FantiniCosmiIndustrie AP20048W Single Room Heat Recovery Ventilation Unit Owner’s Manual
- August 19, 2024
- FantiniCosmiIndustrie
Table of Contents
MECHANICAL VENTILATION
WITH HEAT RECOVERY
ASPIRCOMFORT CLASS 620H WI-FI
SINGLE ROOM HEAT RECOVERY VENTILATION UNIT
- For commercial applications, schools, offices
- Very high recovery efficiency >90%
- Horizontal installation
- Wi-Fi wall control unit (code 1591008 – supplied separately)
ASPIRCOMFORT CLASS is a fan unit complete with heat recovery unit dedicated to
air renewal without wasting energy.
The unit is particularly suitable for single rooms where ducted systems are
not possible.
Thanks to its construction features and components, ASPIRCOMFORT CLASS 620H
WI-FI is able to reach recovery efficiency of more than 90%.
In the winter and summer seasons there is considerable energy recovery of the
renewal air introduced into the room.
FEATURES
- Self-supporting sheet metal frame with polyethylene insulated interior.
- Polypropylene high efficiency cross flow counter current exchanger. Low freezing temperatures and operation down to -25°.
- Brushless forward curved centrifugal fans with electronic motor and modulating control. Very high efficiency and low noise levels.
- ePM1 70% filters with low head loss. Easily removable by removing the lower outer panels.
- Free cooling inside the unit with generous air flow and damper with motorised actuator.
- Management of 3 fan speeds + Auto.
- WI-FI control unit with the possibility of management via App, equipped with sensors for monitoring temperature, relative humidity (RH%), volatile organic compound (VOC) concentration and carbon dioxide (CO2) concentration. Mandatory for operation (supplied separately).
- The unit is equipped with a power cable with Shuko plug.
UNIT ORDERING CODES
Code | Model | Description |
---|---|---|
AP20048W | ASPIRCOMFORT CLASS 620H WI-FI | Heat recovery unit for horizontal |
installation with max. air flow rate of up to
620 m3/h with Wi-Fi control
1591008| | Wi-Fi control unit (to be ordered separately)
UNIT CONFIGURATION
Code | Maximum air flow rate | Installation |
---|---|---|
AP20048W | Up to 620 m3/h | horizontal |
CERTIFICATIONS
The CE marking (on each machine) certifies conformity with the following Community standards:
- Low Voltage Directive 2014/35/EC
- Electromagnetic Compatibility Directive 2014/30/EC
- Ecodesign 2009/125/EC
DIMENSIONS AND FUNCTIONAL SPACES
Width L | mm |
---|---|
Depth D | mm |
Height H | mm |
Diameter DN | 4 03 |
Weight | Ø Kg |
Condensation | Ø |
ACCESSORIES
- 2 connections Ø 250 mm
- Insulated pad
- 2 fixed grids Ø 250 mm for outside wall
- Pre-wired 10 m cable for connecting Wi-Fi control
TECHNICAL FEATURES
Fans
Type of fans| | Centrifugal blades forward directly coupled electronic motor –
0/10 V signal
---|---|---
Number of fans| No| 2+1
Air flow rate V3/V2/V1| m3/h| 620 / 355 / 165
Useful pressure| Pa| 15
Heat exchanger
Type of exchanger | Countercurrent plates – polypropylene material | |
---|---|---|
Number of exchangers | No | 2 |
Recovery efficiency EN13141-7 | % | 86.1 |
Recovery efficiency EN308 | % | 91.8 |
Filters
Type of filters | Pleated filters |
---|---|
Filtration class | ePM1 70 |
Acoustic data
Sound power Lw transmitted by the structure | dB(A) | 59 |
---|---|---|
Sound pressure at 3 m V1 (low) | dB(A) | 33 |
Sound pressure at 3 m V2 (average) | dB(A) | 36 |
Sound pressure at 3 m V3 (high) | dB(A) | 41 |
Sound pressure at 4 m V1 (low) | dB(A) | 30.5 |
Sound pressure at 4 m V2 (average) | dB(A) | 33.5 |
Sound pressure at 4 m V3 (high) | dB(A) | 38.5 |
(Data according to UNI EN 3741 and UNI EN 3744) |
Electrical Data
Supply voltage | V | 230 / 1 / 50 Hz. |
---|---|---|
Absorbed current | A | 3.5 |
Power consumption | W | 340 |
Protection rating | IP | X0 |
Power consumption V3 with 15Pa pressure and clean filters | W | 165 |
Dimensions
Width | mm | 1040 |
---|---|---|
Depth | mm | 905 |
Height | mm | 405 |
Diameter Connections | mm | 250 |
Condensation discharge | mm | 20 |
ADJUSTMENT (Mandatory)
1591008 – CONTROL UNIT FOR ASPIRCOMFORT CLASS WI-FI
- Smart Touch
- Management of 3 fan speeds + Auto
- WI-FI control unit and App
- On-board sensors for temperature monitoring, relative humidity (RH%), volatile organic compound (VOC) concentration and carbon dioxide (CO2) concentration
- Season setting
- Temperature set point
NOTE: supplied separately.
SPECIFICATIONS
Very high efficiency, decentralised heat recovery fan unit, with compact
dimensions for ceiling installation.
Specific unit for commercial applications, schools, offices.
Tested and classified according to the European Ecodesign Regulation
2009/125/EC
Remote control panel with WIFI and APP, to be purchased separately.
CONSTRUCTION FEATURES
Self-supporting sheet metal frame with polyethylene insulated interior.
Polypropylene very high efficiency cross flow counter current exchanger with
recovery efficiencies of more than 90%.
Brushless forward curved centrifugal fans with electronic motor and modulating
control. Very high efficiency and low noise levels.
ePM1 70% filters with low head loss.
Free cooling inside the unit with generous air flow and damper with motorised
actuator.
Compact dimensions for simplified installation with easily accessible bottom
panel for maintenance and serviceability.
160 mm diameter circular inlets with sealing gasket for easy installation.
Quick filter inspection and double discharge for condensation evacuation with
trap supplied.
ECODESIGN AP20048W ERP DATA
A | Supplier’s name or trademark | Fantini Cosmi |
---|---|---|
B | Model identifier | Aspircomfort Class 620H |
C | Declared type | UVNR |
D | Type of drive installed | Variable speed |
E | Heat recovery system | Recovery |
F | Thermal efficiency of heat recovery | % |
H | Nominal flow rate | M3/s |
I | SPF int | W / (m3/s) |
J | Frontal speed | M/s |
K | External pressure rating (Dps , ext) | Pa |
L | Internal pressure drop (Dps , int) | Pa |
M | Internal pressure drop | Pa |
N | to components outside the ventilation (Dps , int) | % |
O | Fan static efficiency as per | % |
P | Energy classification of filters | F7/F7 |
Q | Position and description of the filter signal | Displayed on the control |
panel
R| Sound power level| Lwa| 59
S| Internet address disassembly instructions|
www.fantinicosmi.it
References
Read User Manual Online (PDF format)