Chapter 1 Function Description

1.1 Product overview

RTEC1616 is a digital isolated input and output module, including 16-channel digital isolated input and 16-channel digital isolated output.
Characteristic

  • Support CoE (CANopen over EtherCAT)
  • Support DC synchronization and FreeRun mode
  • Dual port RJ45 connector for EtherCAT communication
  • Input port: 16 optically isolated digital signal inputs, 24V single-ended input, common anode connection;
  • Output port: 16 optical isolation + Darlington output port, each output current is 500mA
  • PWM output: 4 PWM outputs, duty cycle supports 0~100%

Electrical characteristics
The recommended usage conditions are as follows::

| Minimum| Normal| Maximum
---|---|---|---
Supply voltage (V)| 15| 24| 30
Output port current (mA)| 90| 350| 500
Input interface current consumption (mA)| 5| 10| 30
PWM frequency| 0.5K| 1K| 5KHz
Temperature range| -40| —| 85

Chapter 2 Interface Description

1.2 Power interface X5RTELLIGENT RTEC1616 FieldBus Communication Slave
lO Module - Power interface

The power interface X5 includes 3PIN terminals, which are defined as follows:

Mark Definition
PE PowerEarth, connect to the chassis
EGND Negative pole of 24v power supply
VDC Positive pole of 24v power supply

It is recommended to use a switching power supply with a power above 24V/1A.

1.3 Digital input port
16 optically isolated digital input ports, the internal use of common anode connection, the internal circuit diagram is as follows:RTELLIGENT RTEC1616
FieldBus Communication Slave lO Module - Digital inputWhen the external input signal interface type is NPN, the wiring is as follows:

RTELLIGENT RTEC1616 FieldBus Communication Slave lO Module - Digital input
1

When the external signal interface type is relay, the wiring is as follows:

RTELLIGENT RTEC1616 FieldBus Communication Slave lO Module - Digital input
2

1.4 Output port
The 16 output ports are the Darlington output after optocoupler isolation. The internal common terminal is connected to 24V. The equivalent circuit of each output port is  shown in the figure below:RTELLIGENT RTEC1616 FieldBus
Communication Slave lO Module - Output port

The output port of each channel can output a maximum of 500mA current, and a larger current output can be achieved by connecting multiple output ports in parallel. There  is a built-in absorption diode inside the module, which can drive inductive loads.

1.5 Connect EtherCAT
Please use CAT5E (or higher) network cable.
The Ethernet input interface IN is connected to the Ethernet output interface OUT of the previous drive on the controller or the bus. The Ethernet output interface OUT is  connected to the Ethernet input interface IN of the next drive on the bus. If the drive is the last node on the bus, you only need to connect the Ethernet input interface IN.
EtherCAT status indicator
The yellow light of RJ45 is used for Link status, indicating whether there is a network cable connection.
The green light of RJ45 is used for Activity state, indicating whether there is data communication.

RUN/ERRLED Indicator light:

LED COLOUR Status Describe
RUN GREEN Not bright Initialization status
Slow flash Pre operational status
Single flash Safe operational state
Light Operational status
ERR RED Not bright No errors
Slow flash General error
Single flash Synchronization error
Double flash Watchdog error
  • Fast flash: On for 50ms, off for 50ms (10Hz). So cycle.
  • Slow flash: On for 200ms, off for 200ms (2.5Hz). So cycle.
  • Single flash: on for 200ms, off for 1s. So cycle.
  • Double flash: on for 200ms, off for 200ms, on for 200ms, off for 1s. So cycle.

EtherCAT site address
The EC series supports two methods to set the slave address: object dictionary 0x2150 to set the site alias and ESC to set the site alias, and select it through the object  dictionary 0x2151.
The default 0x2151 is 0, and the node address is allocated by the master station and saved in the EEPROM.
When users need to set a fixed address by themselves, they need to set 0x2151 to 1, and then write the required address value in 0x2150.

0x2151 0x2150 Site address
0 1001 The master station configures the station alias to the EEPROM 0x0004

word address of ESC
1| Settings| Object dictionary 2150 Set value to node address value

1.6 SizeRTELLIGENT RTEC1616 FieldBus Communication Slave lO Module -
EtherCAT site

Chapter 3 Parameter Description and Setting

1.7 General parameters
1.7.1 0x1000 Device type

Object Type Data Type Access Type PDO Mapping Default Value
VAR UNSIGNED32 RO NO 0x00001398

Bit 0~15: Device profile number 0x1398: IO Model
Bit 16~31: Additional information 0x0000: Stepper Drive
0x1001 Device name
Display the current product name.

Object Type Data Type Access Type PDO Mapping Default Value
VAR Visible string RO NO RTEC1616

17.3 0x1009 Hardware version

Object Type Data Type Access Type PDO Mapping Default Value
VAR Visible string RO NO 1.0

0x1009 Hardware version

Object Type Data Type Access Type PDO Mapping Default Value
VAR Visible string RO NO 1.0

0x100A Software version

Object Type Data Type Access Type PDO Mapping Default Value
VAR Visible string RO NO 1.0

Save parameters
Sub-index of object dictionary 0x1010: 01 Write 0x65766173 to save current parameters. The data structure is as follows:

Index Subindex Name PDO mapping Defaults
1010 00 Maximum of subindexes No 1
01 Save parameters No 0

Restore factory settings
Subindex of object dictionary 0x1011: 01 Write 0x64616F6C to restore the drive to the factory state.

Index Subindex Name PDO mapping Defaults
1011 00 Maximum of subindexes No 1
01 Save parameters No 0

1.8 POD and COE object dictionary
0x6000 TxPDO_INPUT

Index Subindex Name Attributes Type Range Defaults
0x6000 00 Maximum of subindexes 1
01 INPUT_VALUE1 RO UINT 0~65535 0

0x6000:01 displays the physical level of the current 16-channel IO input

Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
IN8 IN7 IN6 IN5 IN4 IN3 IN2 IN1
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
IN16 IN15 IN14 IN13 IN12 IN11 IN10 IN9

0 — No input signal
1 — With input signal
This module uses a fixed TxPDO mapping mode,RTELLIGENT RTEC1616 FieldBus
Communication Slave lO Module - fig

0x7000 RxPDO_OUTPUT

Index Subindex Name Attributes Type Range Defaults
0x7000 00 Maximum of subindexes 5
01 OUT_VALSET RW UINT 0~65535 0
02 OUT11_PWM_Duty RW UINT 0~10000 0
03 OUT12_PWM_Duty RW UINT 0~10000 0
04 OUT13_PWM_Duty RW UINT 0~10000 0
05 OUT14_PWM_Duty RW UINT 0~10000 0

0x7000:01, when the output port is a normal output port function, it is used to set the value of the output port.

Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
IN8 IN7 IN6 IN5 IN4 IN3 IN2 IN1
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
IN16 IN15 IN14 IN13 IN12 IN11 IN10 IN9

0 — Disable output
1 — Enable output
0x7000:02 to 0x7000:04, when the output ports 11 to 14 are set as the PWM output function, this object is used to control the duty cycle of the PWM output. 0 means 0%,  10000 means 100%.
This module uses a fixed RxPDO mapping mode,RTELLIGENT RTEC1616 FieldBus
Communication Slave lO Module - fig 1

0x8000 OUTPORT_CFG

Index Subindex Name Attributes Type Range Defaults
0x8000 00 Maximum of subindexes 5
01 OUTPORT_State_Reset RW UINT 0~65535 0
02 OUT11_Function RW UINT 0~1 0
03 OUT12_ Function RW UINT 0~1 0
04 OUT13_ Function RW UINT 0~1 0
05 OUT14_ Function RW UINT 0~1 0

0x8000:01, OUTPORT_State_Reset, this object is used to set the default state of the IO expansion module when reset.
This object needs to be saved and re-powered to take effect

Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
IN8 IN7 IN6 IN5 IN4 IN3 IN2 IN1
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
IN16 IN15 IN14 IN13 IN12 IN11 IN10 IN9

0 — Disable output
1 — Enable output
0x8000:02~0x8000:04,Output port function setting, output ports 11 to 14 of the expansion module can be used as PWM output.
This object needs to be saved and re-powered to take effect
0 — Normal output port, the value is controlled by 0x7000:01
1 — PWM function, the duty cycle is controlled by 0x7000:02~04, and the period is set by 0x8001.

0x8001 PWMOUT_CFG

Index Subindex Name Attributes Type Range Defaults
0x8001 00 Maximum of subindexes 5
01 OUT11_PWM_Frequency RW UINT 1000~5000 1000
02 OUT12_PWM_Frequency RW UINT 1000~5000 1000
03 OUT13_PWM_Frequency RW UINT 1000~5000 1000
04 OUT14_PWM_Frequency RW UINT 1000~5000 1000

This object is used to set the frequency of PWM output.
After the set PWM frequency is set, you need to save the parameters and re- power on to take effect.

RTELLIGENT logo