BriskHeat K Series Constant Wattage Heating Cable
INTRODUCTION
Thank you for purchasing a BriskHeat FE series constant-wattage heating cable
system. A heating cable system is a combination of heating cables,
connection/termination kits, temperature controllers, and accessories based on
your particular application. Your heater is designed to provide a long and
efficient service life with function, reliability, and safety in mind.
All BriskHeat Constant-Wattage Heating Cable utilize a parallel resistance
modular design. This allows the heating cable to be cut to length and
terminated in the field, without affecting the heating power per unit length.
The modular design enables the cable terminations / electrical connections to
be made with cold leads and cold ends (e.g. cable not heated in the electrical
junction box).
A temperature controller is required for all constant-wattage heating cables.
For additional information concerning this, or other BriskHeat products,
please contact your local BriskHeat distributor or contact us toll-free (U.S.
and Canada) at 1-800-848-7673 or
614-294-3376.
APPLICATIONS
Intended Applications:
- General Purpose Trace Heating
- Pipe/Tank/Vessel Heating
- Ordinary and Hazardous Locations
- Dry Area Applications
Prohibited Applications:
- Outdoor use
- Immersion heating
- Use on non‐metallic fixtures
- Wet Area Applications
IMPORTANT SAFETY INSTRUCTIONS
DANGER
A person who has not read and understood all operating instructions is not qualified to operate this product.
- Do not immerse heater in liquid.
- Heater must be 5/8 in (13 mm) away from any combustible material.
- Use heater only in approved locations.
- Keep sharp metal objects away from heater.
Failure to observe these warnings may result in electric shock, risk of fire, and personal injury.
WARNING
End-User Must Comply to the Following:
- Only qualified personnel are allowed to connect the electrical wiring.
- Disconnect all supply power at the source before making any heating cable power input connections.
- All electrical wiring must follow local electrical codes and highly recommend following NEC Article 427.
- The person who performs the final installation/wiring must be qualified for this work.
- The end-user is responsible for providing a suitable disconnecting device.
- The end-user is responsible for providing suitable electrical protection devices. It is highly recommended that a ground fault circuit breaker be used.
Failure to observe these warnings may result in personal injury or damage to the heater.
Immediate hazards which WILL result in severe personal injury or death.
Hazards or unsafe practices that COULD result in severe personal injury or
death
Hazards or unsafe practices that COULD result in minor personal injury or
property damage
CAUTION
- Never handle the heater while it is in operation; always disconnect the heater from the power source and allow to cool prior to handling.
- Inspect heater and connection kits before use.
- Never operate heater without a temperature control device.
- Do not wrap the heating cable over itself.
- If spillage of a foreign matter onto heater occurs, disconnect from power source clean after heater is allowed to cool.
- Never operate a heater without an appropriate heat sink (device being heated is considered a heat sink).
- Do not operate heater above rated temperature value.
- Fasten heater to device using approved methods only.
- Do not repair damaged or faulty heaters.
- Do not crush of apply severe physical stress on heater or cord assembly
- Disconnect heater when not in use
Failure to observe these warnings may result in personal injury or damage to the heater.
SAFETY ALERT SYMBOL
The symbol above is used to call your attention to instructions concerning your personal safety. It points out important safety precautions. It means “ATTENTION! Become Alert! Your Personal Safety is involved!” Read the message that follows aAnd be alert to the possibility of personal injury or death.
CONNECTION / TERMINATION KIT DESCRIPTIONS
KCABUC:
Universal Connection/Termination Kit
- 2-Lead pouches
- 2-End pouches
- 1-3 oz. Tube RTV sealant
- 1-Caution label
- 2-Ring terminals
- 2-Splice connector 12-10 AWG
- 2-Wire nuts
- 1-1 in NPT Pipe standoff
- 2 Pipe straps
Enough to complete one power input connection or one power input splice, two
lead terminations and two end terminations.
NOTE: Requires Double-hub junction box.
KCABKC:
Lead/ End Termination Kit
- 5-Lead pouches
- 5-End pouches
- 1-3 oz. Tube RTV sealant
Enough to complete five lead terminations and five end terminations.
KCABSK:
Splice Kit
- 3-Lead pouches
- 3-End pouch
- 1-3 oz. Tube RTV sealant
- 1-Caution label
- 3-Ring terminals
- 3-Splice connectors 12-10
Enough to complete one in-line splice or one tee splice, three lead
terminations and three end terminations.
NOTE: Requires single hub junction box, pipe standoff, two pipe straps.
KCABLP:
Lead Termination Kit
1-Lead pouch
Enough to complete one lead termination.
NOTE: Requires RTV silicon.
KCABEP:
End Termination Kit
1-End pouch
Enough to complete one end termination.
NOTE: Requires RTV silicone.
PRIOR TO INSTALLATION
STEP 1:
Check for suspected damage to heater like rips, punctures, etc. Ensure surface
to be heated is free of jagged or sharp edges or weld splatter.
STEP 2:
Confirm all necessary installation hardware and tools are readily available.
Depending on the application and kit, this may include…
Tools
- Diagonal Cutter
- Crimping Tool / Wire Stripper
- Knife
- Measuring Tape/Ruler
- Screwdriver
Hardware and Accessories
- Temperature Controller
- Temperature Sensor
- Connection / Termination Kits (see kit descriptions to verify contents and additional required hardware)
- Insulating Material
- Monitor Light Kit (Optional)
- RTV Sealant
- Pipe Straps
- Junction Box
- Wire Nuts
- Caution Labels
- Aluminum or Fiberglass
- Adhesive Tape (verify
- temperature rating)
- Heat Conductive Putty
- Pipe Standoffs
- Pipe Reducer
STEP 3:
(A) Verify the total amperage of the system does not exceed the maximum
amperage that the heating system components can handle. (B) Verify that the
total length of cable required does not exceed the maximum circuit length. If
the cable length exceeds (A) or (B), the cable must be divided into sections
LEAD TERMINATION PREPARATION
STEP 1:
Determine the module length of the heating cable. Module points can be
identified by slight indenta-tions on the rounded surface of the outer jacket.
You can determine the module point by touch or visually by sliding back the
metallic overbraid.
NOTE: KE series cable module points must be visually identified due to
FEP outer jacket.
STEP 2:
Cut the cable between the module points for the desired length of cold lead.
The length of “cold lead” must be at least 12 in (305 mm) but no longer than
the module length minus 6 in (152 mm). The section of cable between the end of
the cable and the first module point will be the cold lead. This section will
be used for lead termination/power input connection.
STEP 3A: (KE cable only)
Using a knife, remove 10 in (254 mm) of the outer jacket, exposing the
metallic braid. DO NOT DAMAGE THE BRAID.
STEP 3B: (all K series cable)
Push 6 in (152 mm) of the metallic overbraid back to expose the polyimide
layer of the heater. Using a pair of Wire Cutters, cut off 4 in (101 mm) of
the exposed heater.
STEP 4:
Pull the metallic braid back over the end of the cable. Push the cable through
the side of the metallic braid. Twist the empty braid to form a pigtail lead
and crimp a ring terminal on the end (see picture below). A crimp barrel can
also be used to extend the ground (braid) to another 12 AWG ground wire.
STEP 5:
Slide the metallic overbraid back at least an additional 4 in (101 mm). Using
a knife, carefully cut and remove 4 in (101 mm) of the inner polyimide layer
to expose the spirally wrapped resistance wire and the two bus wires. Do NOT
damage the bus wires or the bus wire insulation; the resistance wire must NOT
come into contact with the exposed bus wires. Unwrap and cut the resistance
wire back to the point you cut the cable jacket.
STEP 6:
Fill a lead pouch with silicone RTV sealant. Slide the lead pouch over the two
bus wires and over the inner wrap and outer braid. Using wire strippers,
remove 0.75 in (19 mm) of the insulation from the bus wires to expose the
conductors.
DO NOT DAMAGE THE CONDUCTORS. ENSURE OUTER BRAID DOES NOT CONTACT THE SPIRALLY
WRAPPED RESISTANCE WIRE.
ENSURE OUTER BRAID DOES NOT CONTACT THE SPIRALLY WRAPPED RESISTANCE WIRE.
END TERMINATION PREPARATION
STEP 1:
Locate the last module point of the cable run. Cut the cable 6 in (24 mm)
beyond this point to form a cold end.
STEP 2A: (KE cable only)
Using a knife, remove 2 in (50 mm) of the outer jacket, exposing the metallic
braid. DO NOT DAMAGE THE BRAID.
STEP 2B: (all K series cable)
Using diagonal cutters and / or a knife, remove 1.5 in (38 mm) of the metallic
braid and 1 in (25 mm) of the polyimide layer to expose the spirally wrapped
resistance wire and the two insulated bus wires. Unwrap and cut off the
resistance wire back to the polyimide layer. Be careful not to damage the
insulation on the bus wires. Make certain the resistance wire, the two bus
wires, and the metallic braid do NOT contact each
other.
STEP 3:
Fill an end pouch with silicone RTV sealant. Slide the filled end pouch over
the two bus wires, inner jacket, and the outer most layer.
Note: When attaching the heating cable to the pipe, make sure that the last
module point is in contact with the pipe surface.
INSTALLATION
POWER INPUT CONNECTION INSTALLATION
Only authorized and trained personnel should perform the following procedure. The hazard of electrical shock exists with any electrical installation project. Disconnect all supply power at the source prior to making the heating cable power input connections.
A temperature controller is required for all constant-wattage heating cable.
STEP 1:
Prepare heating cable end as specified under “Lead Termination Preparation”.
Insert approximately 8 in (200 mm) of the heating cable (s) through the bottom
of the cast aluminum pipe standoff, making sure the first module point stays
in contact with the pipe.
NOTE: A maximum of three cables fit through pipe standoff.
STEP 2:
Place the standoff on the pipe surface at the point where the supply wiring
and associated fittings will connect to the pipe heat tracing cable. Fasten
the standoff to the pipe with pipe straps. Fill the top of the standoff with
Silicone RTV to provide a moisture seal between the pipe and electrical
junction box. Make certain there are no voids between the cable and pipe
standoff. Allow an appropriate amount of time for the Silicone RTV to cure.
STEP 3:
Ensure the junction box chosen is equipped with a minimum of two 1 in NPT
female threaded hubs. Secure junction box onto the standoff. Pull the input
power source wiring through the associated opening into the junction box.
Connect the heating cable lead wires to a temperature controlling device and
input power source wiring using wire nuts provided. Be sure to follow
temperature controlling device installation instructions. If applicable,
secure the braided pigtail ground to the standoff using the standoff ground
screw provided or to the junction box using the junction box ground
screw/receptacle. Ensure an adequate earth ground is provided to safely ground
the entire assembly.
SPLICE INSTALLATION
WARNING
Only authorized and trained personnel should perform the following procedure. The hazard of electrical shock exists with any electrical installation project. Disconnect all supply power at the source prior to making the heating cable power input connections.
STEP 1:
Prepare the heating cable ends to be spliced together as specified under “Lead
Termination Preparation”.
CAUTION: Never connect the two parallel conductors of the heating cable
together.
STEP 2:
Insert the heating cable cold leads up through the pipe standoff and into the
junction box. Attach the pipe standoff and junction box to the pipe where the
splice is to be located. Fasten it with appropriately sized pipe clamps.
NOTE: A maximum of three cables fit through pipe standoff.
STEP 3:
Connect the leads of the heating cable ends together using wire nuts as shown
in the illustrations (wire nuts are not provided with KCABSK).
STEP 4:
Connect the terminal lugs on the braid leads to a grounded screw on the pipe
standoff or on the junction box.
NOTE: The junction box and pipe standoff must be grounded.
STEP 5:
Test the cable installation for continuity and insulation resistance. The
insulation resistance
between the bus wires and the metallic braid must be greater than 50 megohms
at 500 volts. Close the junction box and attach the Caution Label to the cover
of the junction box.
HEATING CABLE INSTALLATION
Cable Wrapping Techniques
A straight run is the simplest method to installing heating cable. It is
possible to have
multiple straight runs on a single object. With a single straight run,
position cable at the bottom of a horizontal pipe.
CAUTION
- Do not wrap the heating cable over itself or have two heating cables touch.
- All parts of heating cable must make intimate contact with surface to be heated.
- Use heat conductive putty to fill voids between cable and pipe surface.
- Wrap adhesive tape every 12 in (305 mm) around heating cable and pipe to attach the cable.
Spiral wrapping provides more heater coverage than a straight run. It can also require more heating cable. Verify the pitch length (see illustration) prior to installation to ensure you have enough heating cable to finish the job. If you need assistance in determining the pitch length, call your local distributor or BriskHeat.
CAUTION
- Do not wrap the heating cable over itself or have two heating cables touch.
- Minimum bend radius may not exceed 1 in (25.4 mm)
- All parts of heating cable must make intimate contact with surface to be heated.
- Use heat conductive putty to fill voids between cable and pipe surface.
- Wrap adhesive tape every 12 in (305 mm) around heating cable and pipe to attach the cable.
- After heating cable installation, an insulation resistance test is recommended before installation of any thermal insulation.
See the ELECTRICAL INSULATION RESISTANCE TEST section of these instructions for insulation resistance test procedure.
Heating Cable Placement on Different Types of Objects
INSTALLING INSULATION
It is highly recommended that thermal insulation is used with this product.
For application assistance and an insulation recommendation, please contact
your local BriskHeat representative or us direct to perform a thermal analysis
of your application.
For applications requiring FM or CE compliance, thermal insulation is required
and not to exceed 1 in (25.4 mm) in thick. For applications requiring greater
than 1 in (25.4 mm) thick insulation, contact your local BriskHeat
representative or us direct to perform a thermal analysis of your application
and to verify FM and/or CE compliance.
After the installation of thermal insulation, an insulation resistance test is
recommended before ener-gizing the system. See ELECTRICAL INSULATION
RESISTANCE TEST section of these instructions for insulation resistance test
procedure.
ELECTRICAL INSULATION RESISTANCE TEST
Electrical tests are recommended at specific points in the receipt and installation of the heating cable. This periodical testing is designed to prevent the expenditure of wasted labor in the event of damage to the product. Installation costs of the cable and thermal insulation are much greater that the heating cable. Quick identification of any heating cable damage is the most economic approach to an installa-tion. An insulation resistance test is recommended at the following point of the installation process:
- UPON RECEIPT of the heating cable
- BEFORE thermal INSULATION installation
- IMMEDIATELY AFTER thermal insulation installation
- As part of a PERIODIC MAINTENANCE program
Procedure
The insulation resistance test is used to check for damage to extruded
jackets. Connections for the megger are made as shown.
Note: T est should use at least a 500 VDC megger. Do not use a megger
with an excess of 2500 VDC.
Minimum acceptable readings should be 20 megohms per circuit, regardless of
length.
A record should be kept of the readings taken from the time the cable is first
installed on the pipe. A history of the insulation resistance reading can be
helpful in spotting moisture ingress into the electrical system (indicated by
a gradual decline in the insulation resistance) or physical damage to the
heating cable (indicated by a sharp decline in the insulation resistance). A
sample record for this is shown. (See the following page)
PERIODIC INSPECTION RECORD
The Periodic Inspection record Form may be used in one of two ways:
- One sheet per circuit – The results of periodic tests of a single circuit are posted in vertical columns, beginning on the left and working toward the right. This allows easy comparison of test values for up to three test sequences on an individual circuit.
- One circuit per column – Test data for a single test sequence on as many as three circuits can be recorded on a single sheet.
For additional Periodic Inspection Record Forms, contact your local distributor/representative or Briskheat at 1-800-848 -7673 (toll free, U.S. / Canada) or 1-674-294-3376 (Worldwide) or bhtsales1@briskheat.com.
Periodic Inspection Record Form
Circuit Number
Heater Type
Circuit Length
Freeze Protection Circuits –| | |
---|---|---|---
Perform these checks as season requiring use ap-| | |
Temperature Maintenance Circuits –| | |
Perform these checks at least twice per year.| | |
Maintenance Checks for Month Year __
Visual inspection inside connection box
corrosion, moisture, etc.
| Initial
Date
| | |
| |
Damage or cracks (leaks) in insulation
seals at valves, hangers, pumps, etc.
| Initial
Date
| | |
| |
Heating cable properly connected and
grounded. heating cable and connections insulated from connection box.
| Initial
Date
| | |
| |
| |
Thermostat checked for moisture, corrosion,
set point, switch operation, and capillary damage
| Set Point
Initial Date
| | |
| |
| |
Megger tests performed at power
connection with both bus wires disconnected from power wiring.
| Reading
Initial Date
| | |
| |
| |
Circuit voltage at power connection.| Reading| | |
Circuit amperage after 5 minutes| Reading| | |
Pipe temperature at time amps were measured.| Reading| | |
Watts/Ft.
Volts x Amps = w/ft. feet
|
Initial Date
| | |
| |
| |
All connections, boxes, and thermostats
have been resealed.
| Initial
Date
| | |
| |
End seals, covered splices and tees marked
On insulation cladding.
| Initial
Date
| | |
| |
Remarks & Comments| | |
---|---|---|---
| | |
| | |
| | |
MAINTENANCE INSTRUCITONS
Anyone who reads and understands these instructions is qualified to maintain this heater.
Maintenance:
- All maintenance should be performed after the heater has cooled to room temperature and with the electricity disconnected.
- Dirt, oil, grease or other foreign matter can be removed with a damp rag and mild household cleaners.
- Do not attempt to repair a damaged heater.
Storage:
- This product should be stored at room temperature in an environment with less than 80% relative humidity.
Disposal:
- This product does not contain any hazardous substances and may be discarded with domes-tic waste.
EMERGENCY PROCEDURES
Read and understand these procedures prior to using this heater. Disconnect power to the heater in the event of an emergency.
Electric Shock:
- Do not touch the injured person while they are still in contact with the electrical current.
- Call your local emergency service if the injured person experiences: severe burns, confusion, difficulty breathing, heart rhythm problems, cardiac arrest, muscle pain and contractions, seizures or a loss of consciousness.
Minor Burns:
- Hold the burned area under cool running water for 10-15 minutes.
- Remove rings or other tight items from burned area.
Major Burns:
- Call your local emergency service.
- Protect the person from further harm.
- Remove rings or other tight items from burned area.
- Monitor breathing and perform CPR if necessary.
Fire:
- Call your local emergency service
TROUBLESHOOTING GUIDE
Please read this guide prior to contacting BriskHeat. This guide is designed to answer the most commonly asked questions. If you are unable to identify the problem or need additional assistance, please contact your local distributor/ representative or us at 1-800-848-7673, 614-294-3376, or bhtsales1@briskheat.com.
PROBLEM | SOLUTION(S) |
---|---|
Entire heating cable run does not heat | Verify heater is connected to proper |
voltage.
Check to see if there is a resistance reading (not an open circuit) in heater using an ohm meter.
Portion of heating cable does not heat| Examine unheated module for damage.
Circuit breaker is tripping| Validate that the circuit breaker is capable of
handling the amp requirement of heater.
Examine heater and power wiring for any damage.
Verify open circuit exists between bus wire and ground braid.
Ensure heater length does not exceed maximum circuit length (See tables below).
KE: Maximum Circuit Length ft (m)
Cable
| 120 VAC
ft (m)
| 208 VAC
ft (m)
| 240 VAC
ft (m)
| 277 VAC
ft (m)
| 480 VAC
ft (m)
---|---|---|---|---|---
4 W/ft (13 W/m)| 480 (146)| 830 (253)| 960 (293)| 1110 (338)| 1920 (585)
8 W/ft (26 W/m)| 240 (73)| 415 (127)| 480 (146)| 555 (169)| 960 (223)
12 W/ft (39 W/m)| 160 (49)| 277 (85)| 320 (98)| 370 (113)| 640 (195)
KM: Maximum Circuit Length ft (m)
Cable
| 120 VAC
ft (m)
| 208 VAC
ft (m)
| 240 VAC
ft (m)
| 277 VAC
ft (m)
| 480 VAC
ft (m)
---|---|---|---|---|---
4 W/ft (13 W/m)| 480 (146)| 830 (253)| 960 (293)| 1110 (338)| 1920 (585)
8 W/ft (26 W/m)| 240 (73)| 415 (127)| 480 (146)| 555 (169)| 960 (223)
12 W/ft (39 W/m)| 160 (49)| 277 (85)| 320 (98)| 370 (113)| 640 (195)
KM: Maximum Circuit Length ft (m)
Cable
| 120 VAC
ft (m)
| 208 VAC
ft (m)
| 240 VAC
ft (m)
| 277 VAC
ft (m)
| 480 VAC
ft (m)
---|---|---|---|---|---
4 W/ft (13 W/m)| 480 (146)| 830 (253)| 960 (293)| 1110 (338)| 1920 (585)
8 W/ft (26 W/m)| 240 (73)| 415 (127)| 480 (146)| 555 (169)| 960 (223)
12 W/ft (39 W/m)| 160 (49)| 277 (85)| 320 (98)| 370 (113)| 640 (195)
18 W/ft (59 W/m)| 105 (32)| 185 (56)| 215 (65)| 245 (75)| 425 (130)
WARRANTY INFORMATION
BriskHeat warrants to the original purchaser of this product for the period of eighteen (18) months from date of shipment or twelve (12) months from date of installation, whichever comes first. BriskHeat’s obligation and the exclusive remedy under this warranty shall be limited to the repair or replacement, at BriskHeat’s option, of any parts of the product which may prove defective under prescribed use and service following BriskHeat’s examination, is determined by BriskHeat to be defective. The complete details of the warranty can be found online at www.briskheat.com or by contacting us at 1-800-848-7673 (toll free, U.S. / Canada) or 1-614-294-3376 (Worldwide).
Corporate Headquarters: 4800 Hilton Corporate Dr. Columbus, OH 43232,
U.S.A.
Europe:
P.O. Box 420124
44275 Dortmund, Germany
Toll Free: 800-848-7673
Phone: 614-294-3376
Fax: 614-294-3807
Email: bhtsales1@briskheat.com
© BriskHeat Corporation. All rights reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>