of alcohol, drugs or medication.

Correctness of the operating instructions
These operating instructions have been created with due care and attention. No claim is made nor guarantee given that the data, illustrations and drawings are complete or correct. All rights are reserved in regards to changes, print failures and errors.

Disposal
For Testboy customers: Purchasing our product gives you the opportunity to return the instrument to collection points for waste electrical equipment at the end of its lifespan.
The WEEE directive regulates the return and recycling of electrical appliances. Manufacturers of electrical appliances are obliged to take back and recycle all electrical appliances free of charge. Electrical devices may then no longer be disposed of through conventional waste disposal channels. Electrical appliances must be recycled and disposed of separately. All equipment subject to this directive is marked with this logo.

Certificate of quality
All aspects of the activities carried out by Testboy GmbH relating to quality during the manufacturing process are monitored permanently within the framework of a Quality
Management System. Furthermore, Testboy GmbH confirms that the testing equipment and instruments used during the calibration process are subject to a permanent inspection process.
Declaration of Conformity
The product conforms to the present directives. For more detailed information, go to www.testboy.de

Operation

Thank you for choosing a Testavit ® Schuki ® 1A.

  • Power socket tester with FI/RCD test (30 mA).

Power socket test
The Testavit®Schuki®1A is able to determine right or wrong connection of the wires in power sockets and shows the results with an optical indication.
Please find the failure indication in the below table.
With using the „FI/RCD-Test“ button (less than 3 seconds) you are able to trigger the residual current device (30 mA at 230V AC).
In order to obtain a correct indication and to carry out the FI/RCD test, the right phase must be applied. WARNING
The test device is not suitable for dual-conductor mains (classic zeroing).
Interchanging the neutral conductor and protective conductor (earth) is not recognized by the device!
Check the voltage tester before use against a known voltage supply (e.g. a power socket) to ensure that it is working correctly.

| L>| OK, Phase on the right side
---|---|---
| L<| OK, Phase on the left side
| PE| Ground missing
| L| Phase missing
| N| Neutral missing, Phase on the  right/left side
| L<>PE| Phase/Ground inverted
| L<>PE&PE| Phase/Ground inverted and Ground missing

LED off; LED on

If the tester indicates a fault condition in the wiring under test, always investigate the wiring or have the wiring investigated bya competent person.
Do not contact accross two phases of a three phase supply.
The tester will not correctly test circuits using isolation transformer.
Before testing, disconnect any loads from the circuits of all socket outlet in same distribution board as possible with the socket under test. Some loads connected may lead to
measuring error.
Check the RCD trigger function in an known correctly circuit with RCD before used.
Use caution with voltages above 30 V ac as a shock hazard may exist.

FOR USE BY COMPETENT PERSONS

Anyone using this instrument should be knowledgeable and trained about the risks involved with measuring voltage, especially in an industrial setting, and the importance of taking safety precautions and of testing the instrument before and after using it to ensure that it is in good working condition.

Definition of measurement categories:

Measurement category II:
Measurement category II is applicable to test and measuring circuits connected directly to utilization points (socket outlets and similar points) of the low- voltage mains installation. Typical short-circuit current is < 10kA.
Measurement category III:
Measurement category III is applicable to test and measuring circuits connected to the distribution part of the building’s lowvoltage mains installation. Typical short-circuit current is < 50kA.
Measurement category IV:
Measurement category IV is applicable to test and measuring circuits connected at the source of the building’s low-voltage mains installation. Typical short- circuit current is >> 50kA.
Read the instruction before use. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. All parts of the device and its accessories are not allowed to be changed or replaced, other than authorized by the manufacturer or his agent.
For cleaning the unit, use a dry cloth.

Technical data

Voltage range 230 V AC, 50 Hz
Power supply by test object, max. 3 mA
FI/RCD Test 30 mA at 230 V AC
Degree of protection IP 40
Over-voltage category CAT II 300 V
Temperature range 0° ~ +50°C
Testing standard IEC/EN 61010-1

(DIN VDE 0411)

Testboy GmbH
Elektrotechnische Spezialfabrik
Beim Alten Flugplatz 3
D-49377 Vechta
Germany
Tel: +49 (0)4441 89112-10
Fax: +49 (0)4441 84536
www.testboy.de
info@testboy.de

Documents / Resources

| Testboy Schuki 1A Mains Outlet Tester [pdf] Instruction Manual
Schuki 1A Mains Outlet Tester, Schuki 1A, Mains Outlet Tester, Outlet Tester, Tester
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Testboy User Manuals

Related Manuals