Altronix PT2724 Series Two (2) Channel 365 Day 24 Hr. Timer/Controllers Instructions

June 3, 2024
Altronix

Altronix PT2724 Series Two (2) Channel 365 Day 24 Hr. Timer/Controllers

![Altronix T2724-Series-Two -2)-Channel-365-Day-24Hr.Timer-Controller-PRODUCT

Overview

Altronix PT2724/PT2724E is an extremely versatile two channel 365 Day 24 Hour Timer/Controller designed to support a wide range of applications. Such applications include: Home and Building Automation, Security, Access Control, Lighting Control, etc.
The timer is equipped with two independently controlled form “C” relay contact that provide many latching and/or momentary operations during a program schedule of your choice. The EE-Prom memory allows for programming of unit prior to or during field installation. Events may be set for single or multiple operations on a daily and/or weekly schedule. The block programming feature enables repeating an event on any combination of consecu-tive days. PT2724 will compensate for daylight savings time if desired. It automatically adjusts for leap year and individually selected holiday exceptions can be programmed to override regularly scheduled events.

Specifications

Input:

  • 12 to 24 VAC or VDC operation.

Relay:

  • Two (2) form “C” relay contacts are rated 10A @ 120VAC/28VDC.
  • Standby current: 10mA (relay off), 50mA (relay on).
  • Tandem relay mode allows both channels to activate simultaneously for all events.

Features

  • EE Prom memory protects against loss of programming due to power failure.
  • Accurate crystal controlled clock.
  • Momentary and/or Latching Events.
  • 50 individually programmed daily/weekly events.
  • Block programming capacity can accommodate a total of 350 events per week.
  • 10 programmable Holiday dates per channel.
  • “First man in” option.

Features (cont’d):

  • Standard or Daylight Savings Time settings.
  • Automatic compensation for leap year.

Visual Indicators

  • Alphanumeric LCD display simplifies programming.

Battery Backup

  • Built-in charger for 12VDC sealed lead acid or gel type batteries (Max charge current 100mA).
  • Optional lithium battery backup maintains clock. Order Altronix part # LB2032.

Mechanical

  • PT2724 – Timer module.
    • Board Dimensions (approx.):
    • 5.25” x 3.6” x 1” (133.4mm x 91.4mm x 25.4mm).
  • PT2724E – Timer module in enclosure.
    • Enclosure Dimensions (H x W x D approx.):
    • 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).

Installation Instructions

  1. Mount PT724A/PT724AE/DPT724A in desired location.

  2. Carefully Review:

  3. Basic Operation: (pg. 3)

  4. Terminal Identification: (pg. 3)

  5. Table Push Button Layout and Description: (pg. 4)

  6. Programming Instructions: (pg. 4-7)

  7. Connect 12 to 24 volts AC or DC to terminals marked [+ DC – / ~ AC ~].
    When using DC carefully observe polarity.

  8. Connect 12VDC battery (optional) to terminals marked [+ BAT – / 12VDC].

  9. Insert lithium battery (optional/not included. Order part LB2032) in battery holder (Fig. 1, pg. 3)
    with the + positive side facing up.

  10. Connect devices to be controlled to dry relay outputs marked [NO, C, NC] of either Channel A or Channel B. Note: It is important when connecting DC powered electromechanical devices such as Mag Locks, Electric Strikes, Bells, Relays, etc. to install a catch diode across the pos (+) and neg (–) terminals of
    the device. Connect diode as close to the device as possible with the banded side facing the pos (+) terminal. This will reduce the possibility of interference.

  11. Program clock and desired event schedule (see programming instructions pg. 4-7).

Basic Operation

PT2724 controls two independently operated dry form “C” relays. Relays can be programmed to: turn on (latch), turn off (release latch) or pulse (momentary toggle) at a specified time and day (this is referred to as an event). Events are programmed via the push buttons and LCD display. Events may be programmed to occur on any day of the week at any time. In addition, events may be programmed as a block events that repeat at a specific time on two (2) or more consecutive days (i.e. MO-FR, SU-TH, etc). Multiple combinations of individual and block events may be programmed. Holiday exceptions are individually selected by date and will override all regularly scheduled events.

Output Relay Modes

Mode Status
Relay OFF De-energizes the relay until a relay ON event is detected.
Relay ON Energizes the relay until a relay OFF event is detected.
Disable Used to cancel an existing programmed event.
Pulse Momentarily energizes the relay for a selectable time period of 1 sec.

to 15 secs.

Time is displayed in 24 hr. military format.

Terminal Identification Table

Terminal Legend Function/Description
NO, C, NC, CH A NO, C, NC, CH B Dry Contact outputs used to switch controlled

devices. When these relays are energized (ON) the NC and C terminals are open and the NO and C terminals are closed. When this relay is de-energized (Off) the NC and C terminals are closed and the NO and C terminals are open.
+ DC –

~ AC ~

| AC or DC Input 12 to 24 volt. When using DC carefully observe polarity
+ BAT – 12VDC| 12VDC stand-by battery input (battery leads provided).


FM

| When this terminal is connected to DC neg. (–) the “First Man in” feature is enabled. The relay will remain in its present position until this connection is terminated. At that time the relay will resume normal operation and latest scheduled events will occur.

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-1

Push Button Layout

Push Button Description Table

Push Button Function/Description
SET Scrolling keys for programming. Escaping out of existing programming.
ENTER Accepts selections made to programming.
UP Scrolls through selections.
DOWN Scrolls through selections.

UP and DOWN keys can be used to select data entries. After scrolling to the correct entry, depress ENTER to accept.

SW2 DIP Switch Selects tandem or individual relay operation.
SW3 Slide Switch Selects channel to be programmed.

Programming Instructions

A. Setting Clock/CalendarAltronix T2724-Series-Two -2\)-Channel-365
-Day-24Hr.Timer-Controller-FIG-3

  • Depress ENTER to scroll until flashing cursor appears under DS (daylight savings mode) in display.
  • To change mode depress UP or DWN until ST (standard time mode) will appear in display.
  • Depress ENTER to accept correct selection.
  • Note: The flashing cursor denotes location of data entry selection to be made. If an entry was made in error or requires changing, depress SET to backspace, make the correct selection and depress
  • ENTER to accept data and advance the cursor. To change or program clock/calendar simply repeat the steps above.

B. Setting and Adding Events

  • Select channel A or B by moving slide switch SW3 to appropriate position.
  • Note: Channel cannot be changed in the middle of programming events. To change channels, you must exit programming then change channel switch position then enter program mode again.

Setting Events

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-5

Note: A01 indicates Channel A event 01. When cursor

  • Depress ENTER until the flashing cursor appears under OFF (relay function) position in display.
  • Now select type of event required, by scrolling using the UP and DWN push buttons until either:
  • ON – Relay ON (latching mode), OFF – Relay OFF (latching mode), PL – Relay Pulse ( momentary) appears in display. Depressing ENTER will make selection.

When selecting the pulse mode, PL01 will appear in the display. It is now necessary to assign the length
of time (duration of relay activation). The pulse can range in length from 1 second minimum to 15 seconds maximum and is selected by using UP or DWN push buttons, then depressing ENTER to accept. Note: If pulse duration is not selected, relay output defaults to 1 second.

Next, select individual day of the week and time (military) by scrolling using UP and DWN push buttons and depress ENTER to accept. You may continue to program events by repeating the previous steps or exit programming by depressing SET.

Note: When programming additional events, it is necessary to select the next consecutive event number following the last event program to continue. When it is required to have the same event repeated on two (2) or more consecutive days of the week (Block Programming), the event must be programmed as a block by selecting BK in the day field.

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-7

Note: To program the consecutive days of the week refer to Setting Block Event (weekly repeat) and Daylight Savings Time – section C1 below.

Depress ENTER. If the event is not programmed, the cursor will move to the OFF (relay function) position. If the event is programmed, the cursor will move to the position and the programmed information of the event will be displayed. At this point depress the UP button to step up through the programmed events. When an unprogrammed event is reached, the cursor will move to the OFF (relay function position). At this point refer to setting events or setting holiday events.

C. Setting Block Events (weekly repeat) and Daylight Savings Time
Select channel A or B by moving slide switch SW3 to appropriate position.
Note: Channel cannot be changed in the middle of programming events. To change channelsyou must exit programming then change channel switch position then enter program mode again.

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-8

Block Event Programming
Flashing cursor will appear at the location of the first day of the week desired. Depress UP and DWN to select day. Depress ENTER to confirm selection, then cursor will appear at the location of the last day of the week desired. Depress UP and DWN to select day. Depress ENTER to confirm selection.

  1. Monday through Thursday depress MO followed by TH.
  2. Wednesday through Sunday depress WE followed SU.

Daylight Savings Programming
The cursor will appear under DS (auto clock adjust daylight savings mode) in display. To change mode depress UP or DWN once ST (clock does not adjust standard time mode) will appear in display. Depress ENTER to accept correct selection.
Note: Select DS for areas that observe daylight savings or ST for areas that don’t observe
daylight savings.

D. Setting Holiday Events:

  • These events will occur on programmed Holiday Dates – see Setting Holiday Dates below).
  • Note: When a holiday event is entered, all holidays will follow that event.
  • Select channel A or B by moving slide switch SW3 to appropriate position.
  • Note: Channel cannot be changed in the middle of programming events. To change channels you must exit programming, then change channel switch position then enter program mode again.
  • Find the first unprogrammed event (refer to Adding Events – section B2 page 5).
  • Depress ENTER until the flashing cursor appears under OFF (relay function) position in display.
  • Now select type of operation required, by scrolling using the UP and DWN push buttons until either: ON – Relay ON (latching mode), OFF – Relay OFF (latching mode), PL – Relay Pulse ( momentary) appears in display. Depressing ENTER will make selection.
  • When selecting the pulse mode, PL01 will appear in the display. It is now necessary to assign the length of time (duration of relay activation). The pulse can range in length from 1 second minimum to 15 seconds maximum and is selected by using UP or DWN push buttons, then depressing ENTER to accept. Note: If pulse duration is not selected, relay output defaults to 1 second.
  • Next select HL (holiday) and time (military) by scrolling using UP and DWN push buttons and depress ENTER to accept. Exit programming by depressing SET. If no holiday event has been entered and a holiday date is entered, the unit will stay in its last position when that date comes up.
  • Note: When a holiday event is entered, all holidays will follow that event.

E. Setting Holiday Dates
Select channel A or B by moving slide switch SW3 to appropriate position.

Note: Channel cannot be changed in the middle of programming events. To change channels you must exit programming, then change channel switch position then enter program mode again.
It is now necessary to assign these holiday events specific calendar dates which they are to occur on.

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-10

Enter the holiday date, day of week and year by depressing UP and DWN to make the selection then depress ENTER to accept.
Note: Holiday events will override all regularly programmed events that occur on a particular holiday date.

F. Delete/Disable Events or Edit Events
Select channel A or B by moving slide switch SW3 to appropriate position.
Note: Channel cannot be changed in the middle of programming events. To change channels you must exit programming, then change channel switch position then enter program mode again. Previously programmed regularly scheduled and/or holiday events may be deleted/disabled without having to erase all events.

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-9Altronix T2724-Series-
Two -2\)-Channel-365-Day-24Hr.Timer-Controller-FIG-10

Now scroll using UP and DWN push buttons to the event you wish to delete, depress ENTER to move flashing cursor under relay option, then depress UP and DWN. Push buttons until DIS is displayed, depress ENTER to confirm.

G. Delete All Events
This will delete all previously programmed events.
Depressing UP push button will now clear all events previously programmed. If you wish to escape from this selection depress any of the other push buttons: SET, ENTER and DOWN.

H. Tandem Relay Mode
To operate in the Tandem Relay Mode, turn switch SW2 ON. This mode setting will allow events programmed for Channel A and Channel B to operate both relays simultaneously (1 DPDT relay output). This setting doubles the amount of programmable events.
Note: When using the Tandem Relay mode, sequential On/Off or Off/On events must be programmed in the same channel. (If there is a Channel Program conflict, such as CH A is set to ON and Channel B is set to OFF. The ON command will override the OFF and both relays will remain ON.

Customer Event Log

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-12

PT2724 Board Dimensions (L x W x H approximate): 5.25” x 3.6” x 1” (133.4mm x 91.4mm x 25.4mm).

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-13

PT2724E Enclosure Dimensions (H x W x D approximate): 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm) 7.25” (184.2mm)

Altronix T2724-Series-Two -2\)-Channel-365-Day-24Hr.Timer-Controller-
FIG-14

Altronix is not responsible for any typographical errors.140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty IIPT2724 I22U