Firestopping for flammable pipes up to 250 mm in diameter with European Technical Approval.

Applications

  • Sealing flammable pipes from 32 mm to 250 mm in diameter in penetrations through fire compartment walls and floors
  • Pipe materials: PVC-C, PVC-U, PE, PE-HD, PE-X, PE-S2, PP, PP-R, ABS, Al-composite
  • Suitable for use in openings in concrete, aerated concrete, masonry, drywall and in combination with coated board
  • Different backfilling and sealing materials are covered

Advantages

  • Quick and easy closure without use of a tool
  • Adjustable position tabs for simple fastening
  • Sound decoupling strip based on PE (foam) can be used
  • Low profile for tight installations

Technical Data

  • Base materials Concrete, Masonry, Drywall
  • Minimum wall thickness 100 mm
  • Minimum floor thickness 150 mm
  • Storage and transportation temperature – range –5° C to 50° C
  • Application temperature range –5° C to 50° C
  • Temperature resistance range –20° C to 100° C
  • Closure of annual gap Gypsum plaster, cementitious mortar, Hilti Firestop Acrylic Sealant CFS-S ACR

Nominal pipe diameter| Number of hooks and fasteners| Order designation| Sales quantity| Item number
---|---|---|---|---
50 mm| 2| Firestop Collar CFS-C P 50 / 1.5″| 1 pc| 435406
63 mm| 2| Firestop Collar CFS-C P 63 / 2″| 1 pc| 435407
75 mm| 3| Firestop Collar CFS-C P 75 / 2.5″| 1 pc| 435408
90 mm| 3| Firestop Collar CFS-C P 90 / 3″| 1 pc| 435409
110 mm| 4| Firestop Collar CFS-C P 110 / 4″| 1 pc| 435410
125 mm| 4| Firestop Collar CFS-C P 125 / 5″| 1 pc| 435411
160 mm| 6| Firestop Collar CFS-C P 160 / 6″| 1 pc| 435412
180 mm| 8| Firestop Collar CFS-C P 180 / 7″| 1 pc| 435413
200 mm| 8| Firestop Collar CFS-C P 200 / 8″| 1 pc| 435414
225 mm| 10| Firestop Collar CFS-C P 225 / 9″| 1 pc| 435415
250 mm| 12| Firestop Collar CFS-C P 250 / 10″| 1 pc| 435416

INSTRUCTION FOR USE: CFS-C P

HILTI-CFS-C-P-Collar-Firestop-fig2

GENERAL INFORMATION

HILTI-CFS-C-P-Collar-Firestop-fig3

Note: The opening diameter should not be larger than the collar outside diameter to allow a safe fixing of the collar to wall/floor

MAIN APPROVED APPLICATIONS

HILTI-CFS-C-P-Collar-Firestop-fig4

e.g. Magnaplast (R): Skolan dB (R), Phonex AS (R); Pipelife (R): Master 3 (R); POLOPLAST (R): Polo Kal NG (R); POLOPLAST (R): Polo Kal 3 S (R); Rehau (R), Raupiano Plus (R), Wavin (R); AS (R)/KeKelit (R); Phonex AS (R); Wavin (R); SciTech (R). Close (R); Blue Power (R), Cloes (R); PhoNoFire (R), Valsire (R); Triplus (R), Valsire (R); Silere (R), Geberit (R); Silent PP (R) Excerpt of ETA document. Check the exact field of application (pipe types and diameters, pipe types, diameters and wall thickness, insulations types) in the ETA 10/0404 document.

OTHER APPROVED APPLICATIONS

HILTI-CFS-C-P-Collar-Firestop-fig5 HILTI-
CFS-C-P-Collar-Firestop-fig6

CHARACTERISTICS OF FIRESTOP COLLAR CFS-C P

HILTI-CFS-C-P-Collar-Firestop-fig7

Hilti Corporation
9494 Schaan, Liechtenstein
P +423-234 2965
www.facebook.com/hiltigroup
www.hilti.group

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals