ProEE PE-R HF Rectifier Module 24V-60A User Manual

June 3, 2024
ProEE

ProEE-logoProEE PE-R HF Rectifier Module 24V-60A Electrical Specifications

Input Feature

Input Single input
Input Voltage Range 90Vac to 290Vac
Rate input Voltage 110Vac / 220Vac
Normal Input 100Vac to 240Vac
Frequency Range 45Hz-65Hz
Max Input Current 10.2A±10%@176Vac/1800W
Surge Current Compliant Standard:ETSI300132-3
Efficiency ≥90%@220Vac@ 220Vac 100% load
PF ≥0.99@220Vac/60A
Leakage Current <3.5mA@264Vac
Input Fuse L Wire ,Fuse 25A
Max input Voltage 310Vac

Output Feature

Output voltage current regulation

Output Voltage +24Vdc
Output Voltage Regulation +24±0.1Vdc
Output Range adjustable Range +21Vdc~+29Vdc
Load sharing(50%~100% Loading) ≤±5%
Line regulation ±0.1%
Load regulation ±0.5%
Voltage precision ±0.6%
Min-current 0A
Rate current 60A
Peaking current 65A
Tempe. coefficient(1/℃) ≤±0.02%
Rate Capacity 1800W(150Vac~290Vac)

1200W(90Vac~150Vac)

Note: The rectifier module output current regulation and communication interruption are as follows:

  1. The output current of the rectifier module can be adjusted according to the current command. The adjustment range is 1A~60A.
  2. Communication fault more than 1 minute (Rectifier and Control monitor),A .Rectifier module output Voltage automatic recovery default Voltage 24V and limited current function not working;b.if the rectifier modules are controller by monitor and Power off, then rectifier system will power on(if the rectifier fault, it can not be turned on again)

Efficiency FigureProEE-PE-R-HF-Rectifier-Module-24V-60A-
fig-1

Output ripple and noise

Output Voltage Ripple and Noise (Peaking-Peaking)
+24Vdc 200mVp-p@ 25℃,(Testing based on rate Input voltage    & Output Voltage

,100%

loading )

Note: Ripple and Noise testing:Ripple and noise Default as 20 MHz

Output dynamic response

Voltage

overshoot

| Adjustment

slope

| Loading| Voltage

overshoot

---|---|---|---


+24V±5%

| ****

0.1A/uS

| 25% to 50% load

50% to 75%load

| ****

≤200us

Note: Adjustment slope Cycle 4ms

Output Overshoot

Output Voltage Overshoot Voltage
On off
+24V ≤5%

Note: Loading Range Minimum to maximum

Power Switch Point

Rated Switching Point Min-Switching Point Max-Switching Point
150Vac 145Vac 160Vac

ProEE-PE-R-HF-Rectifier-Module-24V-60A-fig-2

Power on output delay time

Output Voltage 220Vac@25℃
+24V 3S~10S

Note: The power-on delay time is the time from AC power-on to output voltage (to 23VDC)

LED indicator

The power LED is installed on the power panel side and the output status is shown in the table below

Indicator LED Color NormalStatus Abnormal status Abnormal Reasons
Power running indicators Green On off

Protect indicators

|

Yellow

|

Off

|

on

| Temperature pre-alarm (working    temperature more than 65 °C ,then over temperature shutdown); Sleep shutdown (the module only lights the
 |  |  |  | protection indicator when the system is shut down, and the module does not report alarm).
---|---|---|---|---

Fault Indicator

|

Red

|

Off

|

on

| Output Over voltage power off 、

Fan fault、Over-Temp. Power off Rectifier module inner fault。

Noise Voltage

Noise Voltage Max Note

Phone noise weighting

Voltage

| ≤2mV|


broadband noise Voltage

| ≤50mV| 3.4~150KHz
≤20mV| 0.15~30000KHz
Radio interference noise, or radio frequency noise| ≤5mV| 3.4~150KHz
≤3mV| 150~200KHz
≤2mV| 200~500KHz
≤1mV| 500~30000KHz

Rectifier module and monitor module communication function

RS485 communication mode (half-duplex, double-line) is adopted between the rectifier module and the monitoring module.
The RS485 interface in the rectifier module needs to be isolated. The RS485 power supply is +5Vdc (regulation accuracy ±5%), which is provided by the monitoring module.
The main monitoring information of the rectifier module is:

  1. Adjust Voltage and Current function: meet the requirements of battery floating charge and meet the adjust voltage requirements;
  2. Single module switch machine control;
  3. Alarm information:
    • Mains failure: mains failure (AC input over voltage);
    • Module protection: temperature pre-alarm;
    • Module failure: Output over voltage shutdown, fan failure, over temperature shutdown or no output caused by internal causes of other modules; (module is in: sleep shutdown state, mains failure does not report module failure).

Protection Function

Output Limited Current Protection

Output Voltage| Limited Current

point

| Note
---|---|---
+24V| 105%~110%| Limited current output

Output short circuit Protection

Output Voltage Note
+24V Restart after Protection

Output Over Voltage Protection

Output Voltage Protection Point
+24V 33±2V. (Lock)

Note : After entering the lock protection state, you need to disconnect the AC power first, and then re-power on, the rectifier module can be re- operated.

Input Over Voltage Protection

Input Voltage Note
310±10Vac Output off,Self-recovery after normal voltage
  output recovery point backlash>10V

Note: Input overvoltage protection should be tested at 50A rated load

Input under Voltage Protection

Input Voltage Note
80±5Vac Output is closed. Self-recovery after

normal Voltage

 | Output Recovery point backlash>5V

Over -Temp.Protection

Temp. Note
≤55℃ With maximum output Capacity ability , without

over-temperature protection and the module is running normally.

55℃~65℃| The module can be automatically derate to ensure long-term stable output of at least 50% of rated power

65℃| Power off,After power off,Recovery temperature difference    >10℃

Insulation Performance

Insulation resistance

Input & output| Testing     voltage     500VDC,Insulation Resistance ≥10M

(normal atmospheric pressure, normal temperature, relative humidity <90%,

no condensation)

---|---
Input & ground
Output & ground

Isolation Voltage

Input & output DC Voltage 4240Vdc 1minute ≤30mA
Input & ground DC Voltage 2120Vdc 1minute ≤30mA
Output & ground DC Voltage 710Vdc 1minute ≤30mA

Safety standard

Power supply safety meets the following standards:
GB4943-2001

EMC

EMI

  1. Compliant with the the Below Standard:
    Conduction Emission :
    *EN55022/GB9254, CLASS A
  2. Radiated Emission :
    *EN55022/GB9254, CLASS A

EMS
The power supply shall compliance with the following Criterion:

  1. ESD
    *GB17626.2/IEC61000-4-2

    • the Chassis, the parts that can be touch during normal operation: contact discharge +/-6KV; air discharge +/-8KV, Criterion B (power on test)。
    • the Chassis , the parts that can be touch during normal operation: contact discharge +/-8KV; air discharge +/-10KV,Criterion R (not powered during test)。
    • signal interface inner conductor: contact discharge +/- 2KV Criterion R; (power on test, no test on address line and current line)
  2. EFT
    *GB17626.4/IEC61000-4-4 Level 3 Standard: A

  3. SURGE
    *GB17626.5/IEC61000-4-5 Level 4 Standard: B

  4. DIP
    *GB17626.11/IEC61000-4-11
    Power DIP voltage drop requirement Table (220Vac)

Drop to| Drop Phase| Drop

Time

| Standard
---|---|---|---
0%Ut| 0°/45°/90°/135°/180°/225°/270°/315°| 10ms| B
40%Ut| 0°/45°/90°/135°/180°/225°/270°/315°| 20ms| B
70%Ut| 0°/45°/90°/135°/180°/225°/270°/315°| 100ms| B

Input harmonic current
*IEC 61000-3-2 [6] CLASS A

voltage fluctuations and flicker
*IEC 61000-3-3
Pst≤1.0;P1t≤0.65;dc≤3%;dmax≤4%;d(t) more than 3% time≤200ms

lightning test
In the system application, the AC input can withstand the impact current
waveform of n more than 5 kA, 8/20us, positive and negative 5 times, each
interval of 1 minute (see standard: YD 5098-2001)

Immunity to conducted disturbances
*IEC61000-4-6 Level 3 Standard:A

Radiated interference
*IEC61000-4-3 Level 3 Standard:A

Testing Standard:

A: The power supply did not have any degradation in performance throughout the test, and it was completely the same as the specifications specified in the power supply specification.
B: During the test, the performance of the power supply is allowed to temporarily decrease, but it can be restored after the test is over.
C: A short-term loss of function is allowed, but the end of the test can be restored automatically or manually.
R: Damage to other devices other than the fuse device is not allowed during the test.

Working Environment

Ambient Temperature

  • Working Temp.: -40℃to +55℃.
  • Storage Temp: -40℃to +70℃.
  • Transport Temp: -40℃to +70℃.

Relative Humidity

  • Working RH: 5%~95% (No condensation)
  • Storage RH: 5%~ 95% (No condensation)

Altitude

  • working Altitude: 0~4000M,based 2000m,For every 200 m increase in altitude, the temperature drops by 1℃
  • Storage Altitude : 0~4000M,based 2000m,For every 200 m increase in altitude, the temperature drops by 1℃

Cooling

*The rectifier module with fan, forced air cooling, air is sent out after the wind is coming forward, the fan is placed in the front, and the fan has temperature control speed regulation function.

Vibrate Tolerance

  • Working environment: sinusoidal vibration: 5~9Hz: amplitude 3.5mm; 9~200Hz: acceleration 10m/s2; 3 axial direction, sweeping vibration 5 times in each direction, 1OCT/min (1 octave/min).
  • Transportation environment: random vibration: 2~10Hz: 10m2/s3; 10~200Hz: 3m2/s3; 200~500Hz: 1m2/s3;3 axial, 30min in each direction.
    (Reference standard: ETS300019-2)

Impact Tolerance

  • Working environment: acceleration 250m / s2; pulse width 6ms; 3 axes 6 to each collision 500 times.
  • Transportation environment: acceleration 400m / s2; pulse width 6ms; 3 axes 6 to each collision 500 times.
    (Reference standard: ETS300019-2)

Drop
Transportation environment: drop height 1m; bottom surface 1 time.
(Reference standard: ETS300019-2)

Size

H×W×D: 83.8mm×112mm×257mmProEE-PE-R-HF-Rectifier-Module-24V-60A-
fig-3

N.Weight: <4.8kg

Chassis IP Protection Level
IP20(User normal maintenance operation surface)

Transportation and storage

The product should be placed in a warehouse that is affected by dry, ventilated and non-corrosive gases with a temperature of -10 ° C to 40 ° C and a relative humidity of not more than 80%.
The product has a strong packaging when transported. The outside of the box complies with the relevant national standards and should have signs such as “careful handling” and “moisture proof”. The box containing the product is allowed to be transported by any means of transport. Direct rain and snow strikes and mechanical impacts should be avoided during transportation.

Other Requirement

Item Requirement Note
noise Less than 55dBa
odor not produce odor and harmful odor
Components All devices meet the de-rating
Hot swap Rectifier module for hot swap
Failure isolation After the rectifier module fails, it can

be reliably separated from the system.

|

MTBF

1*105h;25℃,Rate Input,100% loading.

Connector PIN Definition

 | Pin| Signal| Remark| Contact

sequence

---|---|---|---|---
AC input| 1| Rectifier module AC input| L| 2
2| Rectifier module protection Ground| PE| 1
 | 3| Rectifier module AC input| N| 2|
---|---|---|---|---|---
 |


DC

output and

| 1| Rectifier module address wire| ADDRES

S0

| 3|
2| Rectifier module address wire| ADDRES

S1

| 3|
3| Rectifier module share current wire| LOADS

HARE+

| 3|
Signal| 4| Rectifier forbidden| INHIBIT| 4|
 |  |  |  |  | CURRE NT

LIMIT

|  |
 | 5| Rectifier

function

| output| limited| current| 3|
 | 6| Rectifier function| output| limited| current| CURRE NT

LIMIT

| 3|
 | 7| Rectifier address wire| ADDRES

S2

| 3|
 | 8| Rectifier address wire| ADDRES

S3

| 3|
 | 9| Rectifier address wire| LOADS

HARE-

| 3|



DC

output

| 10| RS485 Power +| +3.3V/+

5V

| 3|
11| RS485 Power-| +3.3V/+

5VGND

| 3|
12| Rectifier communication    wire| RS485-| 3|
and Signal
13| Rectifier address wire| ADDRES

S4

| 3|
14| NC| NC| 3|
 | 15| Rectifier communication    wire| RS485+| 3|
 | 16| Address Wire GND| ADDR_G

ND

| 3|
 |  |  |  |  |
 | As

Figure

| Pre- charge| Pre-Cha

rge

| 1|
 | As

Figure

| Rectifier output 48V+| DC+| 2|
 | As

Figure

| Rectifier output 48V+| DC+| 2|
 | As

Figure

| Rectifier output 48V-| DC-| 2|
 | As

Figure

| Rectifier output 48V-| DC-| 1|

Block address definition:

The module internally pulls up the address line. ADDRESS0~4 can be left floating outside the module or shorted to the address line GND.
Shorting means “1”, floating means “0”, such as ADDRESS0 external and address If the line GND is shorted and the other address lines are left floating, the rectifier module address is

  1. The address range of the rectifier module is 0 to 31.。ProEE-PE-R-HF-Rectifier-Module-24V-60A-fig-4
  2. Pre-Charge pin is used to pre-charge the output capacitor inside the rectifier module when the rectifier module is hot swapped.。

Product Maintenance

  1. Product free maintenance time
    The free maintenance level of this product is Class B, and the free maintenance period (warranty period) is 1 year.

  2. On-site maintenance
    The power module has a hot swap function, and the on-site repair mode is module replacement.