Hunter WVL-100 Wireless Valve Link Owner’s Manual
- August 21, 2024
- Hunter
Table of Contents
WVL-100, -200, -400
Wireless Valve Link (WVL)
Wireless Valve Link
OWNER’S MANUAL
WVL-100 Wireless Valve Link
Need more helpful information on your product? Find tips on installation, controller programming, and more.
Introduction
The Hunter Wireless Valve Link System eliminates some of the biggest
contractor costs in irrigation installations: copper wire and unnecessary
excavation to connect or repair distant valves. Like decoders, it replaces
commodity wire with Hunter ingenuity and provides an efficient alternative to
activating irrigation valves. Once connected, wireless signals are immune to
issues that commonly afflict wired systems, such as wire degradation and
lightning damage.
With the Wireless Valve Link, you can add valves up to 2,000′ (600 m) line-of-
sight, or more with a Repeater, without the need for new valve wiring. Often
described as a wireless decoder system, the Wireless Valve Link provides a
flexible solution for complex landscapes. Now it’s possible to cross concrete
sidewalks and asphalt driveways wirelessly, saving time and money during
installation.
This convenient and innovative wireless valve technology simplifies
installation for landscapes of all sizes by eliminating the need to run costly
field wires or cut into hardscape.
- Works with Hunter ICC2 and HCC Controllers and is compatible with Centralus™ and Hydrawise® Software
- Adds up to 54 valves (+P/MV) up to 2,000′ (600 m) line-of- sight
- License-free LoRa Wireless Radio Technology enables wireless communication directly to the valve box — no copper field wiring required®
- Optional Wireless Solar Repeater can double wireless communication range
- Connects across ple, Wireardscapes and other obstacles without wiring for seamless system expansion within specified ranges
- Combines with conventional ICM or two-wire EZDS Modules for ultimate flexibility
- Provides isolation from lightning or surge events in the field to prevent system damage
- Optional Solar Panel Kit for Wireless Valve Link eliminates the need to replace alkaline batteries in the field
*Wireless range is subject to terrain, foliage, buildings, and other site factors. Consult product documentation before installing.
The LoRa® Mark is a trademark of Semtech Corporation or its subsidiaries.
You will need:
- Free Bluetooth® enabled Hunter WVL App, which is required to perform installation or service. Download it from the Apple or Google Play store below.
- Wireless Valve Output Module installed in Hunter ICC2 or HCC Controller
- 9 V DC batteries (2 per valve recommended)
- 1½” (40 mm) hole saw, included with Wireless Valve Output Module
- Irrigation-grade waterproof connectors
- Permanent marker
- Cordless drill driver and/or jigsaw
https://apps.apple.com/us/app/hunter-wvom/id1543810166| https://play.google.com/store/apps/details?id=com.hunter.WVOM&hl=en_US&gl=US
The Bluetooth word mark and logos are registered trademarks owned by Bluetooth
SIG Inc.
and any use of such marks by Hunter Industries is under license. Apple, the
Apple logo, and iPhone are trademarks of Apple Inc., registered in the U.S.
and other countries. Google, the Google logo, Android, and Google Play are
trademarks of Google LLC.
Spare Plastic Parts Kit – 10046600SP
Spare O-Ring Kit – 10059400SP The Wireless Valve Link (WVL) System is a wireless output option for Hunter ICC2 and HCC Controllers. The WVL requires installation of a domestic Hunter Wireless Valve Output Module (WVOM) or its international counterpart (WVOM-E) in a controller output module slot.
- Verify that the WVOM is installed in the controller.
- Make sure the Hunter WVP App is installed on your smartphone.
- Prepare remote access to the controller using one of the following options:
• A Hunter ROAM or ROAM XL Remote
• Centralus™ Software with mobile access
• Hydrawise® Software with mobile access
The WVL has two buttons and two LED lights in the battery compartment. These can perform the following functions, in order of importance. Station Assignment and Comm Check require the installation of a WVOM in the controller.
Feature | Function | Button/Process |
---|---|---|
1 | Station Assignment (REQUIRED) | Assigns controller station numbers to |
individual output links | Press and hold right button for 2 seconds. | |
2 | Si te Sur vey/ Comm Check | Checks radio coverage at proposed installation |
location | Press left button 3 times. | |
3 | Manual Solenoid Test | Tests solenoid connections and |
operation directly from the WVL | Press and hold Manual start button. |
Press to advance.
4| Factory Reset| Erases all programming and assignments| Press right button.
Insert battery. Hold button 5 seconds.
Station Assignment
Bring the WVL to be programmed near the controller location (before installing
in the valve box). This insures solid communications before moving to the
field location.
Unscrew the battery cover retaining ring. Remove the waterproof cap to reveal
the battery compartment.
Install the first battery. You will need to access the right button for
station assignment, so installing the first battery on the left is recommended
to allow easier access to the button.
Press and hold the right button for approximately 2 seconds.
The right LED should turn yellow/green, indicating that the WVL is in
Assignment Mode.
Within 5 minutes, use the Hunter WVL App to add a new station, and allow it
to scan for stations while inAssignment Mode.
Note: Address one module at a time to avoid duplicate addresses or
confusion. After 5 minutes, the WVL will exit the Assignment Mode.
*Duplicate addresses should not be used in the WVL System!
Procedure
- Place the WVL in Assignment Mode (press and hold right gear button for 2 seconds until right LED is yellow).
- Open app, scan and connect to the controller. When connected, the screen will show a list of any WVLs already connected.
- Press (+) to add a WVL, then press the Scan button. The controller will scan for a WVL that is currently in Assignment Mode and display the station numbering options in the app.
- Use the app to select the controller station numbers to assign to the WVL. Click Done for each station after it’s assigned.
- Once the WVL stations are assigned, press the Save button. The controller (via the WVOM) will transmit to the WVL to complete the assignment. The app shows if the save was successful. The Assignment (right) light in the WVL will also flash yellow several times when the assignment is successful.
- After a successful save, install the second 9 V DC battery to improve seasonal battery life (recommended).
- Take the WVL to the field location.
- Install and connect the WVL outputs to Hunter DC-Latching Solenoids. Observe red/black wire polarity.
Status Check
Check the status of any WVL with at least one battery installed.
Press and release the Assignment button once. Do not hold the button down.
The Assignment light will show green if stations have been assigned and red if
not. The left (Manual) light will show battery status: green if battery is
good and red if it needs replacement.
Site Survey/Comm Check
You can verify radio coverage at the proposed installation/valve box site
prior to installation. Move the programmed controller to the valve box
location, and position it as closely to the final installation as possible.
With the battery compartment open, install at least one battery.
Press the left (Manual) button three times. The LED will blink amber every 2
seconds to show it’s listening for the WVOM signal.
Send a manual station start command to any WVL in the system:
- from the controller panel with a helper
- with a Hunter ROAM or ROAM XL Remote
- from a smartphone via central if that is an option
The LED will turn green if it hears the LoRa radio commands from the WVOM.
This indicates a probable successful location.
If it does not turn green within a few seconds after the WVOM has sent a
command, the signal was not heard.
a. If the command was sent to the WVL being tested, the LED will turn red.
b. If the light does not verify communication, you must improve the signal
(elevate controller antenna or add a Repeater), or the location may not work
reliably.
Installation
Complete the above steps first, including station assignment.
Then proceed to install and connect the WVL in the valve box.
The WVL may be installed in its own valve box, next to the valves it will
operate. It can also be installed in the same box as the valves.
Plan ahead to allow sufficient clearance in the valve box before drilling.
Verify that the WVL assembly will fit in the valve box area without
interfering with the valve or other devices in the box Final installation
requires a minimum 4¼” (11 cm) diameter and 6¼” (16 cm) vertical clearance
below the valve box lid.
Determine the center point for the WVL, and drill or use the 1½” (40 mm) hole
saw (supplied with each WVOM) into the valve box lid on the center of the WVL
location.
Note: We recommended drilling to drill upward from the underside of the
valve box lid to avoid any reinforcement ribs.
Additional trimming or modifications may be required, depending on the lid
material and design. For plastic or fiberglass lids, a handheld jigsaw can
remove internal ribs that a hole saw cannot. Insert the WVL threaded column up
through the hole. Screw on the antenna cap above the valve box lid.
Use the threaded nut to tighten the connection to the underside of the valve
box lid. Connect the station output wires to the Hunter DC-Latching Solenoids
(458200) in the valve box.
Observe wire color-coding for these solenoids (458200): black to black, red to
red. Use the black as a common wire for multistation WVLs to combine all black
wires into a single splice.
This system will not operate with AC Solenoids.
Use irrigation-grade, waterproof connectors for wire splices.
Manual Solenoid Test
Test connected solenoid operation with the local Manual start button in the
battery compartment. Press and hold the Manual start button (left) to start
the first station (blue LED will light and solenoid will click if attached).
Press again to advance to the next station (If it’s a multi-station
controller).
On multi-station WVLs, the blue light will blink rapidly to show which station
output is active.
After the last station starts, press the button one more time to stop all test
irrigation. The test function will stop after 1 minute if it does not receive
further commands.
Push the battery cap back on firmly, and hand tighten the retaining ring to
complete the installation. Make sure the large O-rings remain in place to seal
the enclosure.
Replace valve box lid with the installed antenna, and verify proper operation
with a controller station start.
Factory Reset
Factory Reset is used to clear all programming out of a WVL controller,
including station assignment, Site ID, and Channel ID.
Procedure:
- Remove ALL batteries from the WVL.
- Press and hold the right Assignment button.
- Continue to hold the button, and insert one battery. Continue holding the Assignment button for at least 5 seconds until both LED lights turn red.
- Release the Assignment button immediately. The WVL will be completely reset.
• If the reset was successful, both LEDs will turn green momentarily.
• If the reset was not successful, the LEDs will blink red several times.
Use the app and assignment functions above to add the WVL back into the system, including station assignment.
Replacing a Wireless Valve Output Module
The Recover Database feature is used when a WVOM must be replaced for service reasons or is exchanged with another device.
- The new WVOM must be re-linked to all the WVLs in the field to operate.
- Connect with the app to the new WVOM.
- Install the new WVOM, connect with the app, and choose the Recover Database feature.
- The app will prompt you to enter the serial number of a known device (either a WVL or a Repeater) within the system.
- The WVOM will use this known-good valid serial number to search for that device. The WVOM will then attempt to reach all operational WVLs or a Repeater within range. This can take up to 30 minutes.
- When the process is complete, a notification will appear. If all WVLs were found, the WVOM will be ready to irrigate again without further field addressing.
Troubleshooting
In most cases, troubleshooting is best done with the Hunter WVL App open on a smartphone.
Problem | Causes | Solution |
---|---|---|
WVL not watering | Dead batteries. WVL not addressedImproper solenoid or | |
solenoid disconnected. WVL out of communication range. | Use manual test |
function, replace batteries. Verify WVL address (start
from controller). Use manual test function, check solenoid wiring including
polarity (red and black). Improve radio communications.
Multiple stations turn on| Possible duplicate addresses in WVLs| Stop all
irrigation, then start one of the stations. If multiple stations start, change
the address in one of the WVLs.
Controller beeping| No response from WVL. Low battery warning from WVL.| Use
the Hunter WVL App to read which condition is being reported.
Replace batteries and/or improve communications, as indicated.
Controller Err display (usually together with beeping)| No response from WVL.
Low battery warning from WVL. Possible failure on another output module.| Use
the Hunter WVL App to read which condition is being reported.
Replace batteries, improve communications, as indicated. Troubleshoot other
output modules.
Station turns on for 1 second, then shuts off| WVL is wired to AC Solenoid
(not compatible)| Replace the solenoid with the required DC-Latching Solenoid
(Hunter model 458200). Red wires to red, black to black.
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class
B digital device pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, you are encouraged to try to correct the interference by taking one or
more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that of which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Changes or modifications not expressly approved by Hunter Industries could
void the user’s authority to operate this device. If necessary, consult a
representative of Hunter Industries Inc. or an experienced radio/television
technician for additional suggestions.
This equipment complies with FCC radiation exposure limits set forth for an
uncontrolled environment. In order to avoid the possibility of exceeding the
FCC radio frequency exposure limits, human proximity to the antenna shall not
be less than 7.9″ (20 cm) during normal operation.
Contains Transmitter Module FCC ID: 3UWVL
ISED
IC: 2772A-WVL
This device contains licence-exempt transmitter(s)/receiver(s) that comply
with Innovation, Science and Economic Development Canada’s licence-exempt
RSS(s).
Operation is subject to the following two conditions:
- This device may not cause interference.
- This device must accept any interference, including interference that may cause undesired operation of the device.
RadiationExposure Statement:
This equipment complies with ISED radiation exposure limits set forth for an
uncontrolled environment. This equipment should be installed and operated with
greater than 20 cm between the radiator and your body.
CE
Hereby, Hunter Industries declares that the radio equipment type WVL-E-100,
WVL-E-200, and WVL-E-400 are in compliance with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the
following internet address: http://subsite.hunterindustries.com/compliance
Frequency Band (MHz): 434.040 – 434.790
Max Output Power (dBm): 6.139 Helping our customers succeed is what drives us.
While our passion for innovation and engineering is built into everything we
do, it is our commitment to exceptional support that we hope will keep you in
the Hunter family of customers for years to come.
Denise Mullikin, President,
Landscape Irrigation and Outdoor Lighting
HUNTER INDUSTRIES | Built on Innovation® 1940 Diamond Street, San Marcos, CA 92078 USA hunterindustries.com
© 2024 Hunter Industries Inc. Hunter, the Hunter logo, and other marks are
trademarks of Hunter Industries Inc., registered
in the U.S. and certain other countries.
RC-184 EN OM 1/24
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>