WACHENDORFF WPC002 Web Panel Series 1 Installation Guide
- September 6, 2024
- WACHENDORFF
Table of Contents
- WACHENDORFF WPC002 Web Panel Series 1
- Product Information
- Product Usage Instructions
- Guarantee conditions
- Safety instructions
- Commissioning
- Assembly instructions
- Voltage connection
- Interface arrangement
- Settings in the AutomationBrowser
- Ordering information
- Disclaimer
- Other provisions and standards
- Technical consulting & service
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
WACHENDORFF WPC002 Web Panel Series 1
Product Information
Specifications
- Product Name: WACHENDORFF WebPanel Series 1
- Model: WPC002-xxxxxxxxxxxxxxxxx2P
- Power Supply: 12 to 32 VDC
- Compatibility: Most controller DC systems
Product Usage Instructions
Guarantee Conditions
Defective devices are either repaired or replaced under specific conditions.
Please note that the warranty may be void under certain circumstances such as
age, damage due to misuse, unauthorized repairs, or removal of labeling.
Safety Instructions
- Power Supply: Ensure to use an output power that complies with SELV requirements. Connect both power supply connections from the same voltage source.
- Fuse/Switch On: If the display does not switch on within 5 seconds, switch it off and check the wiring before trying again.
- Overvoltage: Ensure adequate isolation from main power supply and similar hazards for DC voltage sources.
- EMERGENCY STOP: Install a hard-wired EMERGENCY STOP in every system to meet safety recommendations.
Supply Voltage Conditions: Do not switch on the
device under inductive load or use the same supply voltage as the
controller.
Wiring
Be cautious with wiring to prevent internal faults and unintentional device
start. Take precautions with programmable controls to avoid property damage or
operator injury.
Commissioning
Refer to the installation instructions for commissioning and installation of
the Wachendorff WebPanel WPC002xxxxxxxxxxxxxxx2P. Detailed specifications and
applications can be found in the data sheet.
FAQ
-
Q: What should I do if the display does not switch on?
A: If the display does not switch on within 5 seconds, switch it off, check the wiring, and try switching it on again. -
Q: Can I use different power sources for the two connections?
A: It is recommended to use the same voltage source for both power supply connections.
Foreword
Thank you for choosing a Wachendorff product. We trust that the product will
provide you with many years of valuable service. To ensure that the product
has a long life expectancy, please check and compare all connections of the
device with the installation instructions before switching on the device.
Guarantee conditions
Defective devices are either repaired or replaced.
However, this does not apply to the following points:
- The warranty is void if the appliance is older than 3 years from the date of purchase.
- Damage caused by force majeure, accident, negligence, improper installation or misuse.
- The product was put into operation or repaired by unauthorised personnel.
- By removing or damaging labelling.
Warning
Ensure that all local and national electrical standards are complied with when
installing the appliance.
Safety instructions
- Power supply: Use an output power that complies with SELV (Safety Extra-Low Voltage) requirements. The device can only be operated with direct current, voltage range: 12 to 32 VDC, compatible with most controller DC systems. If both connections are to be used in parallel for the power supply, the power supply must come from the same voltage source.
- Fuse/switch on: Secure your system/machine properly. If the display does not switch on within 5 seconds of switching on, switch it off. Check that the wiring is correct and try switching the device on again.
- Overvoltage: DC voltage sources should ensure adequate isolation from the main power supply and similar hazards.
- EMERGENCY STOP: A hard-wired EMERGENCY STOP should be installed in every system to fulfil the ICS safety recommendations.
- Supply voltage conditions: Do not switch on the device under inductive load or use the same supply voltage as the controller.
Note: The 24 VDC output of some controllers does not supply enough current to operate the monitor.
Wiring:
- a. The length of the power cables should be minimised (max: 500m shielded, 300m unshielded).
- c. If the wiring could be exposed to a lightning strike or overvoltage, suitable surge arresters must be used.
- d. Keep AC, high-energy and fast-switching DC power cables separate from signal cables.
- e. Add a resistor and a capacitor in the parallel circuit between the unearthed DC power supply and the housing earth. This provides a path for static and high frequency power dissipation. Typical values are 1M Ohm and 4,700pF.
You should be aware that the devices could fail due to an internal fault and thus reach an unsafe state. In addition, electrical faults in the user interface can lead to an unintentional start of the connected devices. This can lead to property damage and/or injury to the operator. If you use programmable controls that require an operator, be aware of the safety risks and take appropriate precautions.
Commissioning
This document describes the commissioning and installation of the Wachendorff WebPanel WPC002- xxxxxxxxxxxxxxx2P. Detailed descriptions of the specifications and applications can be found in the data sheet.
Electronic Surroundings| The WPC002-xxxxxxxxxxxxxxxxx2P has been tested and fulfils the European CE requirements. This means that the electronics in the device are protected against external electrical influences. In special cases, however, there is no complete protection. Correct installation of the cables and proper earthing will ensure that the
device functions perfectly.
---|---
Environment| · Ensure that the device has been installed correctly and
that the device specifications have been adhered to. Avoid installing the
devices in locations where mechanical vibrations or shocks are present.
· Do not work with the appliance in places where there is a risk of explosion, e.g. due to flammable gases, vapours or dust.
· Do not install the appliance in places where corrosive gases such as SO2 exist.
· The device is designed for vertical installation on a flat surface.
· Do not expose the appliance to direct sunlight or other sources of heat.
· Relative humidity: 10 % to 90 % (non-condensing)
IP protection class| IP65 / front
Cleaning instructions| Disconnect the appliance from the power supply before
cleaning it. Clean the appliance with cloths moistened with clean water. Do
not use liquid or spray
cleaning agents for cleaning.
Unpacking the appliance
Unpack the delivery and check that it is complete. If any damage is found,
inform the supplier.
Contents
- Installation instructions
- WPC02-xxxxxxxxxxxxxxxxx2P
- Fastening material
Assembly instructions
Use a mounting frame that provides sufficient rigidity. Refer to the data sheet for the cut-out dimensions. Fasten the monitor with all mounting holes and the brackets and screws supplied. Screw torque: 0.294 to 0.441 Nm. (To achieve a watertight effect and to prevent deformation of the panel). Plan sufficient space around the appliance and inside the installation location for ventilation and cables. Take into account the heat from other devices inside the installation location. The ambient temperature around the appliance must be between -10 and 60°C. It is recommended to allow a distance of 3 cm between the back of the appliance and other appliances.
Voltage connection
The WebPanel has 2 connections for the power supply:
- 12-pole terminal strip for 12 to 36 VDC, or
- Socket for 12 to 36 VDC via external power supply unit (accessory)
Connect:
- 12-pole terminal strip for 12 to 36 VDC:
1. connect the “+” line of your DC voltage source to the “12-36V” input of the 12-pin terminal strip and the “-” line to the “GND” input.
2. To avoid potential differences and damage to the USB ports, NEVER connect the WebPanel to multiple devices with different ground potentials.
- Socket for 12 to 36 VDC via external power supply unit: An external power supply unit is available as an accessory for connection to the mains voltage of 230 VAC. Only use this power supply unit. This is not included in the scope of delivery.
Caution: NEVER use both connections at the same time. This can lead to damage.
Interface arrangement
RK3399:
12-pole screw terminal:
PIN | Description of the |
---|---|
1 | 12-36 VDC (supply) |
2 | GND (supply) |
3 | GND |
4 | RS232 TX |
5 | RS232 RX |
6 | RS485A |
7 | RS485B |
8 | IO0 (TTL) |
9 | IO1 (TTL) |
10 | IO2 (TTL) |
11 | IO3 (TTL) |
12 | IO4 (TTL) |
Interfaces
Interface | Quantity and description |
---|---|
USB | 1x USB 3.0 type A, 1x USB 2.0 (USB/OTG) |
TF | 1x memory card microSD slot (without function, only as an option) |
SIM | 1x SIM card slot (without function, only as an option) |
Serial | 1x RS-232 DB-9 |
Ethernet | 1x RJ-45 Gigabit Ethernet |
WLAN | 1x IEEE 802.11 a/b/g/n/ac/ax |
Bluetooth: | 1x Bluetooth 5.0 |
Display | 1x HDMI, |
Submarine | 1x button for flashing the device (support only) |
Audio | 1x audio out, 3.5 mm jack |
Settings in the AutomationBrowser
All web panels with the suffix “-A” in the article number are supplied with the SpiderControl™ Automation Browser from Ininet. For the settings in the Automation Browser, use the corresponding manual “AutomationBrowser”, which is available for download on our website (https://www.wachendorff- prozesstechnik.de/downloads/panel-pc/ ).
If you have selected the AutomationBrowser as a general and permanent application, you can cancel this selection by unlocking it.
Setting options rear side
The buttons on the back of the WebPanel have no function.
Battery replacement
A 3.0 V Li/MnO2 button cell (CR2032) is installed in the web panel. The
battery may only be replaced by qualified personnel and care must be taken
when handling lithium batteries.
Ordering information
Article description | Order no. |
---|---|
WebPanel, xx” TFT, with or without touch | WPC002-xxxxxxxxxxxxxxxxx2P |
External power supply unit, 230 VAC to 24 VDC with hollow plug and C14 plug
(without 230 VAC connection cable)| DPL-PWRADAP_24VDC1.5A
230 VAC connection cable Power supply unit Panel PC| PPC-PWRCRD_01
Copyright
This document is the property of Wachendorff Prozesstechnik GmbH & Co.KG.
Copying and reproduction are prohibited without prior authorisation. The
contents of this documentation refer to the device described therein.
Disclaimer
All technical content within this document may be modified without prior
notice. The content of this document is subject to periodic revision. Repairs
will be charged to the user in the event of loss due to fire, earthquake,
third party interference or other accidents, or in the event of intentional or
accidental misuse or abuse, or use under abnormal conditions. Wachendorff
Prozesstechnik is not liable for accidental loss due to use or non-use of this
product, such as loss of business revenue.
Wachendorff Prozesstechnik is not liable for the consequences of improper use.
Radio frequencies and maximum transmission power
Frequency band | Transmission power |
---|---|
2400 – 2483.5 MHz | 20dBm EIRP max (100mW) |
5150 – 5725 MHz | 23dBm EIRP max (200mW) |
Other provisions and standards
WEEE information
Disposal of old electrical and electronic equipment (valid in the European
Union and other European countries with a separate collection system) This
symbol on the product or on the packaging means that this product must not be
treated as household waste. Instead, this product should be taken to the
appropriate disposal point for the recycling of electrical and electronic
equipment. If the product is disposed of correctly, you will help to prevent
negative environmental impacts and damage to health that could be caused by
improper disposal. Recycling material will preserve our natural resources. For
more information on how to recycle this product, please contact your local
city office, your household waste collection service or the retailer where you
purchased this product.
RoHS Directive
The device complies with the latest version of the 2011/65/EU Directive on the
restriction of the use of certain hazardous substances in electrical and
electronic equipment (commonly referred to as the Restriction of Hazardous
Substances Directive or RoHS).
RED Directive
The device complies with the latest version of the 2014/30/EU (Electromagnetic
Compatibility Directive) and 2014/53/EU (Radio Equipment Directive, RED)
directives.
A complete version of the EU Declaration of Conformity is available on
request.
Technical consulting & service
If you have any questions about the product, you can find technical support on our homepage: https://www.wachendorff-prozesstechnik.de/tbs/
- For technical support after a purchase (commissioning, project planning, parameterization, configuration, programming, etc.), please dial: +49 6722 9965-966 or send an e-mail to: support@wachendorff.de
- For application advice before a possible purchase (product selection, suitability, recommendation), please call: +49 6722 9965-544 or send an e-mail to: beratung@wachendorff.de
In the event of a repair or device failure, please contact our technical advice & service team first. More than 75% of all cases are resolved over the phone, saving you any costs or the dispatch of your product. You will also receive information on the return procedure.
For the return process, please go to our homepage at https://www.wachendorffprozesstechnik.de/garantie-und-reparatur, open the “Request return number” form and follow the instructions. After we have checked your form, we will send you a document with a return authorisation number (RSN) by e-mail. Please enclose this document with your return.
Note:
The return authorisation number (RSN) is generated specifically for your
return. It regulates the conditions and ensures direct allocation and faster
processing of your return. It is therefore extremely important that the RSN is
enclosed with your return.
Contact:
Support: Phone +49 (0) 67 22 / 99 65 -966, e-mail to
support@wachendorff.de
Application advice: Tel. +49 (0) 67 22 / 99 65 -544, e-mail to
beratung@wachendorff.de
Visit us on the Internet: www.wachendorff-prozesstechnik.de
Wachendorff Prozesstechnik GmbH & Co. KG
Industriestrasse 7 – D-65366 Geisenheim
Phone: +49 (0) 67 22 / 99 65 – 20
Fax: +49 (0) 67 22 / 99 65 – 78
E-mail: wp@wachendorff.de
www.wachendorff-prozesstechnik.de
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>