CMA Series Horizontal Side Discharge Condensing Air Conditioners
“`html
Specifications
-
Model Numbers: CMA1512SA-1, CMA1518SA-1, CMA1524SA-1,
CMA1530SA-1, CMA1536SA-1, CMA1548SA-1 -
Installation: Horizontal/Side Discharge Condensing Units
Product Information
The Horizontal/Side Discharge Condensing Units are designed for
efficient air conditioning. This product comes with safety
precautions and guidelines to ensure proper installation and
operation.
Product Usage Instructions
Safety Precautions
Before installation or operation, carefully read the manual
provided. Ensure the appliance is intact and undamaged.
Modifications or alterations to the appliance are not allowed for
safety reasons.
Warnings for Product Use
Ensure proper ventilation in the room to avoid oxygen deficiency
and carbon monoxide build-up. Improper installation, adjustment, or
maintenance can lead to hazards. Installation and service must be
done by a licensed professional HVAC installer or equivalent.
Warnings for Cleaning and Maintenance
Handle the equipment with care to avoid injury. Wear gloves and
protective clothing while cleaning or maintaining the unit.
Electrical Warnings
Do not attempt to repair electrical components unless qualified.
Improper handling can result in injury.
Fuse Specifications
The air conditioner’s circuit board is equipped with a fuse for
overcurrent protection. Replace the fuse with an identical
component as specified on the circuit board (e.g., T5A/250VAC,
T10A/250VAC).
FAQ
Q: Can I install the unit myself?
A: Installation and service must be performed by a licensed
professional HVAC installer or equivalent to ensure safety and
warranty claims.
Q: How often should I clean the unit?
A: Regular cleaning and maintenance are recommended to ensure
optimal performance. Handle the equipment with care and wear
protective gear.
Q: What should I do in case of a fuse blowout?
A: If the fuse blows out, replace it with an identical component
following the specifications indicated on the circuit board.
“`
Installation Manual
Horizontal/Side Discharge Condensing Units
Model CMA1512SA-1 CMA1518SA-1 CMA1524SA-1 CMA1530SA-1 CMA1536SA-1 CMA1548SA-1
IMPORTANT NOTE: Read this manual carefully before installing or operating your
new air conditioning unit. Make sure to save this manual for future reference.
517.787.2100 · www.marsdelivers.com
IOM – Horizontal/Side Discharge Condensing Units
INSTALLATION MANUAL
SAFETY PRECAUTIONS
03
ACCESSORIES
07
REFRIGERANT PIPING CONNECTION
08
OUTDOOR UNIT INSTALLATION
12
WIRING
16
SPECIFICATION
21
AIR EVACUATION
22
NOTE ON ADDING REFRIGERANT
23
TEST RUN
24
Read this manual
Inside you’ll find many helpful hints on how to use and maintain your air
conditioner properly. Just a little preventive care on your part can save you
a great deal of time and money over the life of your air conditioner. These
instructions may not cover every possible condition of use, so common sense
and attention to safety is required when installing, operating and maintaining
this product.
2
IOM – Horizontal/Side Discharge Condensing Units
SAFETY PRECAUTIONS
Intended Use
The following safety guidelines are intended to prevent unforeseen risks or
damage from unsafe or incorrect operation of the appliance. Please check the
packaging and appliance on arrival to make sure everything is intact to ensure
safe operation. If you find any damage, please contact the retailer or dealer.
Please note modifications or alterations to the appliance are not allowed for
your safety. Unintended use may cause hazards and loss of warranty claims.
Explanation of Symbols
WARNING The signal word indicates a hazard with a medium level of risk which,
if not avoided, may result in death or serious injury. CAUTION The signal word
indicates a hazard with a low degree of risk which, if not avoided, may result
in minor or moderate injury. NOTICE The signal word indicates important
information (e.g. damage to property), but not danger. Read these operating
instructions carefully and attentively before using/commissioning the unit and
keep them in the immediate vicinity of the installation site or unit for later
use!
WARNING
This appliance is not intended for use by persons(including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
3
IOM – Horizontal/Side Discharge Condensing Units
WARNINGS FOR PRODUCT USE
· If an abnormal situation arises (like a burning smell), immediately turn off
the unit and disconnect the power. Call your dealer for instructions to avoid
electric shock, fire or injury.
· Do not insert fingers, rods or other objects into the air inlet or outlet.
This may cause injury, since the fan may be rotating at high speeds.
· Do not use flammable sprays such as hair spray, lacquer or paint near the
unit. This may cause fire or combustion.
· Do not store gasoline or flammable substances near air conditioner. Emitted
gas may collect around the unit and cause explosion.
· Do not Install your air conditioner in a wet room such as a bathroom or
laundry room. Too much exposure to water can cause electrical components to
short circuit.
· Do not expose your body directly to cool air for a prolonged period of time.
· Do not allow children to play with the air conditioner. Children must be supervised around the unit at all times.
· If the air conditioner is used together with burners or other heating devices, thoroughly ventilate
the room to avoid oxygen deficiency and carbon monoxide build up.
· In certain environments, such as kitchens, server rooms, etc., the use of specially designed
air-conditioning units is highly recommended.
·
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional
HVAC installer or equivalent, service agency, or the gas supplier.
WARNINGS FOR CLEANING AND MAINTENANCE
· Turn off the device and disconnect the power before cleaning. Failure to do
so can cause electrical shock.
· Do not clean the air conditioner with excessive amounts of water.
· Do not clean the air conditioner with combustible cleaning agents.
Combustible cleaning agents can cause fire or deformation.
CAUTION
· Turn off the air conditioner and disconnect the power if you are not going
to use it for a long time. · Make sure that water condensation can drain
unhindered from the unit. · Do not operate the air conditioner with wet hands.
This may cause electric shock. · Do not use device for any other purpose than
its intended use. · Do not climb onto or place objects on top of the outdoor
unit. · As with any mechanical equipment, contact with sharp sheet metal edges
can result in personal
injury. Take care while handling this equipment and wear gloves and protective
clothing.
4
IOM – Horizontal/Side Discharge Condensing Units
ELECTRICAL WARNINGS
· Do not share the electrical circuit with other appliances. This equipment
requires a dedicated electrical circuit.
· The product must be properly grounded at the time of installation, or
electrical shock may occur. · For all electrical work, follow all local and
national wiring standards, regulations, and the
Installation Manual. Connect cables tightly, and clamp them securely to
prevent external forces from damaging the terminal. Improper electrical
connections can overheat and cause fire, and may also cause shock. All
electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units. · All wiring
must be properly arranged to ensure that the control board cover can close
properly. If the control board cover is not closed properly, it can lead to
corrosion and cause the connection points on the terminal to heat up, catch
fire, or cause electrical shock.
WARNINGS FOR PRODUCT INSTALLATION
· Installation must be performed by an authorized dealer or specialist.
Defective installation can cause water leakage, electrical shock, or fire.
· Installation must be performed according to the installation instructions.
Improper installation can cause water leakage, electrical shock, or fire. (In
North America,installation must be performed in accordance with the
requirement of NEC and CEC by authorized personnel only.)
· Contact an authorized service provider for repair or maintenance of this
unit. This appliance shall be installed in accordance with national wiring
regulations.
· Only use the included accessories, parts, and specified parts for
installation. Using non-standard parts can cause water leakage, electrical
shock, fire, and can cause the unit to fail.
· Install the unit in a firm location that can support the unit’s weight. If
the chosen location cannot support the unit’s weight, or the installation is
not done properly, the unit may fall and cause serious injury and damage.
· Install drainage piping according to the instructions in this manual.
Improper drainage may cause water damage to your home and property.
· Do not install the unit in a location that may be exposed to combustible gas
leaks. If combustible gas accumulates around the unit, it may cause fire.
· Do not turn on the power until all work has been completed. · When moving or
relocating the air conditioner, consult experienced service technicians for
disconnection and reinstallation of the unit. · Unit must be properly
supported and secured to prevent tipping of unit. · Excessive Weight Hazard –
Use two or more people when moving and installing the unit. Failure
to do so can result in back or other type of injury.
5
IOM – Horizontal/Side Discharge Condensing Units
TAKE NOTE OF FUSE SPECIFICATIONS
The air conditioner’s circuit board (PCB) is designed with a fuse to provide
overcurrent protection. This fuse must be replaced with an identical
component. The specifications of the fuse and printed on the circuit board
,examples of such are T5A/250VAC and T10A/250VAC.
NOTE ABOUT FLUORINATED GASSES (NOT APPLICABLE TO THE UNIT USING R290
REFRIGERANT)
· This air-conditioning unit contains fluorinated greenhouse gasses. For
specific information on the type of gas and the amount, please refer to the
relevant label on the unit itself or the “Owner’s Manual – Product Fiche ” in
the packaging of the outdoor unit. (European Union products only).
· Installation, service, maintenance and repair of this unit must be performed
by a certified technician.
· Product uninstallation and recycling must be performed by a certified
technician. · When the unit is checked for leaks, proper record-keeping of all
checks is strongly recommended.
6
IOM – Horizontal/Side Discharge Condensing Units
ACCESSORIES
The air conditioning system comes with the following accessories. Use all of
the installation parts and accessories to install the air conditioner.
Improper installation may result in water leakage, electrical shock and fire,
or equipment failure.
Accessories (Packed with the indoor unit)
Name Drain fittingsome models
Shape
Quantity 1
Gasketsome models
1
Flare-to-braze adapter(some models)
2
7
IOM – Horizontal/Side Discharge Condensing Units
REFRIGERANT PIPING CONNECTION
Safety Precautions
WARNING
· All field piping must be completed by a licensed technician and must comply
with the local and national regulations.
· When the air conditioner is installed in a small room, measures must be
taken to prevent the refrigerant concentration in the room from exceeding the
safety limit in the event of refrigerant leakage. If the refrigerant leaks and
its concentration exceeds its proper limit, hazards due to lack of oxygen may
result.
· When installing the refrigeration system, ensure that air, dust, moisture or
foreign substances do not enter the refrigerant circuit. Contamination in the
system may cause poor operating capacity, high pressure in the refrigeration
cycle, explosion or injury.
· Ventilate the area immediately if there is refrigerant leakage during the
installation. Leaked refrigerant gas is both toxic and flammable. Ensure there
is no refrigerant leakage after completing the installation work.
Notes on pipe length and elevation
Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in the following table:
The Maximum Length And Drop Height Based on Models. (Unit: m/ft.)
CAUTION
Type of model
North America, Australia and the EU frequency conversion Split Type.
Capacity (Btu/h)
<15K
15K – <24K 24K – <36K 36K – 60K
Length of piping
25/82 30/98.4 50/164 65/213
Maximum drop height
10/32.8 20/65.6 25/82 30/98.4
Oil traps If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil traps in the rising gas piping can prevent this. An oil trap should be installed every 6m(20ft) of vertical suction line riser (36000Btu/h unit). An oil trap should be installed every 10m(32.8ft) of vertical suction line riser (36000Btu/h unit).
8
IOM – Horizontal/Side Discharge Condensing Units
Name
Connecting pipe assembly
Shape Liquid side
Gas side
6.35(1/4in) 9.52( 3/8in) 12.7( 1/2in) 16( 5/8in) 19( 3/4in) 22( 7/8in)
Quantity(PC)
The correct connecting pipes are included with your equipment.
Air Handler Unit Model
Air Handler Unit Connection(in.flare)
Adapter Required at Air Handler Unit (in.flare to braze)
Outdoor Model
Outdoor Unit Connection (in. flare)
18K/24K
Liquid
3/8
Gas
3/4
3/8flare 3/8braze
Liquid 3/8
18K/24K
3/4flare 3/4braze
Gas
5/8
Liquid
3/8
24K/30K/36K/48K
Gas
3/4
60K
Liquid
3/8
Gas
7/8
3/8flare 3/8braze 24K(Hyper Liquid 3/8 Heat)/30K/
3/4flare 3/4braze 36K/48K
Gas
3/4
3/8flare 7/8flare
3/8braze 7/8braze
60K
Liquid 3/8
Gas
7/8
Adapter Required at Outdoor Unit (in. flare to flare or braze)
3/8flare 5/8flare 5/8flare 3/8flare
3/8braze 3/4flare 3/4braze 3/8braze
3/4flare 3/4braze
3/8flare 3/8braze
7/8flare 7/8braze
9
IOM – Horizontal/Side Discharge Condensing Units
Connection Instructions–Refrigerant Piping
CAUTION
· The branching pipe must be installed horizontally. An angle of more than 10°
may cause malfunction. · DO NOT install the connecting pipe until both indoor
and outdoor units have been installed. · Insulate both the gas and liquid
piping to prevent condensation.
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them
properly. This will ensure efficient operation and minimize the need for
future maintenance.
Measure the distance between the · indoor and outdoor units.
Using a pipe cutter, cut the pipe a · little longer than the measured
distance. Make sure that the pipe is cut at a · perfect 90° angle.
Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They
must be completely removed.
· Hold the pipe at a downward angle to prevent burrs from falling into the
pipe.
· Using a reamer or deburring tool, remove all burrs from the cut section of
the pipe.
Pipe Reamer
Point down
90°
Oblique Rough Warped
DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This
will drastically reduce the heating
Step 3: Flare pipe ends
Proper flaring is essential to achieve an airtight seal.
· After removing burrs from cut pipe, seal the ends with PVC tape to prevent
foreign materials from entering the pipe.
· Sheath the pipe with insulating material. · Place flare nuts on both ends of
pipe. Make sure
they are facing in the right direction, because you can’t put them on or
change their direction after flaring.
Flare nut
Copper pipe
· Remove PVC tape from ends of pipe when ready to perform flaring work.
10
IOM – Horizontal/Side Discharge Condensing Units
· Clamp flare form on the end of the pipe. The end of the pipe must extend
beyond the flare form.
Flare form
(Smaller diameter) (Bigger
Pipe
· Place flaring tool onto the form. · Turn the handle of the flaring tool
clockwise
until the pipe is fully flared.
PIPING EXTENSION BEYOND FLARE FORM
Pipe gauge
Tightening torque
Flare dimension(A) (Unit:mm/lnch)
Min.
Max.
Flare shape
(180-200kgf.cm)
32-39 N.m (320-390kgf.cm)
49-59 N.m (490-590kgf.cm)
57-71 N.m (570-710kgf.cm)
67-101 N.m (670-1010kgf.cm)
85-110 N.m (850-1100kgf.cm)
· Remove the flaring tool and flare form, then inspect the end of the pipe for
cracks and even flaring.
Step 4: Connect pipes
Connect the copper pipes to the indoor unit first, then connect it to the
outdoor unit. You should first connect the low-pressure pipe, then the high
pressure pipe.
· When connecting the flare nuts, apply a thin coat of refrigeration oil to
the flared ends of the pipes.
· Align the center of the two pipes that you will connect.
· Tighten the flare nut snugly by hand. · Using a wrench, grip the nut on the
unit tubing. · While firmly gripping the nut, use a torque
wrench to tighten the flare nut according to the torque values in above table.
NOTICE
Use both a spanner and a torque wrench when connecting or disconnecting pipes
to/from the unit.
11
Torque wrench
CAUTION
Ensure to wrap insulation around the piping. Direct contact with the bare
piping may result in burns or frostbite. · Make sure the pipe is properly
connected.
Over tightening may damage the bell mouth and under tightening may lead to
leakage.
NOTICE MINIMUM BEND RADIUS
Carefully bend the tubing in the middle according to the diagram below. DO NOT
bend the tubing more than 90° or more than 3 times. Use care when bending
pipe, do not kink pipe.
Use appropriate tool
min-radius 10cm(3.9 ) · After connecting the copper pipes to the
indoor unit, wrap the power cable, signal cable and the piping together with
binding tape.
NOTICE
DO NOT intertwine signal cable with other wires. While bundling these items
together. DO NOT intertwine or cross the signal cable with any other wiring.
IOM – Horizontal/Side Discharge Condensing Units
OUTDOOR UNIT INSTALLATION
Select the installation location of outdoor units
Before installing the outdoor unit, you must choose an appropriate location.
The following are standards that will help you choose an appropriate location
for the unit.
Proper installation locations meet the following standards:
60cm(24in) above
4″ from back wall
30cm(12in) on left
60cm(24in) on right
200cm(79in) in front
Front view
Top view
Meets all spatial requirements shown in Installation
Space Requirements above.
Firm and solid–the location can
Noise from the unit will
support the unit and will not vibrate.
not disturb other people.
15cm(6in)
The outdoor unit must be installed on risers of at least
15cm(6in) in height or per local code to get unit above local mean snow fall.
Good air circulation
and ventilation.
DO NOT install unit in the following locations:
Where snowfall is anticipated,
take appropriate measures to prevent ice buildup and coil damage.
Near an obstacle that will block air inlets and outlets.
In a location that is exposed to large amounts of dust.
Near animals or plants that will be harmed by hot air discharge. Near any source of combustible gas
Near a public street, crowded areas, or where noise from the unit will disturb others.
CAUTION:
SPECIAL CONSIDERATIONS FOR EXTREME WEATHER
If the unit is exposed to heavy wind:
Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier
in front of the unit to protect it from extremely heavy winds. See Figures below.
If the unit is frequently exposed to heavy rain or snow:
Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow
around the unit.
Strong wind
Wind Baffle
Shelter
Strong wind
90° angle to the direction of the wind
Strong wind
Build a wind Baffle to protect the unit
Build a shelter to protect the unit
12
IOM – Horizontal/Side Discharge Condensing Units
Install drain fitting(Heat pump unit only)
Step 1
Find out the base pan hole of outdoor unit.
Seal
Base pan hole of outdoor unit
Step 2
Fit the rubber seal on the end of the drain fitting that will connect to the
outdoor unit.
Insert the drain fitting into the hole in the base pan of the unit. The drain
fitting will click in place.
Connect a drain hose extension (not included) to the drain fitting to redirect
water from the unit during heating mode.
IN COLD CLIMATES
In cold climates, make sure that the drain hose is as vertical as possible to
ensure swift water drainage. If water drains too slowly, it can freeze in the
hose and flood the unit.
13
IOM – Horizontal/Side Discharge Condensing Units
Anchor outdoor unit
The outdoor unit can be anchored to the ground or to a wall-mounted bracket
with bolt(M10). Prepare the installation base of the unit according to the
dimensions below.
Outdoor Unit Types and Specifications
D B
H
A H
W
W
Front view
Top view
Outdoor Unit Dimensions
W
H
mm
inch
mm
inch
mm
805
31-11/16
554
21-13/16
330
890
35
673
26-1/2
342
946
37-1/4
810
31-29/32
410
952
37-1/2
1333
52-1/2
415
980
38-19/32
975
38-13/32 410
D
inch 13
13-15/32 16-5/32 16-11/32 16-5/32
Mounting Dimensions
A
B
mm
inch
mm
511
20-1/8
317
inch 12-1/2
663
26-1/8
354
13-15/16
673
26-1/2
403
15-7/8
634
24-35/36
404
15-29/32
616
24-1/4
397
15-5/8
(unit: mm/inch)
o2r5mcomre/
9.8″25 or
mcmor/e
9.8″
H
L
A
150
ocmr m/o5r9e”60
cm or
m/ 2o3re.6″
300
cm
/
118″
or more
Rows of series installation
The relations between H, A and L
are
as
follows.
L H
L
L 1/2H
A
25 cm / 9-13/16in or more
1/2H < L H
30 cm / 11-13/16in or more
L > H
Can not be installed
14
IOM – Horizontal/Side Discharge Condensing Units
If you will install the unit on the ground or on a concrete mounting platform,
DO THE FOLLOWING:
Mark the positions for four expansion bolts based on dimensions chart.
Pre-drill holes for expansion bolts. Place a nut on the end of each expansion
bolt. Hammer expansion bolts into the pre-drilled
holes. Remove the nuts from expansion bolts, and
place outdoor unit on bolts. Put washer on each expansion bolt, then
replace the nuts. Using a wrench, tighten each nut until snug.
WARNING
WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIMES.
If you will install the unit on a wall-mounted bracket,
DO THE FOLLOWING:
Mark the position of bracket holes based on dimensions chart.
Pre-drill the holes for the expansion bolts. Place a washer and nut on the end
of each
expansion bolt. Thread expansion bolts through holes in
mounting brackets, put mounting brackets in position, and hammer expansion
bolts into the wall. Check that the mounting brackets are level. Carefully
lift unit and place its mounting feet on brackets. Bolt the unit firmly to the
brackets. If allowed, install the unit with rubber isolator pads o reduce
vibrations and noise.
CAUTION
Make sure that the wall is made of solid brick, concrete, or of similarly
strong material. The wall must be able to support at least four times the
weight of the unit.
15
IOM – Horizontal/Side Discharge Condensing Units
WIRING PRECAUTIONS
WARNING
BEFORE PERFORMING ANY ELECTRICAL WORK, READ THESE WARNINGS.
All wiring must comply with local and national electrical codes, regulations
and must be installed by a licensed electrician.
All electrical connections must be made according to the Electrical Connection
Diagram located on the panels of the indoor and outdoor units.
If there is a serious safety issue with the power supply, stop work
immediately. Explain your reasoning to the client, and refuse to install the
unit until the safety issue is properly resolved.
Power voltage should be within 90-110% of rated voltage. Insufficient power
supply can cause malfunction, electrical shock, or fire.
Installation of an external surge suppressor at the outdoor disconnect is
recommended.
Power must be connected, a switch or circult breaker that disconnects all
poles and has a contact separation of at least 1/8in (3mm) must be
incorporated in the fixed wiring. The qualified technician must use an
approved circuit breaker or switch.
Only connect the unit to an individual branch circuit. Do not connect another
appliance to that circuit.
Make sure to properly ground the air conditioner. Every wire must be firmly
connected. Loose
wiring can cause the terminal to overheat, resulting in product malfunction
and possible fire.
Do not let wires touch or rest against refrigerant tubing, the compressor, or
any moving parts within the unit.
To avoid getting an electric shock, never touch the electrical components soon
after the power supply has been turned off. After turning off the power,
always wait 10 minutes or more before you touch the electrical components.
Make sure that you do not cross your electrical wiring with your signal
wiring. This may cause distortion, interference or
possibly damage to circuit boards. Connect the outdoor wires before
connecting the indoor wires.
WARNING
BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAIN POWER TO
THE SYSTEM.
16
IOM – Horizontal/Side Discharge Condensing Units
OUTDOOR UNIT WIRING
WARNING
Before performing any electrical or wiring work, turn off the main power to
the system.
Step 1: Prepare the cable for connection.
1. You must first choose the right cable size. 2. Using wire strippers, strip
the jacket from
both ends of the signal cable to reveal approximately 15cm (5.9″) of wire. 3.
Strip the insulation from the ends. 4. Stranded wire requires u-lugs or ring
terminals to be crimped onto the ends of the wire.
NOTICE
When connecting the wires, strictly follow the wiring diagram found inside the
electrical box cover.
Choose the cable type according to the local electrical switchs and
regulations.
Please choose the right cable size according to the Minimum Circuit Ampacity
indicated on the nameplateof the unit.
Step 2: Remove the electric cover.
Remove the electric cover of the outdoor unit.
Cover
L1 L2
OPTIONAL
CLASS 2 B W D R C Y1 Y2 L
Outdoor Unit B
TO POWER SOURCE
4. Clamp down the cable with the cable clamp.
5. Insulate unused wires with electrical tape. Keep them away from any
electrical or metal parts.
6. Reinstall the cover of the electric control box.
In North America
1. Remove the wire cover from the unit by loosening the 3 screws.
2. Remove caps on the conduit panel. 3. Mount the conduit tubes(not included)
on the
caonduit panel. 4. Properly connect both the power supply and
low voltage lines to the corresponding terminals on the terminal block. 5.
Ground the unit in accordance with local codes. 6. Be sure to size each wire
allowing several inches longer than the required length for wiring.
Screw
Step 3: Connect the u-lugs to the terminals
Match the wire colors/labels with the labels on the terminal block. Firmly screw the u-lug of each wire to its corresponding terminal.
CLASS 2 B W D
R C Y1 Y2 L
L1 L2
Outdoor Unit A
TO POWER SOURCE
Terminal block
(O40vmerm1-)9/16″
Connecting cable
G
Power supply cord
Conduit panel
Wire Cover
Please select the appropriate through-hole according to the diameter of the
wire.
WARNING
ISOLATE THE POWER SUPPLY LEADS AND
COMMUNICATION LEADS BY THE STRAIN RELIEF AND KEEP POWER SUPPLY LEADS AWAY FROM
COMMUNICATION LEADS. DISCONNECTION MUST BE INCORPORATED IN THE FIXED WIRING IN
ACCORDANCE WITH THE WIRING RULES.
17
IOM – Horizontal/Side Discharge Condensing Units
SPECIFIC WIRING METHODS
WARNING
Please refer to the wiring nameplate for the wiring method. Do not connect 24V
AC to S1 – S2, as this will damage the system.
Connection method A:
This is the preferred method of control with the communicating control, for
the indoor and outdoor unit. Refer to the wiring method of internal and
external machine communication and wired controller as follows:
Connection method B:
To use a 24V thermostat, you need to refer to the following wiring:
24V communication
Cooling Only Outdoor Unit Only Mode
S1 S2 R C Y1 Y2 L
CN6 TO 24V THERMOSTAT
S1 ON
1 23 4
Other Outdoor Unit Only Mode
S1 S2 B W D R C Y1 Y2 L
CN6 TO 24V THERMOSTAT
24V must never be connected to S1 S2. All wiring must be in compliance with
the above scenarios. Incorrect wiring will cause irreversible damage to
control.
24V connection Dip Switch setting as shown in the picture:
Cooling Only
Other
S1-2 dip switch to be “ON”
When using a 24V thermostat, please refer to the non-communicating wiring
diagrams that follow:
Connection method C:
NOTICE
This equipment uses B functionality. This terminal is energized for heating
functionality. Please ensure that thermostat configuration is set up for B
functionality. Note: These methods are for use with a Comfort-Aire outdoor
unit and a third party indoor unit or cased coil and gas furnace.
18
NOTICE
The use of shielded communication or thermostat wire is not required, but is
recommended where separation from high voltage conductors can not be
maintained, or in areas with high electrical noise. The shield and drain
conductor must be grounded at the outdoor unit and stripped back and taped at
the indoor unit. Grounding at both ends results in an increase of noise
transmitted onto the signal wires.
IOM – Horizontal/Side Discharge Condensing Units
Outdoor unit DIP Switch setting Press the SW1 button 10S for force defrosting
SW1
S1
NO. Dial code
Features
ON
OFF
1 S1-1 2 S1-2
3 S1-3
Function to be defined
Communication dial code 24V communication scheme 485 communication scheme
Strong cold and strong heat function
The cooling/heating target The cooling/heating target
pressure compensation value pressure compensation value
is valid
is invalid
4 S1-4
Enhanced defrosting function
Enhanced defrosting
Default setting(standard defrost algorithm)
SPECIFIC WIRING METHODS
NOTICE
The following wiring diagram are suitable for the AHU and ODU with 24V
thermostat.
Non-communication scheme wiring reference
· Wiring for 4H and 2C thermostat
· Wiring for 3H and 2C thermostat
W2 W1/E O/B
Y2 Y1 G L C R DH
THERMOSTAT
DH R C L G Y1
B W W1 W2 E
INDOOR UNIT
S4-1 Default on DH function off. Turn switch off to activate DH function.
R C Y1 Y2 B W D L OUTDOOR UNIT
W1/E O/B Y2 Y1
G L C R DH
THERMOSTAT
S4-2 Default on, W1 and W2 shorted for single stage Aux heat operation. Turn off to separate stages.
DH R C L G Y1
B W W1 W2 E
INDOOR UNIT
S4-1 Default on DH function off. Turn switch off to activate DH function.
R C Y1 Y2 B W D L
S4-2 Default on, W1 and W2 shorted for single stage Aux heat operation. Turn
off to separate stages.
· Wiring for 3H and 1C thermostat
· Wiring for 2H and 2C thermostat
W2 W1/E O/B
Y G L C R DH
THERMOSTAT
O/B Y2 Y1 G C R
THERMOSTAT
DH R C L G Y1
B W W1 W2 E
R C Y1 Y2 B W D L
INDOOR UNIT
OUTDOOR UNIT
S4-1 Default on DH function off. Turn switch off to activate DH function.
S4-2 Default on, W1 and W2 shorted for single stage Aux heat operation. Turn off to separate stages.
19
DH R C L G Y1
B W W1 W2 E
INDOOR UNIT
R C Y1 Y2 B W D L OUTDOOR UNIT
IOM – Horizontal/Side Discharge Condensing Units
· Wiring for 3H and 2C thermostat
E O/B Y2 Y1
G L C R DH
THERMOSTAT
DH R C L G Y1
B W W1 W2 E
R C Y1 Y2 B W D L
INDOOR UNIT
OUTDOOR UNIT
S4-1 Default on DH function off. Emergency heating control two groups
Turn switch off to activate DH
of electric heating at the same time
function.
· Wiring for 2H and 1C thermostat
W/E O/B
Y G C R
THERMOSTAT
DH R C L G Y1
B W W1 W2 E
INDOOR UNIT
R C Y1 Y2 B W D L OUTDOOR UNIT
S4-2 Default on, W1 and W2 shorted for single stage Aux heat operation. Turn
off to separate stages.
· Wiring for 1H and 1C thermostat
O/B Y G C R
THERMOSTAT
DH R C L G Y1
B W W1 W2 E
INDOOR UNIT
R C Y1 Y2 B W D L OUTDOOR UNIT
Control logic
Indoor unit connector
Connector
R C Y1 Y2 B W D L
Purpose
24V power Connection Common Low Cooling Heat Cooling Heating Reversing Valve
Heating control Defrost control System Fault Signal
LED display
The control displays unit status as well as any active fault codes on the LED
display. If the unit is functioning normally, the LED will display current
temperature setpoint. When a fault code is active, the display will flash the
active fault code. Please refer to the fault code table located in the
troubleshooting section of the Service Manual for detailed fault code
information.
· Wiring for 1H and 1C thermostat
NOTICE
This is the least preferred method of control wiring and should only be used
for emergency situations. Full comfort capacity may not be achieved using this
method.
20
IOM – Horizontal/Side Discharge Condensing Units
POWER SPECIFICATIONS
Cooling and Heating power specifications
POWER (outdoor)
INPUT CIRCUIT FUSE
OUTDOOR UNIT POWER LINE
OUTDOOR-INDOOR SIGNAL LINE THERMOSTAT SIGNAL LINE
PHASE FREQUENCY AND VOLT
OUTDOOR UNIT(A) LINE QUANTITY
MCA MOP
LINE DIAMETER(AWG)
LINE QUANTITY LINE DIAMETER(AWG) LINE QUANTITY LINE DIAMETER(AWG)
18K
24K
Std Hyper HT 16 / 16 20 / 20
STD 12 HH 12
Std Hyper HT 19 / 20 30 / 35 2+Ground
STD 12 HH 12
30K
Std Hyper HT 20 / 23 35 / 35
STD 12 HH 10
POWER (outdoor)
INPUT CIRCUIT FUSE
OUTDOOR UNIT POWER LINE
OUTDOOR-INDOOR SIGNAL LINE THERMOSTAT SIGNAL LINE
PHASE FREQUENCY AND VOLT
OUTDOOR UNIT(A) LINE QUANTITY
MCA MOP
LINE DIAMETER(AWG)
LINE QUANTITY LINE DIAMETER(AWG) LINE QUANTITY LINE DIAMETER(AWG)
36K
36K(X6) 48K
60K
Std Hyper HT 24 / 41 40 / 50
STD 10 HH 8
Hyper HT 30 35
Std Hyper HT Std Hyper HT
34 / 42
34 / NA
50 / 50
60 / NA
2+Ground
HH 10
STD 8 HH 6
STD 8 HH NA
Cooling Only power specifications
POWER (outdoor)
INPUT CIRCUIT FUSE
OUTDOOR UNIT POWER LINE
OUTDOOR-INDOOR SIGNAL LINE THERMOSTAT SIGNAL LINE
PHASE FREQUENCY AND VOLT
OUTDOOR UNIT(A) MCA MOP
LINE QUANTITY
LINE DIAMETER(AWG)
LINE QUANTITY LINE DIAMETER(AWG) LINE QUANTITY LINE DIAMETER(AWG)
18K
CO 15 20
CO 12
24K
CO 20 30
CO 12
30K
36K 48K
CO 29 45
2+Ground
CO 12
CO 29 45
CO 12
CO 32 50
CO 10
NOTICE
Line Diameter Sizing per NFPA 70 (2020), Table 310.15 (B) (16) Based on type
NM-B Romex wire. Other sizing options are possible. Consult NFPA 70 or
Licensed Electrician for alternate sizing. Please follow the prompts on the
nameplate of the machine body for actual parameters.
21
IOM – Horizontal/Side Discharge Condensing Units
AIR EVACUATION
NOTICE
When opening valve stems, turn the hexagonal wrench until it hits against the
stopper. Do not try to force the valve to open further. Open valves slowly
until your hear refrigerant, allow pressure to equalize before opening fully.
Open large vapor line valve first.
Preparations and precautions
Air and foreign matter in the refrigerant circuit can cause abnormal rises in
pressure, which can damage the air conditioner, reduce its efficiency, and
cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant
circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is
relocated.
Evacuation Instructions
1. Connect the charge hose of the manifold gauge to service port on the
outdoor unit’s low pressure valve.
2. Connect another charge hose from the manifold gauge to the vacuum pump.
3. Open the Low Pressure side of the manifold gauge. Keep the High Pressure
side closed.
4. Tighten refrigerant valve caps hand tight to ensure there are no vacuum
leaks.
5. Turn on the vacuum pump to evacuate the system.
6. Run the vacuum for at least 15 minutes, or until the Compound Meter reads
-76cmHG(-105Pa) or 500 microns.
7. Close the Low Pressure side of the manifold gauge, and turn off the vacuum
pump.
8. Wait for 5 minutes, then check that there has been no change in system
pressure.
9. If there is a change in system pressure, refer to Gas Leak Check section
for information on how to check for leaks. If there is no change in system
pressure, unscrew the cap from the packed valve (high pressure valve).
10.Insert hexagonal wrench into the packed valve (high pressure valve) and
open the valve by turning the wrench in a 1/4 counterclockwise turn. Listen
for gas to exit the system, then close the valve after 5 seconds.
11. Watch the Pressure Gauge for one minute to make sure that there is no
change in pressure. The Pressure Gauge should read slightly higher than
atmospheric pressure.
12. Remove the charge hose from the service port.
Flare nut
Cap
Outdoor unit
valve body
valve stem
Manifold Gauge
-76cmHg
Compound gauge
Pressure gauge
Low pressure
valve Pressure hose
or Charge hose
High pressure valve Charge hose
Low pressure valve
Vacuum pump
13. Using hexagonal wrench, fully open both the
high pressure and low pressure valves. 14. Tighten all valve caps with a
wrench to
ensure no leaks. You may tighten it further
using a torque wrench if needed.
22
IOM – Horizontal/Side Discharge Condensing Units
NOTE ON ADDING REFRIGERANT
CAUTION
DO NOT mix refrigerant types.
Some systems require additional charging depending on pipe lengths. The
standard pipe length varies according to local regulations. For example, in
North America, the standard pipe length is 7.5m (25′). In other areas, the
standard pipe length is 5m (16`). The refrigerant should be charged from the
service port on the outdoor unit’s low pressure valve. The additional
refrigerant to be charged can be calculated using the following formula:
23
TEST RUN
IOM – Horizontal/Side Discharge Condensing Units
CAUTION
Failure to perform the test run may result in unit damage, property damage, or
personal injury.
Before test run
A test run must be performed after the entire system has been completely
installed. Confirm the following points before performing the test: a) Indoor
and outdoor units are properly installed. b) Piping and wiring are properly
connected. c) No obstacles near the inlet and outlet of the unit that might
cause poor performance or product malfunction. d) Refrigeration system does
not leak. e) Drainage system is unimpeded and draining to a safe location. f)
Heating insulation is properly installed. g) Grounding wires are properly
connected. h) Length of the piping and additional refrigerant capacity have
been recorded. i) Power voltage is the correct voltage for the air conditioner
Test run Instructions
1. Open both the liquid and gas service valves. 2. Turn on the main power
switch and allow the
unit to warm up. 3. Set the air conditioner to COOL mode. 4. For the Indoor
Unit
a.Double check to see if the room temperature is being registered correctly.
b.Check to see that the drainage system is unimpeded and draining smoothly.
c.Ensure there is no vibration or abnormal noise during operation.
5. For the Outdoor Unit a. Check to see if the refrigeration system is
leaking. b. Make sure there is no vibration or abnormal noise during
operation. c. Ensure the wind, noise, and water generated by the unit do not
disturb your neighbors or pose a safety hazard.
6. Drainage Test a. Ensure the drainpipe flows smoothly. New buildings should
perform this test before finishing the ceiling. b. Turn on the main power
switch and run the air conditioner in COOL mode. c. Check to see that the
water is discharged. It may take up to one minute before the unit begins to
drain depending on the drainpipe. d. Make sure that there are no leaks in any
of the piping. e. Stop the air conditioner. Turn off the main power switch and
reinstall the test cover.
NOTICE
If the unit malfunctions or does not operate according to your expectations,
please refer to the Troubleshooting section of Service Manual before calling
customer service.
The design and specifications are subject to change without prior notice for
product improvement. Consult with the sales agency or manufacturer for
details. Any updates to the manual will be uploaded to the service website,
please check for the latest version.
24
Page Intentionally Left Blank
Page Intentionally Left Blank
LIMITED EXPRESS WARRANTY `CMA’ SERIES HORIZONTAL/SIDE DISCHARGE CONDENSERS
Congratulations on purchasing your new HVAC equipment. It’s been designed for long life and reliable service, and is backed by one of the strongest warranties in the industry. Your unit automatically qualifies for the warranty coverage listed below, providing you keep your proof of purchase (receipt) for the equipment and meet the warranty conditions.
DURATION OF WARRANTY & REGISTRATION
The warranty begins on the date of purchase by the original consumer. The
consumer must retain a receipted bill of sale as proof of warranty period.
Without this proof, the express warranty begins on the date of shipment from
the factory.
LIMITED FIVE (5) YEAR PARTS EXPRESS WARRANTY
REMEDY PROVIDED BY THE LIMITED EXPRESS WARRANTY
MARS/Heat Controller warrants all parts of the `CMA’ Series
The sole remedy under the Limited Warranty is replacement of the defective
Condensing Unit to be free from defects in workmanship and materials
part. If replacement parts are required within the period of this warranty,
normal use and maintenance for five (5) year from the date of purchase
MARS/Heat Controller replacement parts shall be used; any warranty
by the original consumer. This Express Limited Warranty applies only
on the replacement part(s) shall not affect the applicable original unit
when the `CMA’ Series Condensing Unit is installed and operated
warranty. Ready access to the unit for service is the owner’s responsibility.
per MARS/Heat Controller installation and operating instructions for
Labor to diagnose and replace the defective part is not covered by this
normal use, and in accordance with all local, state and national codes.
Limited Express Warranty. If for any reason the replacement part/product
is no longer available during the warranty period, MARS/Heat Controller
LIMITED SEVEN (7) YEAR COMPRESSOR EXPRESS WARRANTY
shall have the right to allow a credit in the amount of the current suggested
The compressor only is warranted to be free from defects in
retail price of the part/product instead of providing repair or replacement.
workmanship and materials under normal use and maintenance for
a total of seven (7) years from the date of purchase by the original
LIMITATION OF LIABILITY
consumer. This seven year warranty applies only when the system is installed and operated per MARS/Heat Controller installation and operation instructions for normal use.
1. There are no other express or implied warranties. MARS/Heat Controller makes no warranty of merchantability. We do not warrant that the unit is suitable for any particular purpose or can be used
COMMERCIAL USELIMITED TWO (2) YEAR PARTS WARRANTY
When the unit is put to commercial, business, rental, or any application other
than residential use, the Two Year Parts Limited Warranty as described in
paragraph one is the only warranty that applies.
in buildings or rooms of any particular size or condition except as
specifically provided in this document. There are no other warranties, express
or implied, which extend beyond the description in this document.
2. All warranties implied by law are limited in duration to the one-
EXCEPTIONS The Limited Express Warranty does not cover normal maintenance– MARS/Heat Controller recommends that regular inspection/ maintenance be performed at least once a season and proof of
year term of the parts warranty. Your exclusive remedy is limited to the
replacement of defective parts. We will not be liable for any consequential or
incidental damages caused by any defect in this
unit.
maintenance be kept. Additionally, labor charges, transportation
3. This warranty gives you specific legal rights and you may also have
charges for replacement parts, replacement of refrigerant or filters,
other rights which vary from state to state. Some states do not allow
any other service calls/repairs are not covered by this Limited
limitation on how long an implied warranty lasts or do not allow the
Warranty. It also does not cover any portion or component of the
exclusion or limitation of incidental or consequential damages, so the
system that is not supplied by MARS/Heat Controller, regardless of
above limitations or exclusions may not apply to you.
the cause of failure of such portion or component.
4. No warranties are made for units sold outside the continental United
CONDITIONS FOR WARRANTY COVERAGE · Unit must be operated according to MARS/Heat Controller operating
States and Canada. Your distributor or final seller may provide a warranty on units sold outside these areas.
instructions included with the unit and cannot have been subjected
5. MARS/Heat Controller will not be liable for damages if our performance
to accident, alteration, improper repair, neglect or misuse, or an act
regarding warranty resolution is delayed by events beyond our control
of God (such as a flood)
including accident, alteration, abuse, war, government restrictions,
· Installation was done by a trained, licensed or otherwise qualified
strikes, fire, flood, or other acts of God.
HVAC dealer/contractor
· Performance cannot be impaired by use of any product not authorized by MARS/Heat Controller, or by any adjustments or adaptations to components
HOW TO OBTAIN WARRANTY SERVICE OR PARTS
If you have a warranty claim, notify your installer promptly. If the installer
does not remedy your claim, write to MARS, 1900 Wellworth Ave., Jackson MI
49203. Enclose a report of inspection by your installer or service person.
· Serial numbers and/or rating plate have not been altered or
Include model number, serial number, and date of purchase.
removed · Damage has not been a result of inadequate wiring or voltage
Owner responsibilities are set forth in the instruction manual–read it carefully.
conditions, use during brown-out conditions, or circuit
interruptions
KEEP THIS INFORMATION AS A RECORD OF YOUR PURCHASE
· Air flow around any section of the unit has not been restricted
`CMA’ SERIES HORIZONTAL/SIDE DISCHARGE CONDENSING UNIT
· Unit remains in the original installation · Unit was not purchased over the internet
Model Number
Model Number
Installer Name
Serial Number
Serial Number
Phone No./Contact Info
CMA15_WARRANTY_5/2024
Date of Purchase
Date Installation Completed
Remember to retain your bill of sale as proof of warranty period.
‘XHWRRQJRLQJSURGXFWLPSURYHPHQWVVSHFLILFDWLRQVDQGGLPHQVLRQVDUH
VXEMHFWWRFKDQJHDQGFRUUHFWLRQZLWKRXWQRWLFHRULQFXUULQJREOLJDWLRQV’HWHUPLQLQJWKH
DSSOLFDWLRQDQGVXLWDELOLWIRUXVHRIDQSURGXFWLVWKHUHVSRQVLELOLWRIWKHLQVWDOOHU
$GGLWLRQDOOWKHLQVWDOOHULVUHVSRQVLEOHIRUYHULILQJGLPHQVLRQDOGDWDRQWKHDFWXDOSURGXFW
SULRUWREHJLQQLQJDQLQVWDOODWLRQSUHSDUDWLRQV
,QFHQWLYHDQGUHEDWHSURJUDPVKDYHSUHFLVHUHTXLUHPHQWVDVWRSURGXFWSHUIRUPDQFH
DQGFHUWLILFDWLRQ$OOSURGXFWVPHHWDSSOLFDEOHUHJXODWLRQVLQHIIHFWRQGDWHRIPDQXIDFWXUH
KRZHYHUFHUWLILFDWLRQVDUHQRWQHFHVVDULOJUDQWHGIRUWKHOLIHRIDSURGXFW
7KHUHIRUHLWLVWKHUHVSRQVLELOLWRIWKHDSSOLFDQWWRGHWHUPLQHZKHWKHUDVSHFLILF
PRGHOTXDOLILHVIRUWKHVHLQFHQWLYHUHEDWHSURJUDPV
:HOOZRUWK$YH-DFNVRQ0,3KZZZKHDWFRQWUROOHUFRP
7/2024
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>