DOMETIC GP-AGM-224-6V AGM Battery User Guide
- June 3, 2024
- Dometic
Table of Contents
DOMETIC GP-AGM-224-6V AGM Battery
BATTERY SPECIFICATIONS
SPECIFICATIONS
Technology| AGM, VRLA deep cycle battery
Nominal Voltage| 6 V
Rated Capacity 77°F (25 ±5 °C)| 224 Ah/11.2A; 194 Ah/19.4A; 179 Ah/
35.9A
Capacity Correction for Temperature Variations| 104°F (40°C) 103%
77°F (25°C) 100%
32°F (0°C) 86%
Maximum Discharge Current| 2000 A (5s)
Specific Energy Density| 44.07 Wh/kg
Volumetric Energy Density| 116.27 Wh/L
Internal Resistance| Approx. 1.4mΩ
Terminals| T11
Torque: 11 ~ 14.7 Nm (97.28 – 130 in*lbs)
Cycle Life 77°F (25°C)| 100% Depth of Discharge ~ 250 cycles 50% Depth of
Discharge ~ 1100 cycles 30% Depth of Discharge ~ 2250 cycles
Certifications| UL; CE; IEC60896-21 & 22
Temperature Range
| Charge: 0~40°C (32~104°F)
Discharge: -15~50°C (5~122°F)
Storage: -15~40°C (5~104°F)
Cycle Use
| Initial Charging Current less than 30.0 A Voltage: 7.2 V~7.4 V at 77°F
(25°C) Temp. Coefficient -30mV/°C
Cold Cranking Amps (CCA)| 900
Standby Use
| No limit on Initial Charging Current Voltage: 6.8 V~6.9 V at 77°F (25°C) Temp. Coefficient -20mV/°C
Self Discharge
| Batteries can be stored for up to 6 months before a freshening charge is required.
*Batteries stored at temperatures greater than 77°F (25°C) will require a recharge sooner.
WARNINGS
- Risk of fire if battery not installed correctly.
- Use caution with metallic objects near battery terminals.
- Keep terminals protected to prevent accidental shorting.
- Disconnect immediately if battery excessively hot or making hissing sounds.
- Replace any battery that has signs of damage to the terminals, case or cover.
- Do not overcharge or overdischarge battery.
Length | 10.24 in / 260 mm |
---|---|
Width | 7.09 in / 180 mm |
Height | 9.72 in / 247 mm |
BCI Group # | 27 |
Weight | 67.25 lbs / 30.5 kg |
Carrying | Nylon Strap |
WIRING GUIDE
The illustrations below show how to properly wire AGM batteries.
BATTERY BANK TERMINAL CONNECTIONS
All battery interconnects, busbar, and device connections to resist vibration by using nylon insert lock nuts, thread locking fluid, or lock washers (split lock or external tooth).
12V 224AH AGM BATTERY BANK PARALLEL CONNECTION
Note: New batteries should never be connected to old batteries. All
batteries should be charged to a minimum of 6.5V before connecting them
together All busbar connections to external devices (inverter, converter,
solar controller, etc.) to be equal in length and gauge, sized appropriately
for each device with suitable positive circuit protection (fusing or breakers)
Find tech tips, manuals, and support atgpelectric.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>