Overview:
Altronix AL624 power supply/charger converts low voltage AC input into 6VDC or
12VDC @ 1.2A or 24VDC @ 750mA of continuous supply current (see
specifications). This general purpose power supply has a wide range of
applications for access control, security, and CCTV system accessories that
require additional power.
Specifications:
Input:
-
16VAC to 24VAC, 20VA to 40VA
(Transformer Selection Table).
Output: -
Switch selectable 6VDC-12VDC-24VDC.
-
6VDC or 12VDC @ 1.2A or 24VDC @ 0.75A supply current.
-
Filtered and electronically regulated output.
-
Short circuit and thermal overload protection.
Battery Backup: -
Built-in charger for sealed lead acid or gel type batteries.
-
Automatic switch over to stand-by battery when AC fails.
-
Maximum charge current 0.3A.
-
PTC battery protection.
Visual Indicators: -
AC input and DC output LED indicators.
Features: -
Extremely compact design.
-
Battery leads included.
-
Snap Trac compatible (order Altronix model #ST3).
-
DIN Rail mount version available
(order Altronix model #DPS1).
Board Dimensions (L x W x H approx.):
3” x 2.5” x 1.125” (76.2mm x 63.5mm x 28.6mm).
Voltage Output/Transformer Selection Table:
Installation Instructions:
-
Mount AL624 in the desired location/enclosure (mounting hardware included).
-
Unit is factory set for 12VDC. For 6VDC output cut jumper J2, for 24VDC output cut Jumper J1.
-
Connect the proper transformer to the terminals marked [AC] (refer to Voltage Output/Transformer Selection Table). Use 18 AWG or larger for all power connections (Battery, DC output).
-
Measure output voltage before connecting devices. This helps avoiding potential damage.
-
Connect devices to be powered to the terminals marked [+ DC] and [DC – BAT], carefully observing polarity.
-
Connect battery to the terminals marked [BAT +] and [DC – NEG] (battery leads included)
Note: To avoid damage connect batteries as follows:- For 6VDC operation connect one (1) 6VDC battery.
- For 12VDC operation connect one (1) 12VDC battery or two (2) 6VDC batteries wired in series.
- For 24VDC operation connect two (2) 12VDC batteries wired in series.
Note: When batteries are not used, a loss of AC will result in a loss of output voltage.
LED Diagnostics:
Terminal Identification:
Altronix is not responsible for any typographical errors.140 58th Street,
Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056