Honeywell STT 3000 Temperature Transmitter Instructions
- June 4, 2024
- Honeywell
Table of Contents
STT 3000 Temperature Transmitter
Instructions Manual
STT 3000 Temperature Transmitter Series STT170
Model Selection Guide
34-44-16-07 Issue 33
Instructions
- Choose the Availability column based on the Key Number.
- A dot (• ) denotes unrestricted availability.
- Select the desired Key Number based on the desired communications protocol.
- Select options and approvals from Tables.
Model Selection Guide
With Price Data
Honeywell Proprietary
Key Number
Description | Selection | Availability |
---|---|---|
4-20mA Output, RTD input | STT171 | ↓ |
↓
4-20mA Output, universal input| STT173
HART Protocol, 4-20mA output| STT17H
Configuration tool for STT171, 173 and 17H| STT17C
Table I – Safety Approvals
Approval
Body
| Approval Type| Location or Classification| | | | |
---|---|---|---|---|---|---|---
None| No approval body certifications included| 00|
□
| □| □
| □
FM, CSA, ATEX
| Intrinsically Safe
Non-Incendive
| Class I, Div. 1, Groups A, B, C, D, T4 Class I, Zone 0/1; AEx ia IIC, T4
Class I, Div. 2, Groups A, B, C, D, T4
| ****
BS
| ****
□
| ****
□
| ****
□
|
Intrinsically Safe
Non-Incendive
| Class I, Div. 2, Groups A, B, C, D, T4 Class I, Zone 0/1; Ex ia IIC, T4
Class I, Div. 2, Groups A,B, C,D, T4
- Intrinsically Safe
Zone 0/1
| Ex II 1 GD, EEx ia IIC, T4..T6
Ex II 2 (1) GD, T4..T6
Non-Incendive
Zone 2
| Class I, Div. 2, Groups A, B, C, D, T4
Ex II 3 G, EEx nA [L] T4..T6
| ****
BN
| | | □|
When installed in Field Mount Enclosure Table IV, E , or T
FM
Approval
| Intrinsically Safe
Non-Incendive
| Class I, Div. 1, Groups A,B, C,D, T4
Class I, Zone 0/1; AEx ia IIC, T4 Class I, Div. 2, Groups A, B,C, D, T4
|
1G
|
e
|
e
|
e
|
---|---|---|---|---|---|---|---
CSA
| Intrinsically Safe
Non-Incendive
| Class I, Div. 2, Groups A,B, C,D, T4 Class I, Zone 0/1; Ex ia IIC, T4
Class I, Div. 2, Groups A,B,C,D, T4
|
2G
|
e
|
e
|
e
|
ATEX| * Intrinsically Safe
Zone 0/1
| Ex II 1 GD, EEx ia IIC, T4..T6
Ex II 2 (1) GD, T4..T6
| 3S| e| e| e|
- Ex II G D or II 2 (1) G D allows for installation in potentially explosive atmospheres caused by the presence of combustible dust only when mounted in a metal enclosure of form B according to DIN 43729 (Head-Mount enclosure) that provides a degree of protection of at least IP 6X in accordance with EN 60529, that is suitable for the application and is correctly installed.
TABLE II – No Option
No Option | 0 | □ | □ | □ | □ |
---|
TABLE III – Configuration & Certificates
Configuration
| None – Factory Default Configuration Supplied
Custom Transmitter Configuration with Printed Report **
| 0
T
| □
□
| □
□****
| □
□
| □
---|---|---|---|---|---|---
Calibration| Custom Transmitter Calibration with Printed Report **| C
| □| □| □|
Optional Certificates
| No Option| 0 | □| □| □| □
No Certificate of Conformance/Origin
Certificate of Conformance/Origin
| 0
R
| □
□
| □
□
| □
□
|
The minimum value of orders acceptable for Honeywell is USD 500. A handling fee is the amount of the difference between USD
TABLE IV – Transmitter Housing and Integral Meters (Reference EN0I-6032 for details)|
1
↓
| 3
↓| H
↓| C
↓
---|---|---|---|---
Housing| No Housing Supplied| 0 | •| •| •| •
Field
Housing| Aluminum with Beige Epoxy Coating
316 Stainless Steel| E
T | d
d| d
d| d
d|
Head Mt| Type 4X housing – Beige| C | g| g| g|
Cable/
Conduit
Entry| Not Applicable – No Housing Supplied
1/2″ NPT Cable/ Conduit Entry
M20 x 1.5 Cable/ Conduit Entry| 0
N
M | •
•
•| •
•
•| •
•
•| •
Integral
Meter| No Integral Meter Supplied
E.U. Meter for Field Mount Housing| 0
E| •
h| •
h| •
h| •
TABLE V – Optional Equipment
Mounting
| No mounting bracket
Carbon steel pipe mounting bracket for 2″ pipe Stainless Steel mounting bracket for 2″ pipe Spring loading mounting set
DIN rail mounting clip (top hat or G rail)
| 0
M
S
L
D | □
e
e
f
f
| □
e
e
f
f
| □
e
e
f
f
| □
---|---|---|---|---|---|---
M20 adaptors
| No adaptors required
1 adaptor for M20 x 1.5 wiring entry 2 adaptors for M20 x 1.5 wiring entry
| 0
1
2
| □
□
□
| □
□
□
| □
□
□
| □
3/4″NPT adaptors| 1 adaptor for 3/4″NPT wiring entry| 3 | □| □|
□|
Lightning Protection
| No lightning protection supplied Externally Mountable to Field Mount Housing Internal lightning protection| 0
L
S
| □
□
□
| □
□
□
| □
□
□
| □
RESTRICTIONS
Restriction
Letters
| Available Only With| Not Available With
---|---|---
Table| Selection| Table| Selection
b| VI| Select only one option from this group| |
d| IV| N | |
e| IV| E , or T | |
f| IV| 0 | |
g| IV| | | 0E
h| I| 00| |
IV| E , or T _| |
ACCESSORIES Part Number
DIN rail clip| 50017850-001| | | |
---|---|---|---|---|---
If the Custom Configuration option “T” or the Custom Calibration option “C”
is ordered, the configuration or calibration information required must me be
entered as a note on the order. Any of the following elements can be included,
based on the selected model number:
(STT171, STT173, STT17H)** Tag Number, CJC, Sensor Type, Sensor Wiring,
Temperature Units, URV/LRV, Output Range, Output Limits, Sensor Error Action,
Response Time.
(STT17F) Tag Number, Sensor Type, URV/LRV,
Burnout- High or Low, Response Time
*** Refer to Part Price List (PPL) or Web Channel for pricing.
The minimum value of orders acceptable for Honeywell is USD 500. A handling fee is the amount of the difference between USD 500 and the actual purchase price.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>