Altronix OLS180220 Off-Line Power Supply Installation Guide
- June 4, 2024
- Altronix
Table of Contents
OLS180220 Off-Line Power Supply
Installation Guide
Overview
Altronix OLS180220 power supply/charger converts 220VAC (working range 198VAC- 256VAC), 50/60Hz input into a 12VDC or 24VDC at 6A of continuous supply current (see specifications). This general-purpose power supply has a wide range of applications for access control and security system accessories that require additional power.
Specifications
Input:
- 220VAC (working range 198VAC-256VAC), 50/60Hz,0.8A.
Output:
- 12VDC or 24VDC selectable output.
- 6A continuous supply current.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Battery Backup:
- Built-in charger for sealed lead acid or gel-type batteries.
- Automatic switch over to stand-by battery when AC fails.
- Maximum charge current 0.7A.
Supervision:
- AC fail supervision (form “C” contacts).
- Low battery supervision (form “C” contacts).
Visual Indicators:
- AC input and DC output LED indicators.
Features:
- Power ON/OFF switch.
- Includes battery leads.
Board Dimensions (L x W x H approx.): 7.25” x 4.5” x 1.75” (184.1mm x
114.3mm x 44.5mm).
Voltage Output Selection Table:
Output VDC | Switch Position | Max. Load DC |
---|---|---|
1 2VDC | SW1 – ON | 6A |
24VDC | SW1 – OFF | 6A |
Installation Instructions:
OLS180220 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
-
Mount the OLS180220 in the desired location/enclosure (mounting hardware included).
-
Slide [Power ON/OFF] switch to OFF position.
-
Set the OLS180220 to the desired DC output voltage via SW1 (Voltage Output Selection Table).
Keep power-limited wiring separate from non-power-limited wiring (220VAC 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts.
Shut branch circuit power before installing or servicing equipment.
There are no user-serviceable parts inside.
Refer installation and servicing to qualified service personnel. -
Connect AC power to the terminals marked [L & N], and connect ground to the terminal marked [G].
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting). -
Measure output voltage before connecting devices. This helps avoid potential damage.
-
Connect devices to be powered to the terminals marked [– DC +].
-
When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect the battery to the terminals marked [– BAT +] (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used, a loss of AC will result in the loss of output voltage. -
Connect appropriate signaling notification devices to AC Fail and Low Battery supervisory relay outputs marked [NC, C, NO].
-
Slide [Power ON/OFF] switch to ON position.
LED Diagnostics
Red (DC) | Green (AC) | Power Supply Status |
---|---|---|
ON | ON | Normal operating condition. |
ON | OFF | Loss of AC. Stand-by battery is supplying power. |
OFF | ON | No DC output. Short circuit or thermal overload condition. |
OFF | OFF | No DC output. Loss of AC. Discharged or no battery present. |
Terminal Identification
Terminal Legend | Function/Description |
---|---|
L, G, N | Connect 220VAC to these terminals: L to Hot, N to Neutral, G to |
ground.
— DC +| 12VDC / 24VDC @ 6A continuous supply current.
AC FAIL
NC, C, NO| Used to notify loss of AC power, e.g. connect to audible device or
alarm panel.
Relay is normally energized when AC power is present. Contact rating 1A @
28VDC
Low Battery
NC, C, NO| Used to indicate low battery condition, e.g. connect to the alarm
panel.
Relay is normally energized when DC power is present. Contact rating 1A @
28VDC.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC.
24VDC output threshold set @ approximately 21 VDC.
— BAT +| Stand-by battery connections. Maximum charge rate 0.7A.
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056
website: www.altronix.com | e-mail:
info@altronix.com | Lifetime Warranty
IIOLS180220 – Rev. 010704
H31U
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>