ADVANTECH WOP-200K Human Machine Interface Installation Guide

June 3, 2024
Advantech

Human Machine Interface
Installation Guide

WOP-200K Human Machine Interface

WOP-200K/WOP-200K

ADVANTECH WOP-200K Human Machine Interface -

Model A B C L H
WOP-204K-NAE 129mm/5.08” 103mm/4.06” 26.3mm/1.04” 118.5mm/4.67”

92.5mm/3.64”
WOP-207K-NAE| 189.6mm/7.46”| 144.9mm/5.70”| 30mm/1.18”| 175mm/6.89”| 132.5mm/5.22”
WOP-208K-NAE| 233mm/9.17”| 176mm/6.93”| 37.3mm/1.47”| 221mm/8.70”| 164mm/6.44”
WOP-210K-NAE| 270.1mm/10.63”| 212.1mm/8.35”| 37.4mm/1.47”| 259.5mm/10.22”| 201.5mm/7.93”
WOP-212K-NAE| 335.4mm/13.21”| 245.8mm/9.68”| 54.3mm/2.14”| 302mm/11.89”| 228.5mm/9.0”
WOP-215K-NAE| 399.1mm/15.71”| 297.6mm/11.72”| 51.3mm/2.02”| 384.5mm/15.14”| 283mm/11.14”

ADVANTECH WOP-200K Human Machine Interface - Fig

Tighten each fixing screw until the bezel corner gets in contact with the panel. Suggested torque for fixing screws: 0.25~0.34Nm .
Dispose of batteries

Dispose of batteries according to local regulations.

Function view

| ADVANTECH WOP-200K Human Machine Interface -
Fig3
---|---
ADVANTECH WOP-200K Human Machine Interface - Fig4

  1. Power connector .
  2. COM1&2&3 9Pin female.
  3. USB host .
  4. USB client .
  5. Ethernet port .
  6. COM1&3 5Pin terminal.
  7. COM2 5Pin terminal.

Power supply
Powered by low voltage/Limited energy power source.

ADVANTECH WOP-200K Human Machine Interface - Fig6

Do not open the rear cover of the panel when power is applied.
Be sure that the power supply has enough power capacity for the operation of the equipment.

  • WOP-204K: 24VDC±10% / 0.4A
  • WOP-207K & WOP-208K & WOP-210K &
    WOP-212K & WOP-215K : 24VDC±10% / 0.8A

Pin Diagram

WOP-204K-NAE| COM1 & COM3 5 Pin erminal|
---|---|---
COM2 5 Pin terminal|

WOP-207K-NAE / WOP-208K-NAE / WOP-210K-NAE / WOP-212K-NAE / WOP-215K-NAE
COM1 & COM2 & COM3 DB-9-female:

Pin Descrition
1 RS422 TXD+ / RS485 + (COM2)
2 RS232 RXD (COM1)
3 RS232 TXD (COM1)
4 RS422 RXD+ (COM2)
5 SG
6 RS422 TXD- / RS485 – (COM2)
7 RS485 –  (COM3)
8 RS485 +  (COM3)
9 RS422 RXD- (COM2)

The products have been designed for use in an industrial environment in compliance with the 2014/30/EU directive.
The products have been designed in compliance with:

EN 61000-6-4: 2007 +A1: 2011
EN 61000-3-2: 2014
EN 61000-3-3: 2013
EN 61000-6-2: 2005 / AC: 2005
IEC 61000-4-2: 2008; IEC 61000-4-3: 2006 + A1: 2007 +A2: 2010;
IEC 61000-4-4: 2012; IEC 61000-4-5: 2014 +A1:2017; IEC 61000-4-6: 2013;
IEC 61000-4-8: 2009; IEC 61000-4-11: 2004 + A1: 2017
The installation of these devices into residential, commercial and light- industrial environments is allowed only special measures are taken in order to get the conformity to IEC-61000-6-3

NEMA Certification:
NEMA Type 4X Indoor Use Only
Reproduction of the contents of this copyrighted document, in whole or part, without written permission of Advantech Co., Ltd., is prohibited.
CAUTION

  1. Indoor use and pollution degree II, it must be wiped with a dry cloth for cleaning up the labeling.
  2. Please be used qualified power supply by SELV or double insulation of UL60950 or UL61010-1 or UL61010-2-201 standards.
  3. UL61010-2-201: Shall be mounted in the Industrial Control Panel , and the ambient temperature does not exceed 60 degrees C.
  4. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
  5. We suggest using the cable type – AWG (American Wire Gauge) 18-24 and the corresponding pin type cable terminals.
  6. We suggest used torque value 4.60 lb-in, do not use excessive force when fixing wiring.
  7. Altitude: up to 2000 m
  8. Maximum ambient temperature rated, WOP-204K, WOP-207K & WOP-208K & WOP-210K & WOP-212K & WOP-215K: 60 degree C
  9. Minimum ambient temperature rated -10 degree C
  10. Input Wiring Rating: Min. 90 degreeC
  11. WOP-204K, WOP-207K, WOP-208K, WOP-210K, WOP-212K, WOP-215K has been certificated by UL.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Advantech User Manuals

Related Manuals