SPACE SAVER SSETU Series Point of Use Electric Tankless Installation Guide

September 14, 2024
SPACE SAVER

SPACE SAVER SSETU Series Point of Use Electric Tankless

EASY INSTALLATION

  • Compact size perfect for point-of-use applications close to fixtures
  • Mounts easily to the wall
  • No venting required
  • ½” NPT water connection
  • No T&P valve required (check local codes)

WIDE ARRAY OF MODELS AND MODES OF OPERATION

  • 1.75kW – 3.5kW, 120V
  • 3.5kW – 11kW, 240V (208V)
  • Single Phase, 50/60 Hz
  • Two mode options, easy switching
  • Lavatory mode, default 105°F; temp range 80°F – 149°F
  • Emergency eye wash mode, 85°F

ONBOARD SELF-DIAGNOSTICS & TROUBLESHOOTING

  • Onboard self-diagnostics to monitor performance and protect the unit
  • Bright LED display for status updates and making system selections and adjustments
  • Error codes for troubleshooting and faster resolution

HIGHLY EFFICIENT & RELIABLE THERMOSTATIC DESIGN

  • On-demand water heater capable of supplying endless hot water when appropriately sized
  • Ultra-low activation of 0.17 GPM min.
  • Energy efficiency 0.91 UEF or higher
  • Dry-fire protection to prevent premature element failures
  • Secondary temperature regulation to limit hot water output appropriate for use with hand or eye washing applications
  • Scale detection (Patent Pending) and easy maintenance for extended service life of the heater

CONSTRUCTION

  • Housing – Bayblend® FR3010 plastic, dark gray
  • Chamber Material – Entec Nylon, glass-filled
  • Sheathed copper elements for longer life

WARRANTY

  • 6-Year limited warranty on chambers
  • 1-Year limited warranty on all parts
  • For complete information, consult the written warranty

PRODUCT SPECIFICATIONS

Model Number| Voltage (V)| Number of Elements| Total Input Wattage (kW)| Wattage per Element| Total Current Draw (Amps)| Recommended Canada Circuit Breaker Size (Amps)| Conductor Size (AWG)| Activation GPM
---|---|---|---|---|---|---|---|---
SSETU-18K| 120| 2| 1.75| 0.88| 14.58| 20| 14| 0.17
SSETU-24K| 120| 2| 2.40| 1.20| 20.00| 25| 12| 0.17
SSETU-30K| 120| 2| 3.00| 1.50| 25.00| 35| 10| 0.17
SSETU-35K| 120| 2| 3.50| 1.75| 29.17| 40| 10| 0.17
SSETU-35E| 240+| 2| 3.50| 1.75| 14.58| 20| 14| 0.17
SSETU-45E| 240+| 2| 4.50| 2.25| 18.75| 25| 12| 0.17
SSETU-55E| 240+| 2| 5.50| 2.75| 22.92| 30| 10| 0.17
SSETU-70E| 240+| 4| 7.00| 1.75| 29.17| 40| 10| 0.17
SSETU-90E| 240+| 4| 9.00| 2.25| 37.50| 50| 8| 0.17
SSETU-110E| 240+| 4| 11.00| 2.75| 45.83| 60| 8| 0.17

Copper conductors only. All wiring/conductors must be rated for 90°C or greater.
+ This model may be connected to a 208 VAC supply with reduced power output. Connection to 208 VAC may require different breaker and/or wire size than shown in the table.
NOTICE: Incoming line voltage variations may result in nuisance breaker trips. Contact Technical Support if there are multiple breaker trips when the recommended breaker size is in use.

Volts| kW| 25°F| 30°F| 35°F| 40°F| 45°F| GPM AT TEMPERATURE RISE

50°F       55°F        60°F

| 65°F| 70°F| 75°F| 80°F| 85°F
---|---|---|---|---|---|---|---|---|---|---|---|---

120V

| 1.75kW| 0.47| 0.39| 0.33| 0.29| 0.26| 0.23| 0.21| 0.20| 0.18| 0.17| –| –| –
2.4kW| 0.64| 0.54| 0.46| 0.40| 0.36| 0.32| 0.29| 0.27| 0.25| 0.23| 0.21| 0.20| 0.19
3kW| 0.80| 0.67| 0.57| 0.50| 0.45| 0.40| 0.36| 0.33| 0.31| 0.29| 0.27| 0.25| 0.24
3.5kW| 0.94| 0.78| 0.67| 0.59| 0.52| 0.47| 0.43| 0.39| 0.36| 0.33| 0.31| 0.29| 0.28
| 3.5kW| 0.94| 0.78| 0.67| 0.59| 0.52| 0.47| 0.43| 0.39| 0.36| 0.33| 0.31| 0.29| 0.28
| 4.5kW| 1.20| 1.00| 0.86| 0.75| 0.67| 0.60| 0.55| 0.50| 0.46| 0.43| 0.40| 0.38| 0.35

240V (208V)

| 5.5kW| 1.47| 1.23| 1.05| 0.92| 0.82| 0.74| 0.67| 0.61| 0.57| 0.53| 0.49| 0.46| 0.43
7kW| 1.87| 1.56| 1.34| 1.17| 1.04| 0.94| 0.85| 0.78| 0.72| 0.67| 0.62| 0.59| 0.55
| 9kW| 2.41| 2.01| 1.72| 1.50| 1.34| 1.20| 1.09| 1.00| 0.93| 0.86| 0.80| 0.75| 0.71
| 11kW| 2.94| 2.45| 2.10| 1.84| 1.63| 1.47| 1.34| 1.23| 1.13| 1.05| 0.98| 0.92| 0.87

Cold water inlet temperatures raised to 105°F setpoint.

DIMENSIONS

DIMENSIONS – SHIPPING

Models| Width

in (cm)

| Height

in (cm)

| Depth

in (cm)

| Weight

lb (kg)

1.75kW – 5.5kW| 11.25 (28)| 15.5 (38)| 8 (20)| 6.0 (2.7)
7.0kW – 11kW| 11.25 (28)| 15.5 (38)| 8 (20)| 8.0 (3.6)

INSTALLATION

ORIENTATION & CLEARANCE

  • All models must be oriented with the inlet and outlet facing upward.
  • Top clearance – a minimum of 12 inches (30.5 cm) to provide access for plumbing connections.
  • Side clearance – a minimum of 8 inches (20.3 cm) to remove the screws and protective cover and to provide access for electrical wires to enter through the side of the unit.
  • Bottom clearance – a minimum of 12 inches (30.5 cm) for access to and maintenance of heating elements. Do not store any items beneath the water heater.
  • Front clearance – a minimum of 8 inches (20.3 cm). In the absence of a door or removable access panel in front of the heater, allow a minimum of 15 inches (38.1 cm) for cover removal and ease of service.

For Technical Information call 1-888-599-2837. A. O. Smith Enterprises Ltd. reserves the right to make product changes or improvements without prior notice.