maxsel DTSU666-HW Smart Power Sensor User Guide

June 3, 2024
maxsel

maxsel-LOGO

maxsel DTSU666-HW Smart Power Sensor

Overview

Dimensions

DTSU666-HWmaxsel-DTSU666-HW-Smart-Power-Sensor-01

Note: The dimensional tolerance is ± 1 mm.

Appearance

Specifications on the front panel


Nameplate


Key Specifications
Category DTSU666- HW
Nominal voltage 230 V AC/400 V AC, 50 Hz/60 Hz
Current measurement range Direct connection: 0–80 A Connection through

current transformers: > 80 A
Voltage measurement range| 90–1000 V (line voltage; potential transformers are required if the voltage is greater than 500 V)
Electricity metering accuracy| Class 1 (error within ±1%)
Power grid system| Three-phase four-wire or three-phase three-wire
Baud rate| 4800/9600/19200/115200 bps (default value: 9600 bps)
Operating temperature| –25℃ to +60℃
Installation mode| Guide rail-mounted
Certification| CE, RCM, and UKCA

Port Definition
  • Input voltage: When the line voltage is less than or equal to 500 V, connect the meter directly. When the line voltage is greater than 500 V, connect the meter through potential transformers.
  • Input current: When the input current is 0 A to 80 A, connect the meter directly (channel 1). When the input current is greater than or equal to 80 A, connect the meter through current transformers (channel 2).

Cable Inlet                 Cable Outlet


Installing the DTSU666-HW

  1. Install the Smart Power Sensor on the standard guide rail of DIN35mm.
  2. Press the Smart Power Sensor downwards onto the guide rail, and then push it in place along the guide rail.

maxsel-DTSU666-HW-Smart-Power-Sensor-05

Installing Cables

Preparing Cables

Cable| Port| Type| Conductor Cross- sectional Area Range| Outer Diameter| Source
---|---|---|---|---|---
Channel 1 voltage cable| UA-1 and 3| Single-core outdoor copper cable| 25 mm2| 10 mm| Prepared by the customer
UB-4 and 6
UC-7 and 9
UN-10 and 12
Channel 2 voltage cable| UA-1| Single-core outdoor copper cable| 4–25 mm2| 5–10 mm| Prepared by the customer
UB-4
UC-7
UN-10
Channel 2 current transformer cable| IA*-31|

Single-core outdoor copper cable

| 2–4 mm2| 3–5 mm| Prepared by the customer or supplied with current transformers
IA-33
IB-34
IB-36
IC
-37
IC-39
Communications cable| RS485A-24| Two-core outdoor shielded twisted pair copper cable| 0.25–1.5

mm2

| 4–11 mm| Supplied by the manufacturer
RS485B-25

Note: The maximum torque of 1, 3, 4, 6, 7, 9, 10, and 12 terminal screws is 1.7 N·m, and the recommended torque is 0.9–1.1 N·m. The maximum torque of 31, 33, 34, 36, 37, 39, 24, and 25 terminal screws is 0.4 N·m, and the recommended torque is 0.15–0.25 N·m.

Note:   Each phase of UA, UB, and UC in the Smart Power Sensor is connected with a fuse and a thermistor to prevent damage caused by external short circuits. UA, UB, and UC do not need external fuse protection.


Wiring Scenarios
Current ≤ 80 A > 80 A ≥ 0 A
Line voltage ≤ 500 V > 500 V
Connection mode Current and voltage

direct connection

| Connection through current transformers and voltage direct connection| Connection through current transformers and potential transformers
Connection setting| Direct connection: SPEC = 1 (default)| Connection through transformers: SPEC = 0
Current transformation ratio| CT = 1

(default)

| CT = Ratio of the installed current transformer
Potential transformation ratio| PT = 1.0
(default)| PT = Ratio of the installed potential transformer
Wiring mode| 3P4W: net = n.34
(default)| 3P3W: net = n.33| 3P4W: net = n.34
(default)| 3P3W:
net = n.33| 3P4W:
net = n.34
(default)| 3P3W: net = n.33

Note: You need to set parameters after cable connections are complete. For details, see section 4 “Display and Parameter Settings”.

Current and Voltage Direct Connection (Current ≤ 80 A and Line 3.3

Voltage ≤ 500 V)

Smart Logger networking

  • Three-phase four-wire connection
    Note: In the SmartLogger networking scenario, the power meter is connected to the SmartLogger. In the non-SmartLogger networking scenario, the power meter is connected to the inverter. ****

    1. Shield layer of the signal cable
  • Three-phase three-wire connection

    1. Shield layer of the signal cable

Smart Dongle networking

  • Three-phase four-wire connection
    1. Shield layer of the signal cable
  • Three-phase three-wire connection
    1. Shield layer of the signal cable

Note: You need to set parameters after cable connections are complete. For details, see section 4 “Display and Parameter Settings”.

Connection Through Current Transformer and Voltage Direct Connection

(Current > 80 A, Line Voltage ≤ 500 V)

Current transformers specifications: The accuracy class is 0.5, and the current on the secondary side is 1 A or 5 A.

SmartLogger networking

  • Three-phase four-wire connection
    Note: In the SmartLogger networking scenario, the power meter is connected to the SmartLogger. In the non-SmartLogger networking scenario, the power meter is connected to the inverter.

    1.  Shield layer of the signal cable
  • Three-phase three-wire connection

Caution: Please ensure that the ground cable is installed securely. Poor grounding may cause electric shocks.

Note:

  • You need to set parameters after cable connections are complete. For details, see section 4 “Display and Parameter Settings”.
  • For the three-phase three-wire connection, phase B does not need to connect to a current transformer.

Smart Dongle networking

  • Three-phase four-wire connection

    1. Shield layer of the signal cable
  • Three-phase three-wire connection
    Caution: Please ensure that the ground cable is installed securely. Poor grounding may cause electric shocks.
    Note:

  •  You need to set parameters after cable connections are complete. For details, see section 4 “Display and Parameter Settings”.

  • For the three-phase three-wire connection, phase B does not need to connect to a current transformer.

    1. Shield layer of the signal cable
Connection Through Current Transformer and Potential

Transformer (Current ≥ 0 A, Line Voltage > 500 V)

  • Three-phase four-wire connection
  • maxsel-DTSU666-HW-Smart-Power-Sensor-15 Three-phase three-wire connectionmaxsel-DTSU666-HW-Smart-Power-Sensor-16

Caution:   Please ensure that the ground cable is installed securely. Poor grounding may cause electric shocks.

Note: You need to set parameters after cable connections are complete. For details, see section 4 “Display and Parameter Settings”.

Display and Parameter Settings

Display

The button → is used to switch the displays. Set parameter disp to enable the rotation display function.

No.

|

Display

|

Description

|

No.

|

Display

|

Description

---|---|---|---|---|---

1

| | Positive active energy = 10000.00 kWh|

2

| | Negative active energy = 2345.67 kWh

3

| | None parity, 8 data bits,

and 1 stop bit; baud rate = 9600 bps (default)

|

4

| | 011 represents address (default)

5

| | Phase A voltage

= 220.0 V

|

6

| | Phase B voltage

= 220.1 V

7

| maxsel-DTSU666-HW-Smart-Power-Sensor-18| Phase C voltage

= 220.2 V

|

8

| | Phase A current

= 5.000 A

9

| maxsel-DTSU666-HW-Smart-Power-Sensor-19| Phase B current

= 5.001 A

|

10

| | Phase C current

= 5.002 A

11

| maxsel-DTSU666-HW-Smart-Power-Sensor-20| Total phase active power = 3.291 kW|

12

| maxsel-DTSU666-HW-Smart-Power-Sensor-45| Phase A active power = 1.090 kW

13

| | Phase B active power = 1.101 kW|

14

| | Phase C active power

= 1.100 kW

15

| maxsel-DTSU666-HW-Smart-Power-Sensor-22| Total phase power factor PFt = 0.500|

16

| | Phase A power factor

PFa = 1.000

17

| | Phase B power factor

PFb = 0.500

|

18

| | Phase C power factor

PFc = –0.500

Parameter Settings
No. Parameter Value Range Description

1

| | 1–6553| Current transformer ratio

2

| | 0.1–999.9| Potential transformer ratio

3

|

|

1: 645

2: n.2

3: n.1

4: E.1

5: 0.1

| Communication protocol switchover: 1: Factory mode

2: None parity, 2 stop bits, n.2 3: None parity, 1 stop bit, n.1 4: Even parity, 1 stop bit, E.1 5: Odd parity, 1 stop bit, 0.1

4

| |

1–247

| Modbus communication address

5

|

|

0: 1.200

1: 2.400

2: 4.800

3: 9.600

4: 19.20

5: 115.2

| Communication baud rate: 0: 1200 bps

  1. 2400 bps
  2. 4800 bps
  3. 9600 bps
  4. 19200 bps
  5. 115200 bps

6

| |

0: n.34

1: n.33

| Wiring mode:

0: n.34, three-phase four-wire 1: n.33, three-phase three-wire

7

| |

0–30

| Rotation display time (s):

0: Fixed display

1–30: Time interval of rotation display

8

| |

0–30

| Backlight illumination time control (minutes):

0: Steady on

1–30: Time of backlight illumination without key operation

9

| |

0: ct

1: dc

| Channel switchover:

0: Transformer connection

1: Direct connection

Parameter Setting Operations

Button description: SET means “confirm” or “cursor move” (when inputting numbers or parameters), ESC means “exit”, and → means “add”. The default user password is 701.

  • Set wiring mode (three-phase four-wire or three-phase three-wire) and channel switchover (direct connection or current transformer connection):
  • Set the current transformation ratio or potential transformation ratio:
  • Set communication address or baud rate:

Note:The communication parameters are set for the Smart Power Sensor before delivery. If the communication is abnormal, check and set the parameters.

  • Modify user password:

Troubleshooting

Symptom Cause Analysis Troubleshooting Method

No display after power-on

|

  1. The cable connection is incorrect.
  2. The voltage supplied to the meter is abnormal.

|

  1. Connect the cables correctly (see wiring diagrams).
  2. Supply the correct voltage based on the specifications.

Abnormal RS485 communication|

  1. The RS485 communication cable is disconnected, short-circuited, or reversely connected.
  2. The communication address, baud rate, data bit, and parity bit of the meter do not match those of the inverter.

|

  1. If the communication cable is faulty, replace it.
  2. Set the communication address, baud rate, data bit, and parity bit of the meter to be the same as those of the inverter by pressing buttons. For details, see “Parameter Settings”.

Inaccurate metering|

  1. The cable connection is incorrect. Check whether the corresponding phase sequence of voltage and current is correct.
  2. Check whether the high and low ends of the current transformer inlet are reversely connected. If the values Pa, Pb, and Pc are negative, the high and low ends are connected incorrectly.

|

  1. Connect the cables correctly (see wiring diagrams).
  2. If a negative value is displayed, change the cable connection for the current transformer to ensure that the high and low ends are connected correctly.

Installation Verification

  1. Check that all mounting brackets are securely installed and all screws are tightened.
  2. Check that all cables are reliably connected in correct polarity without short circuit.

Customer Service Contact

Customer Service Contact

Region| Country| Email| Tel
Europe| France| [email protected]| 0080033888888
Germany
Spain
Italy
UK
Netherlands
Other countries| For details, see solar.huawei.com.
Asia Pacific| Australia| [email protected]| 1800046639
Turkey| [email protected]| –
Malaysia| [email protected]| 0080021686868

/1800220036

Thailand| (+66) 26542662 (local call rates)
1800290055 (free in Thailand)
China| [email protected]| 400-822-9999
Other countries| [email protected]| 0060-3-21686868
Japan| Japan| [email protected]| 0120258367
India| India| [email protected]| 1800 103 8009
South Korea| South Korea| [email protected]| –
North America| USA| [email protected]| 1-877-948-2934
Canada| [email protected]| 1-855-482-9343
Latin America| Mexico| [email protected]| 018007703456

/0052-442-4288288

Argentina| 0-8009993456
Brazil| 0-8005953456
Chile| 800201866 (fixed-line only)
Other countries| 0052-442-4288288
Middle East and Africa| Egypt| [email protected]| 08002229000/0020235353900
UAE| 08002229000
South Africa| 0800222900
Saudi Arabia| 8001161177
Pakistan| 0092512800019
Morocco| 0800009900
Other countries| 0020235353900

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

maxsel User Manuals

Related Manuals