staticdj ETCR-FA-FB Series Flexible Coil Current Sensor User Guide

August 31, 2024
staticdj

ETCR-FA-FB Series Flexible Coil Current Sensor

“`html

Specifications:

  • Function: Detecting of AC leakage current, AC big current, high
    harmonic currents, complex waveforms current, inrush transient
    current, phase, electric energy, power, power factor.

  • Testing method: Flexible CT – the output signal is the
    derivative of the current with respect to time, the input current
    can be truly restored by integrating the output voltage
    signal.

  • Coil Diameter: 7.5mm/12mm (optional)

  • Range: 10mA to 10,000A

  • Resolution: 10mA

  • Output Interface: Electric field interference

  • Wire Position: Current Frequency Response Frequency

  • Line Voltage: Working Temperature and Humidity

  • Storage Temperature and Humidity: -10~60°C; below 70%rh

  • Insulation strength: AC 2000V/rms (The two ends of the coil
    after unlocking and unfolding)

  • Suitable Safety Standard: CAT IV 600V, CAT 1000V

Product Usage Instructions:

1. Introduction:

The ETCR-FA-FB Series Flexible Coil Current Sensor is designed
for detecting various types of currents and waveforms. It offers
precise measurements and is suitable for a range of
applications.

2. Model Category:

The product is available in various models with different coil
circle diameters, lengths, and weights. Choose the model that best
suits your requirements.

3. Technical Specification:

Ensure you understand the technical specifications of the
sensor, including its function, testing method, range, resolution,
and safety standards before use.

4. The Principle And Structure:

Get familiar with the components of the sensor including the
coil, trigger, output lead, and handle. Understanding the structure
will help in efficient usage.

FAQ:

Q: Can the coil length and interface be customized?

A: Yes, the coil length and interface can be customized
according to specific requests.

Q: What is the suitable safety standard for the product?

A: The product complies with CAT IV 600V and CAT 1000V safety
standards.

“`

ETCR-FA-FB Series Flexible Coil Current Sensor
Manual
Precautions For Use:
Thanks for your purchase of ETCR series flexible coil current sensor (alternate name: flexible coil, Rogowski Coil, flexible coil current sensor)of our company. In order to better use this product, please be sure to read this user manual in detail: —Read this user manual in details. — Comply by the safety rules and precautions listed in this manual.
Under any circumstance, shall pay special attention on safety in using this sensor. Pay attention to the text labeled on the panel and backplane of the sensor. Keep the sensor clean, maintenance regularly and avoid random bending. Stop using the sensor when there is rupture or break. Do not place and store the meter in high temperature and humidity or dewy places and under direct
sunlight for a long time. Use, disassembly and maintenance of this leakage current meter shall hand by authorized personnel. In case dangers would occur if continue to use a faulty leaker, please stop to use it and seal it for
safekeeping immediately; and then, send it for disposal of authorized agency. The meter manual with the danger mark ” “, users must follow instructions to operate safely.
1. Introduction
ETCR series flexible coil current sensor is composed of coil and handle. The coil hasn`t any bare metal conductor, no-contact measurement, safe and reliable. It is small in size, light in weight, exquisite in appearance, soft and flexible, suitable for narrow environment and flat cable dense place. The measurement range is wide, high accuracy, strong reliability and wide response frequency band (0.1 Hz-1 MHz). Users can customize the coil length according to the request. Widely used in electric power, communications, meteorology, railway, oil field, construction, measurement, scientific research and teaching units, industrial and mining enterprises and other fields. Especially suitable for the flat cable dense place, current test of transformer grounding core , thick wire and cable, relay protection, silicon controlled rectifier, frequency conversion speed regulation, semiconductor switch, power electronic conversion equipment, arc welding and other industrial environment with serious signal distortion.
ETCR series flexible coil current sensor, which is Rogowski coil, adopts advanced Rogowski Coil technology, which is a loop coil uniformly wound on non-ferromagnetic materials, with no hysteresis effect, almost zero phase error, no magnetic saturation, high linearity and strong anti-interference ability. The output signal is the differential of the current with respect to time. By integrating the output voltage signal, the input current can be truly restored. The measured current ranges from milliamperes up to ten thousands of amperes. It is mainly used for the detection of AC leakage current, large current, higher harmonic current (up to 400 times), complex waveform current, transient impulse current, phase, electric energy, power and power factor. With integrator, it is easy to integrate into other equipment, such as phase detection analyzer, industrial control device, data recorder, oscilloscope, harmonic analyzer, power quality analyzer, high-precision digital multimeter, transient impact recorder, distributed measurement system, protection system, etc.
1

2. Model Category
Product Photo

Model ETCR50FA

Coil Circle Diameter
50mm

Coil Length Coil Weight

160mm

80g

ETCR100FA

100mm

320mm

90g

ETCR150FA

150mm

480mm

100g

ETCR200FA

200mm

640mm

110g

ETCR300FA

300mm

950mm

132g

ETCR500FA

500mm

1580mm

170g

ETCR1000FA 1000mm

3150mm

290g

ETCR1500FA 1500mm

4720mm

390g

ETCR200FB

200mm

640mm

212g

ETCR300FB

300mm

950mm

274g

ETCR500FB

500mm

1580mm

400g

ETCR1000FB 1000mm

3150mm

715g

ETCR2000FB 2000mm

6290mm

1340g

ETCR3000FB 3000mm

9420mm

Note: Coil length and interface can be customized according to request.

1970g

Coil Diameter 7.5mm 12mm

3. Technical Specification

Function Testing method

Detecting of AC leakage current, AC big current, high harmonic currents, complex Waveforms current, inrush transient current, Phase, electric energy, power, power factor.
Flexible CT: The output signal is the derivative of the current with respect to time, The input current can be truly restored by integrating the output voltage signal

Coil diameter 7.5mm/12mm (optional)

Range

10mA10000ALarge

Resolution 10mA

Accuracy Class ±0.1%FS (50Hz/60Hz; 23±2, Below 70%RH, cable in the center of the coil)

Phase Error 0.1°(50Hz/60Hz; 23±2)

Output Interface
Electric field interference
Wire Position
Current Frequency Response Frequency
Line Voltage
Working Temperature and Humidity
Storage Temperature and Humidity
Insulation

3.5mm audio plug/ BNC plug/ pigtail (optional), wire length: 2M No hysteresis effect, No electric interfering field The tested wire is at the center of the coil, position error influence ± 0.3% FS 45Hz~70Hz(The tested current frequency) 0.1Hz~1MHz Below AC 1000V line test -20~50; below 80%rh
-10~60; below 70%rh AC 2000V/rms (The two ends of the coil after unlocking and unfolding)

2

strength
Suitable Safety Standard

CAT IV 600V CAT 1000V

4. The Principle And Structure
The theoretical basis of Rogowski coil measure current is Faraday’s law of electromagnetic induction and ampere circuit law. When the measured current I passes through the center of Rogowski coil along the axis, it generates a corresponding magnetic field within the volume surrounded by the ring winding, whose intensity is H. According to the ampere circuit law, it is made as follows: H·dl=I(t). The induction voltage of the coil is proportional to the change rate of H, so the sum of the induced potentials of all the coils is proportional to the rate of change of the current. In other words, e(t)=di/dt, and the integral of output voltage e(t) can get I. Therefore, Rogowski coil is generally used with integrator.

4.1. Coil pigtail output 4.2. Coil pigtail output 4.3. Lead shield layer 4.4. Audio plug

4.5. Output lead

4.6.Coil

4.7.Handle

4.8.Trigger

4.1. Coil pigtail output 4.2. Coil pigtail output 4.3. Lead shield layer 4.4. Output lead

4.5. Flexible Coil

4.6.Lock catch

3

The company is not responsible for other losses caused by use. The contents of this user manual cannot be used as a reason to use the product for special purposes. The company reserves the right to modify the contents of the user manual. If there are any changes, no further notice will be given.

Contact us: support@eitaiinst.com
Follow us: @eitai_inst
4

www.eitaiinst.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals