TECH CONTROLLERS EU-MW-1-230 Executive Module User Manual

August 16, 2024
TECH CONTROLLERS

TECH CONTROLLERS EU-MW-1-230 Executive Module

Specifications

  • Supply voltage: 100-240V / 50-60Hz
  • Operating temperature: 5°C – 50°C
  • Resistive load: < 10 A
  • Maximum power consumption: < 1 W
  • Operating frequency: 868 MHz
  • Maximum transmitting power: < 25 mW

Product Usage Instructions

  1. Safety
    Ensure the controller is properly mounted and clean if dusty or dirty. Any changes to the merchandise described in the manual after March 26th, 2020 are possible. The manufacturer reserves the right to introduce structural changes. Note that illustrations may include additional equipment and colours may vary due to print technology.

  2. Device Description
    MW-1 is a wireless device that switches on/off the potential-free contact upon receiving a message from the main controller. It can control devices like boilers, pumps, or valve actuators depending on the main controller.

  3. Installation
    The controller should be installed by a qualified person to prevent fatal electric shock. Ensure power supply is switched off before working on the controller to avoid accidents. Incorrect wire connections may damage the module.

  4. How to Use the Device

  5. Manual Mode
    After 15 minutes of no interaction, the controller switches from manual mode to automatic mode.

  6. Registration
    To register the first device, press and hold the Manual mode button for 5 seconds. The registration process can be cancelled by pressing the same button.

  7. Advanced Registration
    The MW-1/230 module can work with up to 4 devices simultaneously. At least one device must send a signal to activate the contact.

  8. Restore Factory Settings
    To enter factory settings mode, follow the instructions provided in the manual. Pressing the Manual mode button can cancel this action.

  9. Technical Data
    Refer to the specifications section above for detailed technical data of the product.

  10. Alarms
    In MW-1/230, interval communication occurs every 4 minutes. If there is no communication with the main controller, the heating device contact will be disabled after 15 minutes.

SAFETY

Before using the device for the first time the user should read the following regulations carefully. Not obeying the rules included in this manual may lead to personal injuries or controller damage. The user’s manual should be stored in a safe place for further reference. In order to avoid accidents and errors it should be ensured that every person using the device has familiarized themselves with the principle of operation as well as security functions of the controller. If the device is to be sold or put in a different place, make sure that the user’s manual is there with the device so that any potential user has access to essential information about the device.

The manufacturer does not accept responsibility for any injuries or damage resulting from negligence; therefore, users are obliged to take the necessary safety measures listed in this manual to protect their lives and property.

WARNING

  • High voltage! Make sure the regulator is disconnected from the mains before performing any activities involving the power supply (plugging cables, installing the device etc.).
  • The device should be installed by a qualified electrician.
  • The regulator should not be operated by children.

NOTE

  • The device may be damaged if struck by a lightning. Make sure the plug is disconnected from the power supply during storm.
  • Any use other than specified by the manufacturer is forbidden.
  • Before and during the heating season, the controller should be checked for condition of its cables. The user should also check if the controller is properly mounted and clean it if dusty or dirty.

Changes in the merchandise described in the manual may have been introduced subsequent to its completion on March 26th 2020. The manufacturer retains the right to introduce changes to the structure. The illustrations may include additional equipment. Print technology may result in differences in colours shown.

We are committed to protecting the environment. Manufacturing electronic devices imposes an obligation of providing for environmentally safe disposal of used electronic components and devices. Hence, we have been entered into a register kept by the Inspection For Environmental Protection. The crossed-out bin symbol on a product means that the product may not be disposed of to household waste containers. Recycling of wastes helps to protect the environment. The user is obliged to transfer their used equipment to a collection point where all electric and electronic components will be recycled.

DEVICE DESCRIPTION

MW-1 is a wireless device the task of which is to switch on/off the potential- free contact when receives the message from the main controller. Depending on the main controller, the MW-1 module can e.g., switch on the boiler, pump or valve actuators.

Controller features:

  • Wireless communication
  • Possibility of activating manual mode
  • Wireless communication with 4 devices at the same time

INSTALLATION

The controller should be installed by a qualified person.

WARNING

  • Risk of fatal electric shock from touching live connections. Before working on the controller switch off the power supply and prevent it from being accidentally switched on.
  • Incorrect connection of wires may lead to the module damage!

HOW TO USE THE DEVICE

  1. Control light informing that the device is ON
  2. Wireless communication
  3. Manual mode ON
  4. Stan załączenia styku
  5. Manual mode or cancel current operation
  6. Pairing button

MANUAL MODE

  • In order to activate manual mode, press Manual mode button (no. 5) – the control light will go on (no. 3).
  • In order to enable/disable the radiator or other device connected to MW-1/230, press the Pairing button once (no. 6).
  • In order to deactivate manual mode, press Manual mode (no. 5)

NOTE
In the event of no interaction, after 15 minutes the controller switches from manual mode to automatic mode.

REGISTRATION
In order to register the first device, you should:

  • press Pairing button on MW-1/230
  • go to the main controller menu and select Pairing (Registration) option

NOTE: Once you have selected pairing on MW-1/230, it is necessary to activate pairing option in the main controller within 2 minutes. When this time is over, any pairing attempt will fail.

If:

  • all control lights are flashing simultaneously = the registration has been successful.
  • the control lights are flashing one after another from one side to the other = MW-1/230 module has not received the signal from the main controller.
  • all control lights light up continuously = the registration attempt failed.

NOTE
The registration process may be cancelled at any time by pressing and holding Manual mode button for 5 seconds.

ADVANCED REGISTRATION
MW-1/230 module may cooperate with 4 devices at the same time. In order for the contact to be activated, at least one device must send a signal to MW-1/230 module.

In order to register devices 2,3 and 4, you should:

  • enter device selection mode by pressing and holding Pairing button for 10 seconds – one control light is flashing.
  • use Manual mode button to select the device which is to be registered (press twice to select device no. 2, three times to select device no. 3, four times to select device no. 4).
  • once the device has been selected, press Pairing button.

If:

  • all control lights are flashing simultaneously = the registration has been successful.
  • the control lights are flashing one after another from one side to the other = MW-1/230 module has not received the signal from the main controller.
  • all control lights light up continuously = the registration attempt failed.

RESTORE FACTORY SETTINGS
In order to enter factory settings mode, you should:

  • Press and hold Manual mode for 10 seconds – the two outermost control lights start flashing.
  • Press Pairing button – all control lights are flashing.

NOTE
In order to cancel restoring the factory settings, press Manual mode button.

TECHNICAL DATA

Specification Value
Supply voltage 100-240V / 50-60Hz
Operating temperature 5⁰C – 50⁰C
Resistive load < 10 A
Maximum power consumption < 1 W
Operating frequency 868 MHz
Maximum transmitting power < 25 mW

ALARMS
In MW-1/230, interval communication is carried out every 4 minutes. In the event of no communication with the main controller (e.g. due to power failure or limited range), the receiver will automatically disable the heating device contact after 15 minutes.

EU Declaration of Conformity
Hereby, we declare under our sole responsibility that EU-MW-1/230 manufactured by TECH STEROWNIKI II Sp. z o.o., head-quartered in Wieprz Biała Droga 31, 34-122 Wieprz, is compliant with Directive 2014/53/EU of the European Parliament and of the Council of 16 April 2014 on the harmonization of the laws of the Member States relating to the making available on the market of radio equipment, Directive 2009/125/EC establishing a framework for the setting of ecodesign requirements for energy-related products as well as the regulation by the MINISTRY OF ENTREPRENEURSHIP AND TECHNOLOGY of 24 June 2019 amending the regulation concerning the essential requirements as regards the restriction of the use of certain hazardous substances in electrical and electronic equipment, implementing provisions of Directive (EU) 2017/2102 of the European Parliament and of the Council of 15 November 2017 amending Directive 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment (OJ L 305, 21.11.2017, p. 8).

For compliance assessment, harmonized standards were used:

  • PN-EN IEC 60730-2-9 :2019-06 art. 3.1a Safety of use
  • PN-EN 62479:2011 art. 3.1 a Safety of use
  • ETSI EN 301 489-1 V2.2.3 (2019-11) art.3.1b Electromagnetic compatibility
  • ETSI EN 301 489-3 V2.1.1:2019-03 art.3.1 b Electromagnetic compatibility
  • ETSI EN 300 220-2 V3.2.1 (2018-06) art.3.2 Effective and coherent use of radio spectrum
  • ETSI EN 300 220-1 V3.1.1 (2017-02) art.3.2 Effective and coherent use of radio spectrum
  • PN EN IEC 63000:2019-01 RoHS.

Wieprz, 26.03.2020

  • Central headquarters:
    ul. Biata Droga 31, 34-122 Wieprz

  • Service:
    ul. Skotnica 120, 32-652 Bulowice

  • phone : +48 33 875 93 80

  • e-mail: serwis@techsterowniki.pl

www.tech-controllers.com

FAQ

Q: Can I install the MW-1 device myself?
A: It is recommended to have the MW-1 device installed by a qualified person to ensure safety and proper functioning.

Q: How many devices can the MW-1/230 module cooperate with?
A: The MW-1/230 module can cooperate with up to 4 devices at the same time.