ADVANTECH LEOS552TP Temperature Sensor User Manual
- May 15, 2024
- Advantech
Table of Contents
Temperature Sensor
Featuring LoRaWAN®
LEO-S552-TPG0
User Guide
LEOS552TP Temperature Sensor
Safety Precautions
Advantech will not shoulder responsibility for any loss or damage resulting from not following the instructions of this operating guide.
- The PT100 temperature probe has a sharp point. Please be careful and keep the edges and points away from human body.
- The device must not be disassembled or remodeled in any way.
- To ensure the security of your device, please change the device password during the initial configuration. The default password is 123456.
- The device is not intended to be used as a reference sensor, and Advantech will not should responsibility for any damage which may result from inaccurate readings.
- Do not place the device close to objects with naked flames.
- Do not place the device where the temperature is below/above the operating range.
- Make sure electronic components do not drop out of the enclosure while opening.
- When installing the battery, please install it accurately, and do not install the inverse or wrong model.
- The device must never be subjected to shocks or impacts.
Declaration of Conformity
LEO-S552-TPG0 is in conformity with the essential requirements and other
relevant provisions of the CE, FCC, and RoHS. For assistance, please contact
Advantech technical support:
Email: Lily.Huang@advantech.com.tw
Tel: 886-2-7732-3399
Fax: 886-2-2794-7334
Address: No.1, Alley 20, Lane 26, Rueiguang Road,Neihu
District, Taipei, Taiwan
Product Introduction
1.1 Overview
Advantech LEO-S552-TPG0 is an advanced resistance temperature sensor with a
visualized data display. It features extendable connecting lines and two
detecting probes, including two A-class food-grade temperature probes.
LEO-S552-TPG0 prioritizes security and reliability, ensuring traceable data
and effortless data exports for seamless integration.
LEO-S552-TPG0 is designed for measuring a wide range of temperature in harsh
environments and transmitting data using LoRaWAN® technology. With this low
power consumption technology, LEO-S552-TPG0 can maintain a long operational
life with its embedded batteries.
LEO-S552-TPG0 is widely used for temperature monitoring applications like food
processing, cold chain storage of food or medicine, etc.
1.2 Features
- IP65 waterproof enclosure with dust plug, suitable for harsh environment.
- Support automated temperature monitoring and record data with anti-tamper features to meet HACCP (Hazard Analysis and Critical Control Points) requirements, as well as the authenticity requirements of 21 CFR Part 11B electronic record.
- Provide simplified PDF data export for easy documentation without complex paperwork.
- Built-in two large-capacity replaceable batteries, ensuring an extended battery life.
- Features low-consumption LCD display, enabling intuitive data reading.
- Store up to 10,000 historical records locally and supports data retrieval and retransmission to prevent data loss.
- Equipped with NFC and Type-C USB for quick and easy configuration.
- Function effectively with standard LoRaWAN® gateways and network servers.
Hardware Introduction
2.1 Packing List ** If any of the above items
is missing or damaged, please contact your sales representative.
2.2 Hardware Overview**
2.3 Button Descriptions
Power Button
Function | Action | LCD Display |
---|
Power On: All icons show 3s
Power On/Off| Press and hold the power button for morethan 3 seconds| Power
Off: Off
Update Temperature| Quick press the power button once| Refresh the latest
temperature of the current channel
Switch Temperature
Display (LEO-S552-TPG0with both temperature sensors only)| Quick press the
powerbutton twice| Display another channel’s latest temperature
Reset Button
Function | Action | LED Indicator |
---|---|---|
Reset to Factory Default | Press and hold the reset |
button for more than 10
seconds| Blinks quickly
2.4 Screen Description
Note:
- The screen is only displayed when the temperature sensor is connected to the LEO-S552-TPG0.
- The screen can be enabled/disabled by downlink commands.
Device | OSD | Description |
---|---|---|
Time. | ||
**** | Temperature Threshold Trigger Alarm | |
Battery Level | ||
LoRaWAN ® Network is Activated | ||
Temperature of Channel 1/Channel 2 |
2.5 Dimensions (mm)
2.6 PT100 Probes Specifications
Model | AF10-125- 150 |
---|---|
Measuring Range | -40 °C ~125 °C |
Measuring Accuracy | ± 0.4°C |
Measuring Resolution | **** 0.1°C |
Probe Type | Needle, Food Grade 316 Stainless Steel |
Probe Length | Φ4*100 mm |
Cable Length | 1.5 m |
Cable Material | Food Grade Silicone |
Ingress Protection | IP67 |
Detection Distance | 20-30 mm |
--- | --- |
Cable Length | 1.5 m (Customizable) |
Dimension | 32 × 15 × 8 mm (1.25 × 0.59 × 0.31 in) |
Installation | Wall Screw Mounting, 3M Tape Mounting |
Operation Guide
3.1 Configuration
3.1.1 Configured By NFC
- Download and install “Advantech ToolBox” App on an NFC-supported smart phone.
- Open “Advantech ToolBox” App and attach the NFC area of the smart phone to the device. Click “NFC Read” to read the device and click “Write” to configure the device settings. It’s suggested to change the default password for security reasons. (Default password: 123456).
Note:
- Ensure the location of the smartphone NFC area and it’s recommended to take off the phone case.
- If the smartphone fails to read/write configurations via NFC, move it away and try again later.
3.1.2 Configured by USB
- Download ToolBox software from Advantech’s official website.
- Remove the USB waterproof plug from the bottom of the device, and connect it to the computer via a type-C USB cable. After connecting, the PDF file can be exported directly from the USB drive folder.
- Open ToolBox software, select type as “General” and select the serial port as USB port, then type the login password (Default password: 123456) to log in in to the device to check or configuring the device. It’s suggested to change the default password for security reasons.
3.2 LoRaWAN Settings
LoRaWAN settings is used for configuring the transmission parameters in
LoRaWAN® network.
Basic LoRaWAN Settings:
Configure join type, App EUI, App Key and other information. You can also keep
all settings by default.
Parameters | Description |
---|---|
Device EUI | The device’s unique ID can also be found on the label. |
App EUI | The default App EUI is 24E124C0002A0001. |
Application Port | The port used for sending and receiving data, the default |
port is 85.
Join Type| OTAA and ABP modes are available.
Application Key| Appkey for OTAA mode, the default is:
5572404C696E6B4C6F52613230313823.
Device Address| DevAddr for ABP mode, default is the 5th to 12th digits of SN.
Network Session Key| Nwkskey for ABP mode, default is
5572404C696E6B4C6F52613230313823.
Application Session Key| Appskey for ABP mode, default is
5572404C696E6B4C6F52613230313823.
LoRaWAN Version| V1.0.2 and V1.0.3 are available.
Work Mode| It’s fixed as Class A.
RX2 Data Rate| RX2 data rate to receive downlinks.
RX2 Frequency| RX2 frequency to receive downlinks. Unit: Hz
Spread Factor| If ADR is disabled, the device will send data via this spread
factor.
Confirmed Mode| If the device does not receive an ACK packet from the network
server, it will resend data once.
Rejoin Mode| Reporting interval ≤ 35 mins: the device will send a specific
number of LinkCheckReq MAC packets to the network server every reporting
interval or every double reporting interval to validate connectivity; If there
is no response, the device will re-join the network.
Reporting interval > 35 mins: the device will send a specific number of
LinkCheckReq MAC packets to the network server every reporting interval to
validate connectivity; If there is no response, the device will re-join the
network.
Set the number of packets sent| When rejoin mode is enabled, set the number of
LinkCheckReq packets sent.
---|---
ADR Mode| Allow the network server to adjust datarate of the device. This only
works with Standard Channel Mode.
TXPower| Transmit power of the device.
Note:
- Please contact sales for the device EUI list if there are many units.
- Please contact sales if you need random App keys before purchase.
- Select OTAA mode if you use Advantech IoT Cloud to manage devices.
- Only OTAA mode supports rejoin mode.
LoRaWAN Frequency Settings:
Select supported frequency and select channels to send uplinks. Make sure the
channels match the LoRaWAN ® gateway.
If frequency is set to CN470, AU915 or US915, you can enter the index of the
channel, you wish to enable in the input box, seperating them separated with
commas.
Examples:
1, 40: Enabling Channel 1 and Channel 40
1-40: Enabling Channel 1 to Channel 40
1-40, 60: Enabling Channel 1 to Channel 40 and Channel 60
All: Enabling all channels
Null: Indicates that all channels are disabled
3.3 Time Synchronization
-
ToolBox Sync:
Click Sync to sync the time via ToolBox App or ToolBox Software. -
Network Server Sync:
Change device LoRaWAN® Version as 1.0.3, the device will ask the network server for the time everytime it joins the network.
Note:
- This function is only applicable to network server using LoRaWAN ®1.0.3 version orlater.
- By default, the network server synchronizes time in the UTC+0 timezone. It’s suggested to sync the timezone via ToolBox to change the timezone.
3.4 Basic Settings
Parameters | Description |
---|---|
Reporting Interval | Reporting interval of transmitting data to the network |
server.
Range: 1~1440min; Default: 10min
Data Storage| Start or Stop reporting data storage locally.
Data Retransmission
| Star or stop data retransmission.
Record the network disconnection time point after startup, and retransmit the
periodic report data between the disconnection time point and the networking
time point after reconnecting networking.
Temperature Unit
| Change the temperature unit displayed on the screen and ToolBox.
Note: 1) The temperature reported by the device is mainly the value of
℃.
2) After changing the temperature unit, it is necessary to modify the value
of relevant threshold settings.
Button Lock| After it is enabled, the device cannot be turned off by pressing
the external power button.
** 24-Hour Clock| Click to change the time displayed on the screen and
ToolBox switches to the 24-hour clock from 12-hour clock.
Note:** The data storage time is not affected and remains at 24-hour clock.
Change| Change the password for ToolBox app or software to read/write.
Password| this device.
---|---
3.5 Advanced Settings
3.5.1 Calibration Settings
ToolBox supports temperature calibration. Type the calibration value and save,
the device will add the calibration to raw value, then display and report the
final value.
3.5.2 Threshold Settings
LEO-S552-TPG0 can set temperature threshold alarms, temperature change alarms
and so on. Enable the threshold settings and enter the threshold.
LEO-S552-TPG0 sensor will upload the current data instantly when the alarm is
triggered. Note that when you change the temperature unit, please re-configure
the threshold.
Parameters | Description |
---|---|
Temperature Threshold | When the temperature is over or below the threshold |
value, the device will report an alarm packet.
Alarm Dismiss Report
| After it is enabled, when the collected value changes from exceeding the
threshold range to not exceeding the threshold range, a threshold packet will
be reported to release the threshold.
---|---
Alarm Reporting Interval| Set the interval of the alarm report, the default
interval is 1min.
Alarm Reporting Times| Set the times of alarm report, the default is 1 time.
Temperature change greater than| When this function is enabled, the device
will report an alarm packet when the absolute value of the difference between
the two collected values exceeds the set threshold.
3.5.3 Data Storage
LEO-S552-TPG0 sensor supports storing more than 10,000 data records locally
and exporting data via ToolBox. The device will record the data according to
the reporting interval even not joining to network.
-
Export as csv file
Click Export, then select the data period and click Confirm to export data. The maximum export data period on ToolBox App is 14 days. -
Export as PDF file
LEO-S552-TPG0 sensor supports data plug-and-play by USB port, which exports encrypted & anti-tampering PDF data.
- USB data export without driver installation. After plugging into the USB interface, the PC will display a disk folder from device to display the stored data which is automatically exported as an encrypted document in PDF format (to prevent tampering – FDA CFR 21B regulatory requirements)
- Copy the PDF file to your PC’s another disk folder to get the data.
Note:
- The PDF file is not allowed to be edited to prevent tampering.
- When the device is configured by the ToolBox software on the PC, the disk folder from device will disappear. You can export PDF files again by unplugging and reinserting the USB port.
- The disk folder from device is only used to export PDF file and is not allowed to put other files.
3.5.4 Data Retransmission
LEO-S552-TPG0 sensor supports data retransmission to ensure the network server
can get all data even if the network is down for some time. There are two ways
to get the lost data:
- Network server sends downlink commands to enquire the historical data for specifying time range, refer to section Historical Data Enquiry.
- When the network is down if no response from LinkCheckReq MAC packets for a period of time, the device will record the network disconnected time and re-transmit the lost data after the device re-connects the network.
Here are the steps for retransmission:
-
Ensure the device time is correct, please refer Time Synchronization to sync thetime.
-
Enable Data Storage and Data Retransmission feature. Go to Device > Setting > LoRaWAN Settings to enable rejoin mode and set the number of packets sent. For example, the device will send LinkCheckReq MAC packets to the network server regularly to check any network disconnection; if there is no
response for 32+1 times, the join status will change to de-active and the device will record a data lost time point (the time it reconnected to the network). -
After the network connection is restored, the device will send the lost data from the point in time when the data was lost according to the data retransmission interval (600s by default).
Note :
- If the device is rebooted or re-powered when data retransmission is not
completed, the interrupted retransmission data will be retransmitted first
after the network is reconnected to the network, and then the newly triggered
retransmission data will be
transmitted. - If the network is disconnected again during data retransmission, it will only send the latest disconnection data.
- The retransmission data format is started with “20ce”, please refer to section Historical Data Enquiry.
- Data retransmission will increase the uplinks and shorten the battery life.
3.6 Maintenance
3.6.1 Upgrade
- Download firmware from Advantech website to your smartphone or computer.
- Click Browse to import firmware and upgrade the device.
Note:
- Operation on ToolBox is not supported during a firmware upgrade.
- Only the Android version of ToolBox App supports the upgrade feature.
3.6.2 Backup
LEO-S552-TPG0 supports configuring backup setting for easy and quick device
configuration in bulk. Backup is allowed only for devices with the same model
and LoRaWAN® frequency band.
- Go to Template page on the App and save the current settings as a template. You can also edit the template file.
- Select one template file saved in the smartphone and click Write, then attach the smartphone to another device to write the configuration.
Note : Slide the template item left to edit or delete the template. Click the template to edit the configurations.
3.6.3 Reset to Factory Default
Please select one of the following methods to reset the device:
Reset Via Hardware: Hold on the reset button (internal) for more than 10s.
Reset Via ToolBox App: Go to Device > Maintenance to click Reset button, then
attach the smartphone with NFC area to the device to complete the reset.
Reset via ToolBox Software: Go to Maintenance > Backup and Reset to click
Reset button.Note: Reset operation will not
clean the stored data, please click Data Cleaning or Clear button to clear
data if necessary.
Installation
Device Installation
Wall Screw Mounting:
- Fix the wall plugs to a flat surface according to the device mounting holes, then secure the device to the wall plugs using screws. When installing, please ensure the LCD display is positioned vertically on the ground below eye level for clear visibility of the content.
- Cover the screws with cover caps.
Device Payload
All data are based on the following format (HEX), the Data field should follow little-endian:
Channel 1 | Type1 | Data1 | Channel2 | Type2 | Data2 | Channel 3 | … |
---|---|---|---|---|---|---|---|
1 Byte | 1 Byte | N Bytes | 1 Byte | 1 Byte | M Bytes | 1 Byte | … |
5.1 Basic Information
LEO-S552-TPG0 reports basic information about the sensor every time it joins
the network.
Channe l | Type | Description |
---|---|---|
ff | 01(Protocol Version) | 01=>V1 |
09 (Hardware Version) | 01 00 => V1.0 | |
0a (Software Version) | 01 01 => V1.1 | |
0b (Power On) | Device is on | |
0f (Device Type) | 00: Class A, 01: Class B, 02: Class C | |
16 (Device SN) | 16 digits |
Example:
ff0bff ff0101 ff16 6723d29626820016 ff090100 ff0a0101 ff0f00
Chann el| Type| Value| Chann el| Type|
Value
ff| 0b (Power On)| ff (Reserved)| ff| 01 (Protocol Version)| **
01 (V1)
Chann| Type| Value| Chann| Type| Value
el| | | el| |
---|---|---|---|---|---
** ff| 16 (Device SN)| 6723d296
26820016| ff| 09
(Hardware version)| 0100 (V1.0)
Chann el| Type| Value| Chann el| Type|
Value
ff| 0a (Software version)| 0101 (V1.1)| ff| 0f (Device Type)| 00
(Class A)
5.2 Sensor Data
LEO-S552-TPG0 reports sensor data according to reporting interval (10 min by
default).
Note: CH1=Left channel of LEO-S552-TPG0, CH2=Right channel of LEO-S552-TPG0.
Item | Chann el | Type | Description |
---|---|---|---|
Battery Level | 01 | 75 | UINT8, Unit: %, [1-100] |
Temperature (CH1) | 03 | 67 | INT16/10, Unit: °C |
Temperature (CH2) | 04 | 67 | INT16/10, Unit: °C |
Threshold Alarm (CH1) | 83 | 67 | 3 Bytes, Temperature(2B) + Alarm Status (1B) |
Temperature: INT16/10, Unit: °C Alarm Status: 00 -Alarm dismiss, 01 -Alarm
Threshold Alarm (CH2)| 84| 67| 3 Bytes, Temperature(2B) + Alarm Status (1B)
Temperature: INT16/10, Unit: °C Alarm Status: 00 -Alarm dismiss, 01 -Alarm
Temperature_cha nge Alarm (CH1)| 93| d7| 5 Bytes, Temperature(2B) +
Temperature_change(2B) + 02 Temperature: INT16/10, Unit: °C
Temperature_change: INT16/100, Unit: °C
Temperature_cha nge Alarm (CH2)| 94| d7| 5 Bytes, Temperature(2B) +
Temperature_change(2B) + 02 Temperature: INT16/10, Unit: °C
Temperature_change: INT16/100, Unit: °C
Example:
-
Periodic Packet
017564 0367f900 040001Channel| Type| Value| Channel| Type| Value
01| 75 (Battery)| 64 => 100%| 03| 67 (Temperature of Left Channel)| f9 00 => 00 f9
=>249/ 10
=24.9°C
Note : When the channel does not connect any sensor, it will report periodic packet as 030001 (CH1 no sensor) or 040001 (CH2 no sensor).
-
Temperature Threshold Alarm Packet
8367 5201 01Channel| Type| Value
83
|
67
(Temperature)
| 52 01 => 01 52 => 338/10 = 33.8°C
01 => Temperature Threshold Alarm
3. Temperature_change Alarm Packet
8367 5201 01
Channel| Type| Value
94| 67
| Temperature: 4e 01 => 01 4e => 334/10 = 33.4°C
Temperature_change: c6 02 => 02 c6 => 710/100=7.1°C
02 => Temperature_change Alarm
5.3 Downlink Commands
LEO-S552-TPG0 supports downlink commands to configure the device. The
application port is 85 by default.
Note : CH1=Left channel of LEO-S552-TPG0, CH2=Right channel of
LEO-S552-TPG0.
Chann el | Type | Description |
---|---|---|
ff | 10 (Reboot) | ff (Reserved) |
8e (Reporting Interval) | 3 Bytes, |
Byte 1: 00
Byte 2-3: interval time, UNIT16, unit: min, [1-1440]
02 (Collecting Interval)| 2 Bytes, UINT16, unit: s
| 17 (UTC Time Zone)| 2 Bytes, INT16/10
---|---|---
25 (Button Lock)| 2 Bytes, 0000: disable, 0100: enable
e9 (Time Type)| 1 Byte, 00: 12-hours clock, 01: 24-hours clock
2d (Screen)| 1 Byte, 00: disable, 01: enable, ff: enable when temperature
sensor is connected (default)
ea (Temperature Calibration)| 3 Bytes,
Byte 1: 00-diable CH1, 80-enable CH1; 01-disable CH2, 81-enable CH2
Byte 2-3: calibration value, INT16/10, unit: °C
eb (Temperature Unit)| 1 Byte, 00: °C, 01: °F
06 (Threshold Alarm)| 9 Bytes,
Temperature threshold:
CTRL(1B)+Min(2B)+Max(2B)+Alarm
Reporting Times(2B)+Alarm Reporting Interval(2B)
• CTRL:
Bit2~Bit0:
000=disable 001=below 010=above 011=within 100=below or above Bit5~Bit3:
001=Temperature Threshold of CH1 010=Temperature Threshold of CH2
Bit6: 1=Alarm Enabled, 0=Alarm Disabled Bit7: 1=Alarm Dismiss Report Enabled,
=Alarm Dismiss Report Disabled
• Min/Max: UNIT16/10, unit: °C
• Alarm Reporting Interval: UINT16, unit: min
Temperature_change threshold:
| | CTRL(1B)+0000+Change_value(2B)+000000 00 (4B)
• CTRL:
58=Temperature_change Threshold of CH1 Enabled
18=Temperature_change Threshold of CH1 Disabled
60=Temperature_change Threshold of CH2 Enabled
20=Temperature_change Threshold of CH2 Disabled
• Change value: UNIT16/10, unit: °C
---|---|---
68 (Data Storage)| 00: disable, 01: enable
69 (Data Retransmission)| 00: disable, 01: enable
6a (Data Retransmission Interval)| 3 Bytes
Byte 1: 00
Byte 2-3: interval time, unit:s range: 30~1200s (600s by default)
Example:
-
Set reporting interval as 20 minutes.
ff8e001400Channel| Type| Value
ff| 8e (Reporting Interval)| 14 00 => 00 14 = 20 minutes -
Reboot the device.
ff10ffChannel| Type| Value
ff| 10 (Reboot)| ff (Reserved) -
Set time zone.
ff17ecffChanne l| Type| Value
ff| 17| ec ff => ff ec = -20/10=-2 the time zone is UTC-2 -
Enable temperature threshold and set the threshold value as over 30°C.
ff06 ca 0000 2c01 01000200Channel| Type| Value
ff| 06 (Threshold Alarm)| CTRL: ca =11 001 010
010 = above
001 =CH1 Temperature Threshold 1 = enable the Threshold Alarm, 1=Alarm Dismiss Report Enabled
Max: 2c 01 => 01 2c => 300/10 = 30°C
Alarm Reporting Times: 01 00=>00 01=1
Alarm Reporting Interval: 02 00=>00
02=2 mins
5.4 Historical Data Enquiry
LEO-S552-TPG0 supports sending downlink commands to enquire historical data
for specified time point or within a certain time range. Before utilizing this
feature, it is import to make sure the device time is correct and data storage
feature was enable to store the data.
Command format:
Channel | Type | Description |
---|---|---|
**** fd | 6b (Enquire data in time point) | **** 4 Bytes, unix timestamp |
6c (Enquire data in time range) | Start time (4 bytes) + End time (4 bytes), |
Unix timestamp
6d (Stop query data report)| ff
ff| **** 6a (Report Interval)| 3 Bytes,
Byte 1: 01
Byte 2: interval time, unit: s, range: 30~1200s (60s by default)
Reply format:
Channel | Type | Description |
---|---|---|
**** fc | **** 6b/6c | 00: data enquiry success |
01: time point or time range invalid 02: no data in this time or time range
**** 20| ce (Historical Data)| 9 Bytes
Data time stamp (4 B) + Chn_mask (1 B)+CH1
Data(2B) + CH2 Data (2B)
Chn_mask:
Bit | 7- 4 | 3- 0 |
---|---|---|
CH1 (Left Channel) | CH2 (Right Channel) | |
0000=No |
0001=Temperature Threshold Alarm 0010=Temperature Threshold Alarm Dismiss
0011=Temperature_change Threshold Alarm
0100=Temperature Periodic Report
Note:
- The device only uploads no more than 300 data records per range jnquiry.
- When enquiring about the data in time point, it will upload the data that is the closest to the search point within the reporting interval range. For example, if the device’s reporting interval is 10 minutes and users send a command to search for 7:00’s data, if the device finds there is data stored in 17:00, it will upload these data.
If not, it will search for data between 16:50 to 17:10 and upload the data which is the closest to 17:00.
Example:
-
Enquire historical data between 2023/10/19 15:30:00 to 2023-10-26 15:30:00.
fd6c f8da3065 78153a65Channel| Type| Value
fd| 6c (Enquire data in time range)| Start time: f8da3065=> 6530daf8 = 1697700600s =2023/10/19 15:30:00 End time: 78153a65 => 653a1578 = 1698305400s =2023-10-26 15:30:00
Reply :
fc6c00
Channel| Type| Value
fc| 6c (Enquire data in time range)| 00: data enquiry success
20ce 78153a65 6401000501
Chann el| Type| Time Stamp| Value
20| ce (Historic al Data)| 78153a65 =>
653a1578 =
1698305400s
= 2023-10-26
15:30:00| CH2 is Temperature Periodic Report CH2: 0501=>0105= 261/10= 26.1 °C
---|---|---|---
FCC Caution
§ 15.19 Labelling requirements.
This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions:
- This device may not cause harmful interference, and
- this device must accept any interference received, including interference that may cause undesired operation.
§ 15.21 Information to user.
Any Changes or modifications not expressly approved by the party responsible
for compliance could void the user’s authority to operate the equipment.
§ 15.105 Information to the user.
Note : This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation.
This equipment generates uses and can radiate radio frequency energy and, if
not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated withmini mum distance 20cm between the radiator & your body.