Foundation™
3 to 5 Tons Packaged Rooftop Units
Cooling and Gas/Electric
- Model Number: EDK GDK Used With:
- Packaged Cooling, Electric Heat (Optional)
- Packaged Cooling, Gas Heat
August 2024 RT-PRC114B-EN C2024
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
List of Options
Note: Most factory installed options are available for downflow air discharge units ally. vony win draenne system for avalabilly. Hate AMiAne
Table 1. List of options
Factory Installed Options | Field Installed Options |
---|---|
Barometric Relief(a) (Downflow Low Leak Economizer Only) | Barometric Relief |
(Standard and Low Leak Economizer, Downflow and Horizontal Configuration)
Complete Coat™ Microchannel Condenser Coil| Crankcase Heater
Condensate Overflow Switch| Demand Control Ventilation with CO2 Sensor
Economizer (Downflow)(a)| Economizer (Horizontal)
Electric Heaters| Frostat™
Low Leak Economizer – Downflow| Low Ambient Kit
Manual Outside Air Dampers| Low Leak Economizer – Horizontal
Motorized Outside Air Dampers| LP Conversion Kit
MERV-13 Filters| Powered Exhaust
Oversized Motor| Remote Potentiometer
Reference or Comparative Enthalpy Economizer| Roof Curb
Stainless Steel Heat Exchanger with 10 Year Warranty| Thermostat
Factory Installed Options| Field Installed Options
---|---
Through-the-Base Electrical Access| Tool-less Hail Guard
Through-the-Base Gas Piping|
Unit Mounted Non-Fused Disconnect Switch(b)
- a )Sane field set up fulled
- b) Must be ordered with Through the Base Electrical option
Table 2. (gas or electric aged rooftop performance data
Nominal Size (Ton) | 3 | 4 | 5 |
---|
Cooling Performance (a)
Gross Cooling Capacity| 38,000| 51,300| 59,500
AHRI Net Cooling Capacity| 36,600| 49,500| 57,500
Nominal Airflow CFM/AHRI Rated CFM| 1200/1050| 1600/1400| 2000/1600
EER(b)/EER2(c)| 12.0/10.6| 12.0/10.6| 12.0/10.6
SEER(b)/SEER2)(c)| 14.0/13.4| 14.0/13.4| 14.0/13.4
Gas Heating Performance
Low Heat (Input/Output) – (Btu/h)| 72,000/57,600| 72,000/57,600| 72,000/57,600
Medium Heat (Input/Output) – (Btu/h)| 100,000/80,000| 115,000/ 92,000|
115,000/ 92,000
Other Information
Net Weight (lbs) – Gas Heat| 524| 566| 586
Net Weight (lbs) – Electric Heat| 473| 516| 536
Filters – Type Furnished| Throwaway| Throwaway| Throwaway
Number and Size Recommended| (4) 16×16×2| (4) 16×16×2| (4) 16×16×2
- (a) Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb.
- (b) EER and SEER are rated at AHRI conditions and calculated in accordance with AHRI Standard 210/240-2017. Airflow and net cooling capacity not shown.
- (c) EER2 and SEER2 are rated at AHRI conditions and certified in accordance with AHRI Standard 210/240-2023.
Table 3. Unit MCA and MOP electrical data (standard indoor fan motor – cooling or gas heat)
Tons
| Unit Operating Voltage Range| Standard Indoor Fan Motor
---|---|---
Minimum Circuit Ampacity (a)| Maximum Fuse Size or
Maximum Circuit Breaker
3
| 208-230| 23| 30
460| 11| 15
575| 9| 15
4
| 208-230| 23| 35
460| 11| 15
575| 10| 15
5
| 208-230| 28| 40
460| 13| 15
575| 11| 15
- (a) Values do not include Power Exhaust accessory.
Table 4. Unit indoor fan data
E/GDK | Volts | Standard (HP – RPM) | Oversized (HP – RPM) |
---|---|---|---|
036 | 208-230 | 1 – 1725 | 2 – 1725 |
460
575
048| 208-230| 1 – 1725| 2 – 1725
460
575
060| 208-230| 1 – 1725| 2 – 1725
460
575
Table 5. Unit dimensional data
| 3 to 5 Tons
---|---
Unit Length UL| 76.814 in.
Unit Width UW| 47.934 in.
Unit Height UH| 42.004 in.
Curb Length CL| 70.871 in.
Curb Width CW| 41.983 in.
Supply Length SL (a)| 21.060 in.
Supply Width SW (a)| 14.000 in.
Return Length RL (a)| 32.188 in.
Return Width RW (a)| 14.430 in.
- (a) Dimensions are for curb openings and not duct inserts. Reference the product catalog for duct insert dimensions.
Trane and American Standard create comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit. trane.com or americanstandardar.com. Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print exactly. RT.PRC114B-EN 23 Aug 2024 Supersedes RT-PRC1144-EN (Jul 2024)