AEG VB2 Plus Vacuum Circuit Breaker User Manual
- June 3, 2024
- AEG
Table of Contents
- VB2 Plus Vacuum Circuit Breaker
- Overview
- Structural principle
- Technical parameter
- Dimensions
- Electrical schematic diagram
- Installation, commissioning and operation
- Maintenance
- Transportation and storage
- Random documents
- Spare parts
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
VB2 Plus Vacuum Circuit Breaker
VB2 Plus
User Manual
VB2 Plus Vacuum Circuit Breaker
Caution!
Please read this manual carefully before installing and using the circuit
breaker:
The installation and use of circuit breakers must comply with the requirements
of this manual.
Circuit breaker should be used in accordance with the normal indoor
environmental conditions.
Any operation and maintenance of the circuit breaker should be carried out by
professional trained full- time electrical personnel.
It is forbidden to operate the circuit breaker beyond its rated parameters.
Attention must be paid to any identification of circuit breakers
It is necessary to ensure the applicability and safety of interlocking
conditions and working procedures of circuit breakers.
It is not allowed to carry out maintenance work when the switch cabinet and
secondary control circuit are charged.
It must be ensured that the circuit breaker is not impacted by any external
force, otherwise the equipment will be damaged.
Any illegal operation of the circuit breaker may damage the equipment and even
cause serious accidents.
This manual should be placed in a convenient place.
Professional personnel should be responsible for the safety management of
circuit breakers.
Overview
1-1 General:
VB2 plus indoor high-voltage vacuum circuit breaker is an indoor switchgear
with three-phase ACv 50Hz and rated voltage of 12kV, which can be used for the
protection and control of electrical equipment in power plants, substations
and industrial and mining enterprises, and is suitable for places with
frequent operation.
1-2 General provisions:
VB2 Plus breaker complies with the following standards:
GB/T 1984
High-voltage alternating-current circuit-breakers IEC 62271-100
High-voltage switchgear and controlgear – Part 100: Alternating curren
circuit-breakers
IEC 60694 Common specifications for high-voltage switchgear and controlgear
standards DL/T 403
HV vacuum circuit-breaker for rated voltage 12kV to 40.5kV
1-3 Normal operating conditions:
Ambient temperature
Maximum temperature:+ 40ºC
Minimum temperature: – 15ºC
Maximum daily average temperature: + 35ºC
Ambient humidity
Daily average relative humidity: | ≤95% |
---|---|
Monthly average relative humidity: | ≤90%; |
Daily average saturated vapor pressure: | ≤2.2×10 -3 Mpa |
Monthly average saturated vapor pressure: | ≤1.8×10-3Mpa |
Altitude: ≤1000m, conventional products can be used below 1000m above s level,
and high-altitude products need to be noted when ordering.
Earthquake intensity: No higher than Level 8
Others: no inflammable and explosion hazard, no chemical corrosive gas and no
violent vibration.
Note: in case of different use environment or other special requirements,
it is necessary to consult with the manufacturer.
Structural principle
2-1 Main structure
The conductive circuit of the circuit breaker is a fixed structure, and the
conductive circuit is set in the insulating parts. This structure can
effectively prevent the influence of external factors such as external force
impact and pollution environment on the vacuum interrupter. The conductive
circuit of the circuit breaker is installed at the back of the mechanism box
and connected with the mechanism as a whole.
Primary circuit current route: when breaker is at the closing position, from
the upper terminal to the static contact in the vacuum arc extinguishing
chamber, through the oving contact and its connected soft connection, to the
lower terminal, the insulating pull rod and the internal disc spring pass
through the connecting rod of the circuit breaker to complete the operation
movement of the circuit breaker and keep the contact.
2-2 Operating mechanism
The operating mechanism of the circuit breaker is a spring energy storage
mechanism. There are closing unit, opening unit composed of one or several
coils, auxiliary switch, indicating device and other components in the
mechanism box; the front is provided with closing and opening button, manual
energy storage operation hole, spring energy storage status indicator board
and closing and opening indicator board.
- Closing / opening indication
- Energy storage indication
- Counter
- Closing button
- Opening button
- Manual energy storage operation
- Nameplate
- Fixed pole
- Door opener
- Chassis
2-2-1 Energy storage
The energy required for closing the circuit breaker is provided by the closing
spring. Energy storage can be done either by motor or by hand with energy
storage handle.
2-2-2 Closing
During the closing process, the circuit breaker can be closed no matter
whether the “closing” button is pressed manually or the closing coil is
activated by remote operation.
Note: when the circuit breaker is in the closing state, or the closing
locking device is selected but the external power supply is not connected, and
the handcart type circuit breaker is in the process of propulsion, the closing
operation cannot be carried out.
2-2-3 Opening
Either press the “opening” button, or connect the external power supply to
make the opening trip or overcurrent trip electromagnet act, so that the
circuit breaker can realize the opening operation.
2-2-4 Undervoltage protection function When the secondary control voltage is
less than or equal to 90% of the rated voltage, the undervoltage module must
start to store energy for components and enter the holding state; when the
secondary control voltage drops to 50% of the rated voltage, the energy of the
undervoltage module is released to the opening coil of the circuit breaker to
release the opening holding switch and the opening half shaft So as to realize
the opening operation.
2-3 Anti misoperation interlock The circuit breaker can provide perfect anti
misoperation function
- After the closing operation of the circuit breaker is completed, the losing interlocking board 18 rotates against the closing board 13, and it cannot be closed again when the circuit breaker is not opened.
- After closing the circuit breaker, if the closing electric signal is not removed in time, the internal anti tripping controller of the circuit breaker will cut off the closing circuit to prevent multiple reclosing.
- When the handcart type circuit breaker fails to reach the test position or working position, the handcart interlocking board 19 shall buckle the closing board and cut off the closing circuit to prevent the circuit breaker from entering the load area in the closing state.
- After the handcart type circuit breaker is closed in the working position or test position, the trolley will not be able to move if the roller presses the pushing mechanism, so as to prevent pulling out or pushing the load area in the closing state.
- If electrical closing locking is selected, manual closing operation is prevented when the secondary control power supply is not connected.
Technical parameter
3-1 Main technical parameter
No. | Item | Unit | Value |
---|---|---|---|
1 | Rated voltage | kV | 12 |
2 | Rated current | A | 630/1250/1600/2000/2500/3150/4000′ |
3 | Rated power frequency withstand voltage (1 min) | kV | 42 |
4 | Rated lightning impulse withstand voltage | 75 | |
Rated frequency | 50 | ||
6 | Rated short-circuit breaking current | kA | 2531.540 |
7 | Rated short-time withstand current(4s) | 2531.540 | |
8 | Rated peak withstand current | 6380100 | |
q | Rated short-circuit making current | 6380100 | |
10 | Rated operation procedure | 0-0.3s-00-180s-CO | |
11 | Contact distance | mm | 9.01.1.0 |
12 | Contact travel | 3.5±0.5 | |
13 | Average closing speed | m/s | 0.4-0.8 |
14 | Average opening speed | 0.9-1.3 | |
15 | Closing time (rated voltage) | ms | 30-70 |
16 | Opening time (rated voltage) | 20-50 | |
17 | Closing bounce time | ms | s2 |
18 | Three-phase opening/closing | ss2 | |
19 | Main loop resistance | [In | s 50(630A) : s 45(1250A); |
s40(1600-2000A): s35(above 2500A)
20| Energy storage time| s| s10
21| Classification| class| E2-M2-C2
3-3 Technical parameters of operating mechanism and locking electromagnet
Rate voltage (V)| Energy storagemotor (A)| Closing coil (A)|
Opening coil (A)| Lockoutelectromagnet(mA)
---|---|---|---|---
DC 110| 2.0| 2.| 2.| 35
DC 220| 1.0| 1.| 1.| 20
Dimensions
- Withdrawable – 150mm apart
- Withdrawable – 210mm apart
- Withdrawable – 275mm apart
- Withdrawable – 275mm apart
Electrical schematic diagram
Conventional circuit breaker products are equipped with anti-trip circuit, but according to the needs of users, the anti-tripping circuit can be removed. The internal wiring diagram of 64 core handcart type circuit breaker is shown in Fig. 1, 58 core internal wiring diagram is shown in Fig. 2.
- Withdrawable (64 cores)
Optional wiring setting:
Option | Jumper wire | a-b | c-d | e-f | g-h | a-f | a-g | b-c | i-j | 1-k |
---|---|---|---|---|---|---|---|---|---|---|
■ Anti-pumping relay | •Blocking coil | V | V | V | V | / | / | / | / | V |
❑Blocking coil | / | / | / | / | V | V | V | V | V | |
❑Anti-pumping relay | •Blocking coil | 41 | V | V | V | / | / | / | / | / |
❑Blocking coil | / | / | / | / | is/ | V | •%/ | ii | / | |
S9 : Limit switch | HQ : Closing coil | V1 -V4 : Rectifier | ||||||||
--- | --- | --- | ||||||||
S8 : Limit switch | TO : Opening coil | KO : Anti-pumping relay(Optional) | ||||||||
S4: Auxiliary switch for blocking coil | RO-R1 : Resistance | Y1: Blocking |
coil(Optional)
S1 -S3 : Energy storage position switch| aseci : Jumper terminal| GK-1:
Controller
OF : Auxiliary switch| M : Energy-storage motor| SC: Overcurrent trip
Withdrawable (58 cores)
Optional wiring setting:
Option | Jumper wire | a-b | c-d | e-f | g-h | a-f | a-g | b-c | i-j | 1-k |
---|---|---|---|---|---|---|---|---|---|---|
■ Anti-pumping relay | •Blocking coil | V | V | V | V | / | / | / | / | V |
❑Blocking coil | / | / | / | / | V | V | V | V | V | |
❑Anti-pumping relay | •Blocking coil | 41 | V | V | V | / | / | / | / | / |
❑Blocking coil | / | / | / | / | is/ | V | •%/ | ii | / | |
S9 : | Limit switch | HQ : Closing coil | V1 -dV4 : | Rectifier | ||||||
--- | --- | --- | --- | --- | ||||||
S8 : | Limit switch | TO : Opening coil | KO : | Anti-pumping relay(Optional) | ||||||
S4: | Auxiliary switch for blocking coil | RCR1 : Resistance | Y1 : | Blocking |
coil(Optional)
Si 1-S| Energy storage position switch| a .-q : Jumper terminal| |
QF :| Auxiliary switch| M : Energy-storage motor| |
Installation, commissioning and operation
6-1 When the circuit breaker is lifted from the packing box, the hook shall be
hung on the lifting position with lifting mark on the circuit breaker. When
moving, the upper and lower outlet arms shall not be stressed, and the circuit
breaker shall not be subject to large impact and vibration.
6-2 The circuit breaker installed in the switch cabinet shall not be subject
to tension or deformation, and the bolt at the bottom mounting point shall be
added with disc spring gasket. When connecting the main terminal, the main
terminal shall not be subject to permanent tension and pressure (such as the
bus bar). When connecting the bus, bolts with strength ≥ 8.8 and disc spring
are used to fasten the bus.
6-3 Push the handcart type circuit breaker into the switch cabinet according
to the following steps:
Swing the circuit breaker into the push in hole, clockwise to push in (counter
clockwise to exit). The total driving distance is about 200 mm. In the opening
state, you should enter the working position or test position smoothly. Please
turn the handle at medium speed for 20 turns. When you hear the “click”
position switch mechanism action ound, it is in place (do not damage the
propulsion mechanism due to excessive force).
6-4 In case of problems in operation, determine the causes according to the
table below. If it can’t be solved, please contact the manufacturer. Do not
disassemble the circuit breaker by yourself.
No. | Fault phenomena | Reasons |
---|---|---|
1 | Failure to closing | 1.The breaker is in the closing position state |
2.The handcart does not fully come into operation position or test position
3.The closing locking device is employed and the auxiliary supply is
unconnected or lower than the specifications
4.secondary circuit is incorrect
2| The handcart cannot be pushed in or pulled out| 1 The breaker is in the
closing position state
2 The pushing- handle is not fully inserted into the pushing hole.
3.The pushing mechanism is not fully placed at the test position, so that the
clapper cannot be unlocked with the cabinet body
4.The cabinet body earthing interlocking is not released
6-5 The commissioning and operation work shall be carried out by specially
trained personnel who have a detailed understanding of the performance of the
circuit breaker. The corresponding protection and prevention measures must be
considered in the work.
One of the preconditions for trouble free operation is to use the circuit
breaker under normal working conditions according to the corresponding
provisions of GB/T 1984 and IEC 60694 standards.
- Check the circuit breaker for damage or any other harmful environmental impact. If there is such a phenomenon, it should be eliminated before power on to restore to normal working conditions.
- Remove dirt, especially on the surface of insulating parts. These may be due to contamination during transportation or storage, which may affect the insulation performance of the product.
- Check the connection status of primary circuit contact, secondary circuit connection and grounding body.
- Manual operation test.
Maintenance
Maintenance must be carried out by AEG personnel or the user’s personnel who
are familiar with the equipment and have been trained and qualified. If the
maintenance is carried out by the user’s personnel, the user shall be
responsible for the consequences of the repair.
7-1 During normal use, the circuit breaker is free of maintenance. Because the
circuit breaker has the characteristics of simple structure and durability, it
has a long service life. The maintenance work is related to the wear and aging
of parts. In order to make the circuit breaker work reliably, the interval
time and range of maintenance work needed to be carried out will depend on the
influence of working environment, operation times, operation time and short
circuit current breaking times and other factors.
7-2 Before maintenance, all auxiliary power supply must be disconnected and
there is no danger of power transmission again. The circuit breaker itself is
open and the spring is not stored energy. In order to prevent accidents,
special care should be taken in the operation mechanism.
7-3 Disassembly and replacement of circuit breaker parts shall be carried out
by AEG personnel or corresponding trained personnel, especially during
reassembly, necessary adjustment shall be made.
7-4 Maintenance of circuit breaker
a. The operation structure shall be inspected when the circuit breaker has
been operated for 5 years (from the day when the new equipment is put into
operation) or when the circuit breaker operates for the specified times (5000
times for the circuit breaker with 25kA and below, 4000 times for the circuit
breaker with 31.5kA, and 2500 times for the circuit breaker with 40kA):
-
Cut off the energy storage power supply and operate the circuit breaker to close and open once to release energy.
-
Check the grease condition of rolling or sliding bearing surface.
-
Check the correctness of each component function during electrical and mechanical action.
-
Do a comprehensive appearance inspection。
b. The operation structure shall be maintained after 10 years of operation (calculated from the day when the new equipment is put into operation) or the operation times of the circuit breaker (25 Ka and less than 10000 times, 31.5 Ka circuit breaker for 8000 times, 40 Ka circuit breaker for 5000 times): -
Cut off the energy storage power supply and operate the circuit breaker to close and open once to release energy.
-
Re apply grease to supporting shaft, rolling and sliding bearing.
-
Check the correctness of each component function during electrical and mechanical action.
-
Check the condition or looseness of fasteners installed at connecting rod, crank arm and supporting rod.
-
During maintenance, it is important to check the parts which are subjected to high stress during operation.
In case of replacement of parts, all fasteners shall be replaced.
Comprehensive review of operating mechanism.
7-5 After the circuit breaker has been running for about 5 years or when the
operating mechanism is under maintenance, the circuit breaker body should also
be inspected. Especially when inspecting the appearance, it is also necessary
to check the contamination, damp and corrosion of the equipment surface. Clean
the dust on the surface of insulating parts with dry cloth, and then wipe all
kinds of dirt with silk cloth with household alkaline cleaning agent or safety
cleaner (pay attention to whether the detergent used is applicable to plastic
and synthetic rubber materials), and do not use carbon tetrachloride or
trichloroethylene to wipe.
The minimum interval of the above inspection work shall be less than 5 years
for the switchgearoperating in some special use occasions or under harmful
environmental conditions (such as in theenvironment with high pollution and
heavy corrosive gas).
Transportation and storage
8-1 When the product is transported, the circuit breaker shall be placed in a
closed packing box without energy storage, and a proper amount of desiccant
shall be built in. The circuit breaker shall be protected with plastic film to
prevent water penetration during loading and unloading and dust intrusion
during storage.
8-2 The following tools shall be used to load and unload the packing box
- Crane
- Forklift
- Driving
8-3 Pay attention to the following items during transportation:
-
Avoid shocks
-
Avoid other destructive mechanical forces
-
The lifting appliance should not be hooked on the circuit breaker body or operating mechanism. It should be hooked at the lifting position with lifting mark.
8-4 The circuit breaker shall be stored in the state of opening of operating mechanism and energy storage spring without energy storage.
Basic storage requirements -
The dry and well ventilated storage room shall meet the relevant provisions of GB /T 1984 and IEC 60694.
-
The temperature of the storage room shall not be lower than – 15 ° C.
-
Do not disassemble or damage the package. Cover with a protective light covering and maintain adequate ventilation.
-
Regularly check whether there is condensation phenomenon and other conditions not suitable for storage requirements.
Random documents
a. Product certificate
b. Factory inspection report
c. Packing list
Spare parts
When the user needs, the spare parts can be determined according to the following list, and put forward when ordering, so as to meet the needs.
http://weixin.qq.com/r/hnVxaVvESgY1rR8K9yCU
www.aeg-imc.com
400-820-5234
2022IM2202
GEIS BREAKERS (SHANGHAI) CO.,LTD.
(An AEG Company)