HITACHI RAS Series Inverter Driven Air Conditioners Installation Guide
- August 9, 2024
- Hitachi
Table of Contents
RAS Series Inverter Driven Air Conditioners
“`html
Specifications:
- Models: RAS-080CNCCLW to RAS-300CNCCLW
- Production Location: Wuhu, China
- Refrigerant Type: R410A
- Voltage: 380-415 V 50 Hz / 380 V 60 Hz
- Cooling Capacity: 8HP to 30HP
Product Usage Instructions:
Installation:
1. Carefully read the installation & maintenance manual
before proceeding with the installation.
2. Ensure the air conditioner is placed within the specified
temperature range for optimal performance.
3. Verify the model number and electrical characteristics match
the purchase order.
4. If there are any issues during installation, contact your
local agent or contractor for assistance.
Maintenance:
1. Regularly inspect the outdoor unit for any damages or debris
that may obstruct airflow.
2. Clean the air filters periodically to ensure efficient
operation.
3. Schedule professional maintenance checks at least once a year
to keep the unit in optimal condition.
Operation:
1. Use the air conditioner within the specified temperature
range for cooling operation.
2. Avoid placing objects near the air outlet to prevent damage
due to condensation.
3. Pay attention to the direction of the outlet air for proper
airflow.
FAQ:
Q: What should I do if I notice a decrease in cooling
performance?
A: Check and clean the air filters, ensure the outdoor unit is
free from obstructions, and verify the temperature settings are
correct.
Q: Can I perform maintenance tasks myself?
A: While basic tasks like cleaning filters can be done by the
user, it is recommended to schedule professional maintenance checks
annually to ensure proper functioning of the unit.
“`
INSTALLATION & MAINTENANCE MANUAL
INVERTER-DRIVEN
AIR CONDITIONERS Max SERIES
OUTDOOR UNITS
MODELS
(Standard Type)
RAS-080CNCCLW TO RAS-300CNCCLW
EN INSTALLATION & MAINTENANCE MANUAL Original Instructions
Scan the code to get the electronic manual.
A16381N3TL
Models
Applicable Models
HP
Cooling Only
HP
Cooling Only
8HP RAS-080CNCCLW 20HP RAS-200CNCCLW
10HP RAS-100CNCCLW 22HP RAS-220CNCCLW
12HP RAS-120CNCCLW 24HP RAS-240CNCCLW
14HP RAS-140CNCCLW 26HP RAS-260CNCCLW
16HP RAS-160CNCCLW 28HP RAS-280CNCCLW
18HP RAS-180CNCCLW 30HP RAS-300CNCCLW
Unit Nomenclature RAS – 080 C N C C L W
Nomenclature Description
W
Production Location: Wuhu, China
L
L: 3N~ 380-415 V 50 Hz / 4 Wires 3N~ 380 V 60 Hz / 4 Wires
C
C: “C” Series (Standard Type)
C 3rd Generation
N Refrigerant Type: R410A
C
C: Cooling Only System (2 Pipes System)
080
System Capacity (e.g., 080 = 8 HP, H20 =120 HP)
RAS
Unit Type RAS: Outdoor Unit
Working Range
This air conditioner has been designed for a specific temperature range. For
optimum performance and a long life, operate this unit within the range limits
listed in the table.
Outdoor Air Inlet Temperature (°C DB) Continuous Operation Range Pull Down Operation Range
< Cooling Operation > Intermittent Range 55 52 50 48 45 40 35 30 25 20 15 10 0 -10 15 20 23 25 Indoor Air Inlet Temperature (°C WB)Temperature
DB: Dry Bulb WB: Wet Bulb
Cooling Operation
Indoor Air Inlet 15 to 23°C WB Temperature
Outdoor
10 to
Air Inlet Temperature
48 (52 *1) °C DB
i
Models
*1. The maximum operating temperature for cooling operation of the Cooling Only type is 48 °C (52 °C). The temperatures in parenthesis indicate the temporary maximum operating temperatures.
· Temporary high ambient operation is allowed depending on the installation
condition.
· Do not install the unit where the ambient temperature is always high.
· If an air outlet duct is attached and set in high static mode, or an
optional hood such as a snow protection hood is attached, the outdoor unit
operational temperature should not exceed 48 °C.
· When the outdoor air inlet temperature is more than 48 °C during cooling
operation, “intermittent operation” may be activated to prevent the unit from
overloading. If the outdoor unit operates for a long time at a temperature
higher than 52 °C protection control may be activated.
· If installing units in a place where the ambient temperature continuously
exceeds 48 °C, the combination ratio must be lower than 130%.
· The cooling capacity deteriorates at a high ambient temperature. Select a
larger capacity outdoor unit than an outdoor unit which capacity is larger
than the compatible building heat load.
· When the ambient temperature is more than 48 °C during cooling operation,
the noise level to increase from 5dBA to 7dBA, due to an increase in fan
rotation speed.
NOTES:
· The appropriate amount (100%) of refrigerant must be charged. Excessive
charging of refrigerant is forbidden.
· Units should not be installed in areas where they will be affected by direct
sunlight or where a short circuit of the discharged air may occur. Installing
the units in an inappropriate place may active the protection control and the
alarm system. The life span of the products and part may be considerably
shortened.
· Periodic maintenance (1/certain month) must be applied to the heat exchanger
fin to avoid adhesion of dirt and clogging of sand to the outdoor unit heat
exchanger.
· When the cooling load is low and the outdoor air inlet temperature is 10 °C
DB or lower, “thermo-OFF” may be activated to prevent frost formation on the
indoor unit heat exchanger. Depending on the operating condition, the outlet
air temperature of the indoor unit
IMPORTANT NOTICE
may be excessively low. Pay attention to the direction of the outlet air. Do
not place objects near the air outlet and under the indoor unit as they may be
damaged by condensates that may form if the humidity or the latent heat load
is continuously high.
· The operational range differs when connected to All Fresh Air Unit,
Econofresh and other special indoor units. Refer to the Technical Catalog for
more details.
IMPORTANT NOTICE
· Hitachi-Johnson Controls Air Conditioning pursues a policy of continuing
improvement in design and performance in its products. As such, Hitachi-
Johnson Controls Air Conditioning reserves the right to make changes at any
time without prior notice.
· Hitachi-Johnson Controls Air Conditioning cannot anticipate every possible
circumstance that might involve a potential hazard.
· This manual provides common descriptions, basic and advanced information to
maintain and service this air conditioner which you operate as well for other
models.
· The installer and system specialist must safeguard against refrigerant
leakage in accordance with local codes. The following standards may be
applicable, if local regulations are not available. International Organization
for Standardization: (ISO 5149 or European Standard, EN 378). No part of this
manual may be reproduced in any way without the expressed written consent of
HitachiJohnson Controls Air Conditioning.
· This air conditioner is designed for standard air conditioning applications
only. Do NOT use this unit for anything other than the purposes for which it
was intended.
· The unit is a partial unit air conditioner, complying with partial unit
requirements of the International Standard, and must only be connected to
other units that have been confirmed as complying with corresponding partial
unit requirements of the International Standard.
· This manual is essential for product operation and should remain with the
air conditioning equipment.
· If you have questions, please contact your distributor or contractor.
Introduction
This manual focuses on the outdoor/indoor unit. Read this manual carefully
before installation. Also, refer to other manuals where necessary. Forward
this manual and the warranty to the next team of installers and then users.
Ask them to keep this manual with the air conditioner for future reference.
(Refrigerant Piping Work) (Electrical Wiring Work) (Ref. Charge Work) (Test
Run) (User)
· With regard to the installation (including the mechanical installation,
refrigerant system installation and electrical wiring connection), please read
the following pages carefully. Installation Work …Chapter 4 Refrigerant Piping
Work…Chapter 5 Electrical Wiring… Chapter 6
· For wiring between the indoor unit and the outdoor unit, refer to the
Installation and Maintenance Manual for the outdoor unit.
· For the optional decorative panel, refer to the Installation and Maintenance
Manual for the optional decorative panel.(Only for 1-Way, 2-Way, and 4-Way
Cassette Types)
· For each optional controller, refer to the Installation and Maintenance
Manual and the Operation Manual.
· For each optional part, refer to the Installation and Maintenance Manual.
· For the central controller, refer to the Installation and Maintenance Manual
and the Operation Manual.
Product Inspection upon Arrival
1. Upon receiving this product, inspect it for any damages incurred in
transit. Claims for damage, either apparent or concealed, should be filed
immediately with the shipping company.
2. Check the model number, electrical characteristics (power supply, voltage,
and frequency rating), and accessories to determine if they are correct with
the purchase order.
3. Please contact your local agent or contractor if any issues involving
installation, performance, or maintenance arise. Liability does not cover
defects originating from unauthorized modifications performed by a customer
without the written consent of Hitachi-Johnson Controls Air Conditioning.
Performing any mechanical alterations on this product without the consent of
the manufacturer will render your warranty null and void.
ii
TABLE OF CONTENTS
Models ……………………………………………………………………………………………………………………………. i IMPORTANT NOTICE
………………………………………………………………………………………………………..ii 1. Safety
Summary…………………………………………………………………………………………………………..1 2. Before
Installation………………………………………………………………………………………………………..8
2.1 About This Product…………………………………………………………………………………………………..8 2.2 Line-Up of
Outdoor Units………………………………………………………………………………………..10 2.3 Combination of Indoor
Unit and Outdoor Unit………………………………………………………….12 2.4 Piping Connection Kit
(Optional) between Outdoor Units………………………………………….13 2.5 Multi-Kit (Optional)
between Indoor Unit and Outdoor Unit ………………………………………14 2.6 Factory-Supplied
Accessories ………………………………………………………………………………….14 3. Selection of Installation
Location ………………………………………………………………………………..16 3.1 Installation Location
………………………………………………………………………………………………16 3.2 Service Space and Installation Area
…………………………………………………………………………16 4. Installation
Work………………………………………………………………………………………………………..19 4.1 Transportation and
Handling ………………………………………………………………………………….19 4.2 Outdoor Unit Installation
……………………………………………………………………………………….21 5. Refrigerant Piping
Work………………………………………………………………………………………………24 5.1 Piping
Materials……………………………………………………………………………………………………..24 5.2 Flaring and Joint
……………………………………………………………………………………………………26 5.3 Caution about Outdoor Unit
Installation ………………………………………………………………….27 5.4 Piping Connection Work
…………………………………………………………………………………………28 5.5 Piping Work between Outdoor Units
………………………………………………………………………………………….. 34 5.6 Piping Size, Piping Connection and
Multi-Kit Selection ……………………………………………..42 5.7 Piping Branch
Restrictions………………………………………………………………………………………45 5.8 Restrictions on Height
Difference between Indoor Units ……………………………………………46 6. Electrical Wiring
…………………………………………………………………………………………………………47 6.1 General
Check………………………………………………………………………………………………………..47 6.2 Electrical Wiring for
Outdoor Unit………………………………………………………………………………………48 6.3 Electrical Wiring
Connection……………………………………………………………………………………49 6.4 Electrical Wiring Connection
of Indoor Unit and Outdoor Unit …………………………………..52 6.5 PSW and DIP Switch
Setting for Outdoor Unit …………………………………………………………..54 7. Air-Tight Test and
Additional Refrigerant Charge …………………………………………………………..58 7.1 Air-Tight
Test………………………………………………………………………………………………………….58 7.2
Vacuuming…………………………………………………………………………………………………………….59 7.3 Additional
Refrigerant Charge Calculation………………………………………………………………..60 7.4 Charging Work
……………………………………………………………………………………………………….61 8. Test
Run…………………………………………………………………………………………………………………….63 8.1 Before Test
Run………………………………………………………………………………………………………63 8.2 Test Run
………………………………………………………………………………………………………………..64 9. Safety and Control Device
Setting………………………………………………………………………………..70 iii
1. Safety Summary
Indicates a hazardous
DANGER situation which, if not
avoided, will result in death
or serious injury.
Indicates a hazardous
WARNING
situation which, if not avoided,could result in death
or serious injury.
Is used with the safety
alert symbol, indicates a
CAUTION hazardous situation which, if
not avoided, could result in
minor or moderate injury.
Is used to address practices
NOTICE not related to personal
injury.
NOTE
NOTE
Indicates useful information for operation and/or maintenance.
General Precautions
WARNING
To reduce the risk of serious injury or death, read these instructions
thoroughly and follow all warnings or cautions included in all manuals that
accompany the product. Incorrect installation could cause leaks, electric
shock, fire or explosion.
· Hitachi-Johnson Controls Air Conditioning will not assume any liability for
injuries or damage caused by not following steps outlined or described in this
manual. Unauthorized modifications to Hitachi-Johnson Controls Air
Conditioning products are prohibited as they:
May create hazards that could result in death, serious injury or equipment
damage;
Will void product warranties; May invalidate product regulatory
certifications.
· This system should be installed by personnel certified by Hitachi-Johnson
Controls Air Conditioning. Professional personnel must follow all local and
national codes. Where Seismic Performance requirements are specified, take
appropriate measures during installation to guard against possible damage or
injury that might occur in an earthquake due to incorrect installation or a
unit falling.
· This air conditioning system is intended to be used by expert or trained
users in shops, in light industry and on farms, or for commercial
1. Safety Summary
use by lay persons.
· Use appropriate Personal Protective Equipment (PPE), such as gloves and
protective goggles and, where appropriate, have a gas mask nearby. Also use
electrical protection equipment and tools suited for electrical operation
purposes. Keep a quenching cloth and a fire extinguisher nearby during
brazing. Use care in handling, rigging, and setting bulky equipment.
· Before servicing, turn off the power supply and use accepted lockout and tag
out procedures at all main switches. Failure to do so can result in damage to
internal components with severe or fatal electrical shock.
· This unit is a pressurized system. Never loosen threaded joints while the
system is under pressure and never open pressurized system parts.
· When the air conditioner needs repair or is transported to a new location,
contact your distributor or contractor. If the repair and the installation are
not completed, electric shock or fire can result.
· When transporting, be careful when picking up, moving and mounting these
units. Although the unit may be packed using plastic straps, do NOT use them
for transporting the unit from one location to another. Do NOT stand on or put
any material on the unit. Get a partner to help, and bend with your knees when
lifting to reduce strain on your back. Sharp edges or thin aluminum fins on
the air conditioner can cut fingers, so wear protective gloves.
· Use only recommended/standardized replacement parts provided by
HitachiJohnson Controls Air Conditioning.
· This air conditioning system can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental capabilities or
lack of experience and knowledge if they have been given supervision or
instruction concerning use of the air conditioning system in a safe way and
understand the hazards involved. Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children without
supervision.
· Do NOT attempt to “clean” indoor unit components with liquid or powdered
cleaning agents during maintenance. Electric shock, sparks, flame, and serious
or fatal injury can occur.
· When the flat panel is opened (closed) or the
1
1. Safety Summary
air filter is attached (removed), hold them firmly. If not, it may cause
falling or injury. (only for wall mounted type)
· Do NOT insert fingers or objects into air inlet/ outlet. Injury can result
from rotating fan blades or energized electrical components.
· Do NOT touch the main circuit board or electronic components in the
controller or remote devices. Make sure that dust and/or moisture does not
accumulate on the circuit board.
· Do NOT touch the wired controller with wet hands to prevent damage to the
wired controller or an electrical shock.
· If you smell anything burning, shut down the unit and turn off the power at
the main power supply. Contact the fire department and your installer or
electrical contractor.
· Do not apply hair spray, insecticides, lacquers, or other pressurized
substances within 1 m of any air conditioner. The substances can react with
energized electrical contractor.
· For safe operation, the air conditioning system shall be inspected and
maintained every 6 months.
CAUTION
To reduce the risk of minor or moderate injury, the following general
precautions must be followed.
· About Wireless Controller
Pay attention to the following to use the batteries correctly. If not, it may
cause liquid spill or burst.
· Never use new and used batteries together.
· Never use the different types of batteries (for example manganese battery
and alkaline battery) together.
· When the wireless controller is not used over a prolonged period of time
(more than 2 or 3 months), remove the batteries from the wireless controller.
After removing the old batteries, wait five or more seconds before inserting
the new ones
NOTICE
Take the following precautions to reduce the risk of property damage.
· Each model number and all matching model
2
numbers within a system must have the same version of software. Follow these
steps to verify that your product model numbers have the same version of
software.
Access the main printed circuit board in each product.
Locate a white sticker with a P-XXXX number or
Connect a service checker and locate the ROM number.
· In a hospital or facility, install the unit at least 3 m away from medical
or electronic devices. Operation of the unit may adversely affect the devices.
The devices generate electromagnetic interference (EMI) waves that can
directly radiate into the unit and cause malfunction.
· If there is a source of electrical interference near the power source,
install noise suppression equipment (filter).
· If the wired controller is installed in a location where electromagnetic
radiation is generated, make sure that the wired controller is shielded and
cables are sleeved inside conduit tubing.
· Be careful that moisture, dust, or variant refrigerant compounds not enter
the refrigerant cycle during installation work. Foreign matter could damage
internal components or cause blockages.
· If air filters are required on this unit, do NOT operate the unit without
the air filter set in place. If the air filter is not installed, dust may
accumulate and breakdown may result.
· Do NOT install the unit in a location where animals and plants can come in
direct contact with the outlet air and become adversely affected.
· Be sure the condensate hose discharges water properly. If connected
incorrectly, leaks can occur.
· Do NOT install the unit with any downward slope to the side of the
condensate pipe. If you do, you may have drain water flowing back which may
cause leaks.
· Do NOT install the unit in any place where oil can seep into the units, such
as a kitchen in restaurants, and so forth. For these locations or social
venues, use specialized units with oilresistant features built into them. In
addition, use a specialized ceiling fan designed for restaurant use. These
specialized oil-resistant units can be ordered for such applications. However,
in places where large quantities of oil can splash onto the unit, such as a
factory,
even the specialized units cannot be used. These products should not be
installed in such locations.
· Do NOT install this unit in any place where silicon gases can coalesce. If
the silicon gas comes into contact with the surface of the heat exchanger, the
finned surfaces repel water. As a result, moisture can enter from the
condensate pan into the electrical box, possibly causing electrical failures.
· Do not place any flammable items or anything that can cause a fire on or
around the outdoor unit. It may cause a fire.
· During the test run, check the unit’s operation temperature. If the unit is
used in an environment where the temperature exceeds the operation boundary,
it may cause severe damage. Check the working range in the manual.
· The A-weighted emission sound pressure level does not exceed 70 dB (A).
Installation Precautions
WARNING
To reduce the risk of serious injury or death, the following installation
precautions must be followed.
· When installing the unit into:
A wall: Make sure the wall is strong enough to hold the unit’s weight. It may
be necessary to construct a strong wood or metal frame to provide added
support.
A room: Properly insulate any refrigerant piping run inside a room to prevent
“condensation” that can cause dripping and water damage to wall and floors.
Damp or uneven areas: Use a raised concrete pad or concrete blocks to provide
a solid, level foundation for the unit to prevent water damage and abnormal
vibration.
An area with high winds: Securely anchor the outdoor unit down with bolts and
a metal frame. Provide a suitable air baffle.
· Do NOT install the unit in the following places. Doing so can result in an
explosion, fire, deformation, corrosion, or product failure. Explosive or
flammable atmosphere Where a fire, oil, steam or powder can directly enter the
unit, such as nearby or
1. Safety Summary
above a kitchen stove. Where oil (including machinery oil) may be
present. Where corrosive gases such as chlorine,
bromine, or sulfide can accumulate, such as near a hot tub or a hot spring.
Where dense, salt-laden airflow is heavy, such as in coastal regions. Where
the air quality is of high acidity. Where harmful gases can be generated from
decomposition.
· Do NOT position the condensate pipe for the indoor unit near any sanitary
sewers where corrosive gases may be present. If you do, toxic gases can seep
into breathable air spaces and can cause respiratory injuries. If the
condensate pipe is installed incorrectly, water leakage and damage to the
ceiling, floor, furniture, or other possessions may result. If the condensate
pipe becomes clogged, water may drip from the indoor unit. Do NOT install the
indoor unit where such dripping can cause moisture damage or at uneven
locations.
· During transportation, do NOT allow the backrest of the forklift make
contact with the unit, otherwise, it may cause damage to the heat exchanger
and also may cause injury when stopped or started suddenly.
· Before performing any brazing work, be sure that there are no flammable
materials or open flames nearby.
· Remove gas inside the closing pipe when the brazing work is performed. If
the brazing filler metal is melted with remaining gas inside, the pipes will
be blown off and it may cause injury.
· Be sure to use nitrogen gas for the airtight test. If other gases such as
oxygen gas, acetylene gas or fluorocarbon gas are accidentally used, it may
cause an explosion or gas intoxication.
· Perform a test run to ensure normal operation. Safety guards, shields,
barriers, covers, and protective devices must be in place while the
compressor/unit is operating. During the test run, keep fingers and clothing
away from any moving parts.
· Do NOT install the indoor unit anywhere discharge airflow can pass directly
toward nearby heating equipment (space heaters). It may interfere with the
combustion process in these units.
· When the indoor unit is operating with heating equipment, ventilate the room
sufficiently. Any leaked refrigerant gas that happens to come into contact
with any heat source can become
3
1. Safety Summary
toxic on contact and can cause suffocation in the immediate area.
· Do NOT install this system in close proximity to septic sewer lines where
flammable and toxic gases can coalesce.
CAUTION
To reduce the risk of minor or moderate injury, the following installation
precautions must be followed.
· Proper handling of this unit requires two people. Safe handling and
installation of the indoor unit requires the strength of two people. Mounting
the unit alone may cause injury due to a fall of the unit. Although the unit
may be girded with plastic bands, do NOT use it for transportation. Avoid
contact with finned surfaces of the heat exchanger as sharp edges can cause
severe injury to hands and fingers. Use appropriate work gloves for the job.
NOTICE
Take the following precautions to reduce the risk of property damage.
· The optional decorative panel can become deformed if the positioning of the
indoor unit’s suspension brackets is not stable or level. Condensation can
accumulate in low spots as a result due to escaping air through any resulting
gaps between the indoor unit and the decorative panel.
· Check to ensure that the condensate hose discharges moisture properly. If
connected incorrectly, it can result in leakage and cause damage to furniture.
· Make sure to use the factory-supplied condensate hose and hose clamp. Non-
factory supplied condensate hose and hose clamp can cause water leakage.
· Do NOT bend or twist the factory-supplied condensate hose. This could
compromise the seal and result in water leakage.
· Do NOT apply excessive force to the condensate pipe connection. This can
also compromise the seal properties of the connection.
· Verify that the installed unit is level with floor and ceiling surfaces. Any
variance or inclination can cause moisture to back up into the condensate pan,
overflow, and seepage onto ceiling or wall surfaces, and cause damage to
carpeted surfaces or furniture below. 4
· Air circulation should be optimized to achieve the best distribution pattern
and not settled into isolated pockets that can make people uncomfortable.
· Inspect the condensate pan before the onset of winter to drain away all
accumulated water in the pan.
· The heat exchanger of indoor unit overheats whenever there is a slight
amount of refrigerant circulating during slowdown or stoppage. As a result,
water in the condensate pan evaporates and can condense on ceiling or wall
surfaces.
· After the drain check is completed, insert the rubber plug again and seal
the gap with a silicon sealant.
· Clean up the site when finished, remembering to check that no metal scraps
or bits of wiring have been left inside the unit being installed.
· Do NOT install the decorative panel with motion sensor and radiation sensor
or motion sensor kit in the following places. It may cause failure or
deterioration of the sensor.
Ambient temperature changes drastically. Where excessive force or vibration is
applied
to the sensor. Where static electricity or electromagnetic
waves may generate. Where interference of infrared light such as
glasses or mist are in the detecting area. Where the lens for sensor is
exposed to high
temperature and humidity for a long time. Where fluid and corrosive gas exist.
Where direct lights such as sunlight or
headlights affect the sensor. Where hot air from a heater, etc. affects
directly to the sensor. Where the air flow returns to the sensor by
hitting obstacles such as a shelf, locker, etc. Where the blower devices such
as ceiling
fan, ventilating fan, etc. affect the air flow from the indoor unit. Where
weather affects directly the surface of the sensor. Where the lens surface may
smudge or be damaged such as a dusty environment. Detecting function will
decrease if the lens for sensor smudges. In this case, wipe off smudges using
a cotton swab soaked with alcohol (Isopropyl alcohol is recommended.) or a
soft cloth. (When wiping off smudges on the lens for sensor, do NOT apply
excessive force. If excessive force is applied, the resin lens may be damaged
and this may cause
malfunctions such as misdetection or undetectable motion.)
· When using the remote control thermo function, consider the following points
when selecting the installation location.
Where the average temperature of the room can be detected
Where there is no direct sunlight Where there is no heat source nearby Where
hot/cold air from the outdoors, or
a draft from elsewhere (such as air vents, diffusers or grilles) can affect
air circulation.
· When installing the wired controller in the following locations with poor
temperature distribution, install remote sensors.
Where the unit is exposed to direct sunshine or direct light.
Where the unit is in close proximity to a heat source.
Where hot/cold air from the outdoors, or a draft from elsewhere (such as air
vents, diffusers or grilles) can affect air circulation.
In areas with poor air circulation and ventilation.
· When a wireless controller is used, locate at a distance of at least 3 m
between the indoor unit and electric lighting. If not, the receiver part of
the unit may have difficulty receiving operation commands.
Refrigerant Precautions
WARNING
To reduce the risk of serious injury or death, the following refrigerant
precautions must be followed.
· As originally manufactured, this unit contains refrigerant charged by
Hitachi-Johnson Controls Air Conditioning. Hitachi-Johnson Controls Air
Conditioning uses only refrigerants that have been approved for use in the
unit’s intended home country or market. HitachiJohnson Controls Air
Conditioning distributors similarly are only authorized to provide
refrigerants that have been approved for use in the countries or markets they
serve. The refrigerant used in this unit is identified on the unit’s faceplate
and/or in the associated manuals. Any additions of refrigerant into this unit
must comply with the country’s requirements with regard to refrigerant use and
should be obtained from Hitachi-Johnson Controls Air Conditioning
distributors. Use
1. Safety Summary
of any non-approved refrigerant substitutes will void the warranty and will
increase the potential risk of injury or death.
· To avoid the possibility of different refrigerant or refrigerant oil being
introduced into the cycle, the sizes of the charging connections have been
changed from R407C type and R22 type. It is necessary to prepare the following
tools listed in “Necessary Tools and Instruments List for Installation” in the
Installation and Maintenance Manual before performing the installation work.
Use refrigerant pipes and joints which are approved for use with R410A.
· The refrigerant R410A is adopted. The refrigerant oil tends to be affected
by foreign matters such as moisture, oxide film, (or fat). Perform the
installation work with care to prevent moisture, dust, or different
refrigerant from entering the refrigerant cycle. Foreign matter can be
introduced into the cycle from such parts as expansion valve and the operation
may be unavailable.
· The outdoor unit shall only be connected to indoor units suitable for the
same refrigerant (R410A).
· The design pressure for this product is 4.15 MPa. The pressure of the
refrigerant R410A is 1.4 times higher than that of the refrigerant R22.
Therefore, the refrigerant piping for R410A must be thicker than that for R22.
Make sure to use the specified refrigerant piping. If not, the refrigerant
piping may rupture due to an excessive refrigerant pressure. Besides, pay
attention to the piping thickness when using copper refrigerant piping. The
thickness of copper refrigerant piping differs depending on its material.
· The maximum operating pressure is 4.15 MPa. This maximum operating pressure
shall be considered when connecting the outdoor unit to correlated indoor
units.
· When installing the unit, and connecting refrigerant piping, keep all piping
runs as short as possible, and make sure to securely connect the refrigerant
piping before the compressor starts operating. If the refrigerant piping is
not connected and the compressor activates with the stop valve opened, the
refrigerant cycle will become subjected to extremely high pressure, which can
cause an explosion or fire.
· If installed in a small room, take measures to prevent the refrigerant from
exceeding the maximum allowable concentration in the event that refrigerant
gases should escape. The
5
1. Safety Summary
installation should meet the requirements in each regional regulation. If
refrigerant gas leaks during the installation work, ventilate the room
immediately.
· The refrigerant system may be damaged if the slope of the piping connection
kit exceeds +15°.
· Tighten the flare nut with a torque wrench in the specified manner. Do NOT
apply excessive force to the flare nut when tightening. If you do, the flare
nut can crack and refrigerant leakage may occur.
· When maintaining, relocating, and disposing of the unit, dismantle the
refrigerant piping after the compressor stops.
· When pipes are removed from under the piping cover, after the insulation
work is completed, cover the gap between the piping cover and pipes using a
packing material (field-supplied). If the gap is not covered, the unit may be
damaged if snow, rain water or small animals enter the unit.
· Do NOT apply excessive force to the spindle valve at the end of opening.
Otherwise, the spindle valve flies out due to refrigerant pressure. At the
test run, fully open the gas and liquid valves. Otherwise, these devices will
be damaged. (It is closed before shipment.)
· Before installation is complete, make sure that the refrigerant leak test
has been performed. If refrigerant gases escape into the air, turn off the
main switch, extinguish any open flames and contact your service contractor.
Refrigerant (Fluorocarbon) for this unit is odorless. If the refrigerant
should leak and come into contact with open flames, toxic gas could be
generated. Also, because the fluorocarbons are heavier than air, they settle
to the floor, which could cause asphyxiation.
· If refrigerant gas should leak, turn off all heating equipment and ventilate
the room immediately. Mop down or vacuum floor areas of residual toxic
particulate.
· This product contains fluorinated greenhouse gases that its functioning
relies upon. Do NOT vent into the atmosphere. Refrigerant type: R410A For mass
of charged refrigerant, refer to chapter 7. GWP1: 2090 1. GWP=global warming
potential
Electrical Precautions
WARNING
To reduce the risk of serious injury or death, the following refrigerant
precautions must be followed.
· This air conditioning system shall be installed in accordance with national
wiring regulations.
· Highly dangerous electrical voltages are used in this system. Carefully
refer to the wiring diagram and these instructions when wiring. Improper
connections and inadequate grounding can cause serious injury or death.
· Means for disconnection from the supply mains, which have a contact
separation in all poles that provide full disconnection under over voltage
category III conditions, must be incorporated in the fixed wiring in
accordance with the wiring rules.
· Be sure to use the dedicated circuit and perform all electrical work in
strict accordance with this manual and all relevant regulatory standards.
· This air conditioning system is not intended for use by persons (including
children) with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or
instruction concerning use of the air conditioning system by a person
responsible for their safety.
Supervise children to ensure they do not play with the unit.
If the power supply wiring is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in order to
avoid a hazard.
· Do NOT open the service cover or access panel to indoor or outdoor units
without turning off the main power supply. Before servicing, open and tag all
disconnect switches. Never assume electrical power is disconnected. Check with
a multimeter.
· Turn off all power at the main power source before performing maintenance
work. Failure to do so can result in damage to internal components with severe
or fatal electrical shock.
· Do NOT operate indoor units with the electrical box and switch panel open
and exposed. Incidental contact with energized components can prove fatal.
6
· Insulate all electrical components and connections from exposure to
moisture. Failure to do so can result in an electrical short circuit and fire.
· Do NOT tamper with or attempt to “repair” electrical wiring or connections.
Call your installer or electrical contractor. Serious or fatal injury can
occur.
· Only use electrical protection equipment and tools suited for this
installation.
· The Main Fuse shall be replaced by the professional person.
· Use an exclusive power supply for the air conditioner at the unit’s rated
voltage.
· Use the specified cables between units. · Be sure to install circuit
breakers such as an
earth leakage circuit breaker (ELB)/ground fault interrupter (GFCI), isolating
switch, molded case circuit breaker and so on), with the specified capacity.
Ensure that the wiring terminals are tightened securely to recommended torque
specifications. If a circuit breaker or fuse is frequently activated, shut
down the system and contact your service contractor.
· Shut down at the main power supply if the ELB (GFCI) activates frequently.
Contact your distributor or contractor immediately. Failure to act accordingly
can result in serious injury and damage to the unit.
· Clamp electrical wires securely with a cable band after all wiring is
connected to the terminal block. In addition, run wires securely through the
wiring access channel or the electrical conduit.
· When installing the power lines, do NOT apply tension to the cables. Secure
the suspended cables at regular intervals, but not too tightly.
· Make sure that the terminals do NOT come into contact with the surface of
electrical box. If the terminals are too close to the surface, it may lead to
failures at the terminal connection.
· After stopping operation, be sure to wait at least five minutes before
turning off the main power switch. Otherwise, water leakage or electrical
breakdown may result. Disconnect the power supply completely before attempting
any maintenance for electrical parts. Confirm that no residual voltage is
present after disconnecting the power supply.
· Residual voltage can cause electric shock. At all times, check for residual
voltage after disconnecting from the power source before starting work on the
unit.
1. Safety Summary
· The installation of a residual current device (RCD) having a rated residual
operating current not exceeding 30 mA is advisable.
· Do NOT clean with, or pour water onto the controller as it could cause an
electric shock and/or damage the unit. Do NOT use strong detergent such as a
solvent. Clean with a soft cloth.
· Check that the earth (ground) wiring is securely connected. Do NOT connect
ground wiring to gas piping, water piping, lightning conductor, or telephone
ground wiring.
· Do NOT run the relay wiring for the motion sensor and power supply wiring in
parallel. Electromagnetic Interference (EMI) may cause malfunction of the
sensor. (Only for indoor unit with motion sensor)
· The polarity of the input terminals is important, so be sure to match the
polarity when using contacts that have polarity.
· Before installing the controller or remote devices, ensure the indoor and
outdoor unit operation has been stopped. Further, be sure to wait at least
five minutes before turning off the main power switch to the indoor or outdoor
units. Otherwise, water leakage or electrical breakdown may result.
· Do NOT install the wired controller in the hightemperature and humidity
location.
· When connecting the controller cabling to the units, do NOT touch or adjust
any safety devices inside the indoor or outdoor units. All safety features,
disengagement, and interlocks must be in place and functioning correctly
before the equipment is put into operation. If these devices are improperly
adjusted or tampered with in any way, a serious accident can occur. Never
bypass any safety device or switch.
NOTICE
Take the following precautions to reduce the risk of property damage.
· Use an exclusive power supply with the rated voltage for the controller that
requires an external power supply.
· Communication cable must be shielded twist pair cable (0.75 mm2). Shielded
cable must be considered for applications and routing in areas of high EMI and
other sources of potentially excessive electrical noise to reduce the
potential for communication errors. When shielded cable is 7
2. Before Installation
applied, proper bonding and termination of the cable shield is required as per
Hitachi-Johnson Controls Air Conditioning guidelines. Plenum and riser ratings
for communication cables must be considered per application and local code
requirements.
· The air conditioner may not function normally in the following instances: If
electrical power for the air conditioner is supplied from the same transformer
as a device1 referred to below. If the power source cables for this device1
and the air conditioner are located in close proximity to each other. *1. A
device can include a lift, container crane, rectifier for electric railway,
inverter power device, arc furnace, electric furnace, largesized induction
motor and large-sized switch.
Regarding the cases mentioned above, surge voltage may be inducted into the
power supply cables for the air conditioner due to a rapid change in power
consumption of the device and an activation of a switch. Check field
regulations and standards before performing electrical work in order to
protect the power supply for the air conditioner.
· Turn off and disconnect the unit from the power source when handling the
service connector. Do NOT open the service cover or access panel to the indoor
or outdoor units
without turning off the main power supply.
2. Before Installation
2.1 About This Product
Hitachi proudly introduces the New “air365 Max” series, the highly-efficient
and reliable airconditioning system. Recently, increased numbers of buildings
are requiring “Intelligent” facilities – communication networks, office
automation, and a comfortable environment. Particularly, comfortable space is
required all the day through the year in office buildings. This multi-split
system air conditioner, “air365 Max” series can meet these requirements. The
proven combination of the scroll compressor and the inverter provides the best
air conditioning for small/medium office buildings.
· SYSTEM FREE System
Hitachi has developed the SYSTEM FREE system with its customers always in
mind. This system, which is unique in the world,
8
allows the interconnection of the same indoor units for all the Hitachi
systems. This system provides the end user with greater flexibility for
installation, which means that the air-conditioning systems will integrate
better with the whole of the installations that make up the building.
· Wide Product Range of Outdoor Units
Space, structure and necessary functions, in line with evolution in building
design, the requirements for air conditioning have also diversified.
· About Refrigerant
WARNING
· The design pressure for this product is 4.15 MPa. The pressure of the
refrigerant R410A is 1.4 times higher than that of the refrigerant R22.
Therefore, the refrigerant piping for R410A must be thicker than that for R22.
Make sure to use the specified refrigerant piping. If not, the refrigerant
piping may rupture due to an excessive refrigerant pressure. Besides, pay
attention to the piping thickness when using copper refrigerant piping. The
thickness of copper refrigerant piping differs depending on its material.
NOTICE
· The refrigerant R410A is adopted. The refrigerant oil tends to be affected
by foreign matters such as moisture, oxide film, (or fat). Perform the
installation work with care to prevent moisture, dust, or different
refrigerant from entering the refrigerant cycle. Foreign matter can be
introduced into the cycle from such parts as expansion valve and the operation
may be unavailable.
· To prevent the different refrigerant or refrigerant oil from being mixed
into the cycle, the sizes of the charging connections have been changed from
R407C type and R22 type. It is necessary to prepare the following tools before
performing the installation work.
· Use refrigerant pipes and joints which can
be used for R410A.
· Necessary Tools and Instruments List for Installation
No.
Tool
No.
Tool
2. Before Installation
No.
Tool
1 Handsaw
8 Plier
16 Cutter for Wires
2 Phillips Screwdriver
9 Pipe Cutter
17 Gas Leak Detector
3 Vacuum Pump
10 Brazing Kit
18 Leveller
4 Refrigerant Gas Hose
11 Hexagon Wrench
19 Clamper for Solderless Terminals
5 Megohmmeter
12 Spanner
20 Hoist (for Indoor Unit)
6 Copper Pipe Bender
13 Weigher
21 Ammeter
7
Manual Water Pump (for Indoor Unit)
14 Charging Cylinder 15 Gauge Manifold
22 Voltage Meter 23 Wrench
Use tools and measuring instruments only for the new refrigerant R410A as they come into direct contact with the refrigerant.
G: Interchangeability is available with current R22 l: Only for Refrigerant R410A (No Interchangeability with R22) 5: Prohibited F: Only for Refrigerant R407C (No Interchangeability with R22)
Interchangeability
Measuring Instrument and Tool
with R22
Reason of Non-Interchangeability and Attention (: Strictly Required)
Use
R410A R407C
Pipe Cutter Chamfering Reamer
Flaring Tool
Extrusion Adjustment Gauge
G
G
–
Cutting Pipe Removing Burrs
G l
G · The flaring tools for R407C are applicable to Flaring for Tubes
R22.
· If using flaring tube, make dimension of tube Dimensional
l
–
larger for R410A.
· In case of material 1/2H, flaring is not
Control for Extruded Portion of Tube
available.
after Flaring
Pipe Bender
G
G
· In case of material 1/2H, bending is not available. Use elbow for bend and braze.
Bending
Refrigerant Expanding Tool
G
Pipe
l Torque Wrench
G
· In case of material 1/2H, expanding of tube
G
is not available. Use socket for connecting Expanding Tubes
tube.
G
· For 12.7, 15.88, spanner size is increased
by 2mm.
Connection of
G
· For 6.35, 9.52, 19.05, spanner size is the Flare Nut same.
Brazing Tool
G
G · Perform correct brazing work.
Brazing for Tubes
Nitrogen Gas
G
G
· Strict Control against Contamination (Blow nitrogen during brazing.)
Prevention from Oxidation during Brazing
Lubrication Oil (for Flare Surface)
l
F
· ·
Use a synthetic oil which is equivalent to the oil used in the refrigeration cycle. Synthetic oil absorbs moisture quickly.
Applying Oil to the Flared Surface
9
2. Before Installation
Interchangeability
Measuring Instrument and Tool
with R22
Reason of Non-Interchangeability and Attention (: Strictly Required)
Use
R410A R407C
Refrigerant Cylinder
· Check refrigerant cylinder color.
l
F Liquid refrigerant charging is required
regarding zeotropic refrigerant.
Refrigerant Charging
Vacuum Pump
G
G The current ones are applicable. However,
Adapter for Vacuum Pump
l*1
F
it is required to mount a vacuum pump adapter which can prevent reverse oil flow when a vacuum pump stops.
Vacuum Pumping
· No interchangeability is available due to
higher pressures when compared with R22.
Manifold Valve
l
F Do not use current ones to the different
Vacuum Pumping,
Vacuum
Drying/
Refrigerant
Charge
Charging Hose
l
F
refrigerant. If used, mineral oil will flow into the cycle and cause sludges, resulting in clogging or compressor failure. Connection diameter is different; R410A:
Vacuum Holding, Refrigerant Charging and Check of Pressures
UNF1/2, R407C: UNF7/16.
Charging Cylinder 5
5 · Use the weight scale.
–
Weight Scale
G
Refrigerant Gas Leakage Detector
l*1
G
–
· The current gas leakage detector (R22) is
F
not applicable due to different detecting
method.
Measuring Instrument for Refrigerant Charging
Gas Leakage Check
*1. Interchangeability with R407C.
2.2 Line-Up of Outdoor Units
Standard Type: CNCCLW
1. This outdoor unit series “CNCCLW” can build the capacity of 8 to 120 HP by
combining the outdoor units of 8 to 30 HP.
2. The combinations not indicated in the table below are unavailable.
HP
8
10
12
14
16
18
Model RAS-080CNCCLW RAS-100CNCCLW RAS-120CNCCLW RAS-140CNCCLW RAS-160CNCCLW RAS-180CNCCLW
HP
20
22
24
26
28
30
Model RAS-200CNCCLW RAS-220CNCCLW RAS-240CNCCLW RAS-260CNCCLW RAS-280CNCCLW RAS-300CNCCLW
HP
32
34
36
38
40
42
Model RAS-320CNCCLW RAS-340CNCCLW RAS-360CNCCLW RAS-380CNCCLW RAS-400CNCCLW RAS-420CNCCLW
RAS-180CNCCLW RAS-180CNCCLW RAS-180CNCCLW RAS-220CNCCLW RAS-220CNCCLW RAS-
240CNCCLW Combination
RAS-140CNCCLW RAS-160CNCCLW RAS-180CNCCLW RAS-160CNCCLW RAS-180CNCCLW RAS-
180CNCCLW
HP
44
46
48
50
52
54
Model RAS-440CNCCLW RAS-460CNCCLW RAS-480CNCCLW RAS-500CNCCLW RAS-520CNCCLW RAS-540CNCCLW
RAS-220CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-260CNCCLW RAS-260CNCCLW RAS-
280CNCCLW Combination
RAS-220CNCCLW RAS-220CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-260CNCCLW RAS-
260CNCCLW
10
2. Before Installation
HP
56
58
60
62
64
66
Model RAS-560CNCCLW RAS-580CNCCLW RAS-600CNCCLW RAS-620CNCCLW RAS-640CNCCLW RAS-660CNCCLW
RAS-280CNCCLW RAS-300CNCCLW RAS-300CNCCLW RAS-220CNCCLW RAS-240CNCCLW RAS- 240CNCCLW
Combination RAS-280CNCCLW RAS-280CNCCLW RAS-300CNCCLW RAS-220CNCCLW RAS- 220CNCCLW RAS-240CNCCLW
–
–
–
RAS-180CNCCLW RAS-180CNCCLW RAS-180CNCCLW
HP
68
70
72
74
76
78
Model RAS-680CNCCLW RAS-700CNCCLW RAS-720CNCCLW RAS-740CNCCLW RAS-760CNCCLW RAS-780CNCCLW
RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-260CNCCLW RAS-260CNCCLW RAS- 260CNCCLW
Combination RAS-220CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS- 260CNCCLW RAS-260CNCCLW
RAS-220CNCCLW RAS-220CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS- 260CNCCLW
HP
80
82
84
86
88
90
Model RAS-800CNCCLW RAS-820CNCCLW RAS-840CNCCLW RAS-860CNCCLW RAS-880CNCCLW RAS-900CNCCLW
RAS-280CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS-300CNCCLW RAS-300CNCCLW RAS- 300CNCCLW
Combination RAS-260CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS- 300CNCCLW RAS-300CNCCLW
RAS-260CNCCLW RAS-260CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS- 300CNCCLW
HP
92
94
96
98
100
102
Model RAS-920CNCCLW RAS-940CNCCLW RAS-960CNCCLW RAS-980CNCCLW RAS-H00CNCCLW RAS-H02CNCCLW
RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-260CNCCLW RAS-260CNCCLW RAS- 260CNCCLW
RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-260CNCCLW RAS-
260CNCCLW Combination
RAS-220CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-
260CNCCLW
RAS-220CNCCLW RAS-220CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS-240CNCCLW RAS- 240CNCCLW
HP
104
106
108
110
112
114
Model RAS-H04CNCCLW RAS-H06CNCCLW RAS-H08CNCCLW RAS-H10CNCCLW RAS-H12CNCCLW RAS-H14CNCCLW
RAS-260CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS- 300CNCCLW
RAS-260CNCCLW RAS-260CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS-
280CNCCLW Combination
RAS-260CNCCLW RAS-260CNCCLW RAS-260CNCCLW RAS-280CNCCLW RAS-280CNCCLW RAS-
280CNCCLW
RAS-260CNCCLW RAS-260CNCCLW RAS-260CNCCLW RAS-260CNCCLW RAS-280CNCCLW RAS- 280CNCCLW
HP
116
118
120
Model RAS-H16CNCCLW RAS-H18CNCCLW RAS-H20CNCCLW
RAS-300CNCCLW RAS-300CNCCLW RAS-300CNCCLW
RAS-300CNCCLW RAS-300CNCCLW RAS-300CNCCLW Combination
RAS-280CNCCLW RAS-300CNCCLW RAS-300CNCCLW
RAS-280CNCCLW RAS-280CNCCLW RAS-300CNCCLW
11
2. Before Installation
2.3 Combination of Indoor Unit and Outdoor Unit
The following indoor units can be combined with the Hitachi “air365 Max” series outdoor unit.
Table 2.1 Indoor Unit Type List
Indoor Unit
Nominal Capacity
Type
0.4 0.6 0.7 0.8 0.9 1 1.1 1.3 1.5 1.6 1.8 2 2.3 2.5 3 3.3 3.6 4 4.5 5 6 8 10 12 16 20
1-Way Cassette 2-Way Cassette 4(R)-Way Cassette AC Compact Ducted AC Low Static Ducted AC M/H Static Ducted AC Slim/Mini Ducted
{} {}
All Fresh Air
Convertible
{} {}
DC Low Static Ducted DC M/H Static Ducted
DX-AHU kit
Floor Celling
Floor Concealed
Floor Exposed
Mini 4-Way Cassette Total Heat Exchanger
Wall Mounted
: Available, { }: India only NOTE:
The number of indoor units connectable to “air365 Max” series outdoor unit is listed in Tables 2.2 System
Combination. Comply with the following conditions when installing the unit.
Table 2.2 System Combination – CNCCLW
Outdoor Unit
Min. Capacity at Max. Number of
Recommended
Range of
Total Length between Each IDU
Individual Operation Connectable IDU Number of Connectable IDU Combination Capacity and Expansion Valve Kit(*)
RAS-080CNCCLW
20
8
40m
RAS-100CNCCLW
25
10
RAS-120CNCCLW
30
60m
RAS-140CNCCLW
36
70m
RAS-160CNCCLW
40
16
80m
RAS-180CNCCLW
45
RAS-200CNCCLW
50
18
RAS-220CNCCLW
55
20
120m
RAS-240CNCCLW
60
RAS-260CNCCLW RAS-280CNCCLW RAS-300CNCCLW
0.6HP (1.6kW)
26
50 to 200%
150m
RAS-320CNCCLW
32
RAS-340CNCCLW
180m
RAS-360CNCCLW
RAS-380CNCCLW
64
to
RAS-540CNCCLW
RAS-560CNCCLW
38
50 to 180%
200m
RAS-580CNCCLW to
RAS-H20CNCCLW
50 to 150%
12 Refer to NOTES on page 13.
2. Before Installation
NOTES:
· The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total
Outdoor Unit Capacity
· For the system under which all the indoor units are supposed to operate
simultaneously, the total indoor unit capacity should be less than outdoor
unit capacity. Otherwise, it may cause a decrease of operating performance and
operating limit in overload operation.
· For the system under which all the indoor units are not supposed to operate
simultaneously, the total indoor unit capacity is available up to 130%, 150%,
180% or 200% depending on the indoor unit type and capacity.
· Maximum number of connectable indoor units differs depending on the model,
capacity, environment and installation place of connected indoor units. Refer
to the Technical Catalog for the selection.
· The air flow volume for indoor units of 0.6 to 1.3HP is set higher than that
for indoor units of 1.5HP or more.
· Total Length between Each I.U. and Expansion Valve Kit (*): This is the
summation of the piping length between each wall mounted type without
expansion valve and expansion valve kit in the refrigerant system.
The load capacity per hour or the possibility of all indoor units simultaneous
operation is unknown at the design stage, the total capacity of combined
indoor units should be not over 100% against the outdoor unit capacity.
2.4 Piping Connection Kit (Optional) between Outdoor Units
MC – NP 21 SA 1
Type of Generation Applicable System
SA, TA: for Heat Pump and Cooling Only System (2 Pipes)
Corresponding Outdoor Units Capacity
[ Standard ] 21: 32 – 48 HP 22: 50 – 60 HP 31: 62 – 90 HP 40: 92 – 120 HP
Refrigerant Type
NP: R410A
Unit Type
MC: Multi Connection Kit for Outdoor Units
Applicable Outdoor Unit
Item
Cooling Only
No. of ODU
Model
Remarks
32 – 48
Piping Connection
Kit
50 – 60 62 – 90
92 – 120
2 MC-NP21SA1 for Gas: 1
for Liquid: 1 2 MC-NP22TA
3
MC-NP31TA
for Gas: 2 for Liquid: 2
4
MC-NP40TA
for Gas: 3 for Liquid: 3
13
2. Before Installation
2.5 Multi-Kit (Optional) between Indoor Unit and Outdoor Unit
MW – NP 282 A 3
1. Line Branch First Branch
2. Multi-Kit after First Branch
Type of Generation Applicable System
A: for Heat Pump and Cooling Only System (2 Pipes)
(Standard Type)
Outdoor Unit HP 8, 10
Model MW-NP282A3
(Standard Type)
Total Indoor Unit HP
Model
<12
MW-NP282A3
No. of Branches Corresponding Outdoor Unit and Indoor Unit Capacity
12 – 16 18 – 24 26 – 54
MW-NP452A3 MW-NP692A3 MW-NP902A3
12 – 17.99 18 – 25.99 26 – 55.99
MW-NP452A3 MW-NP692A3 MW-NP902A3
Refrigerant Type
56 – 120
MW-NP2682A3
56
NP: R410A
Unit Type MW: Line Branch Multi-Kit
3. Header Branch (Standard Type)
MH: Header Branch Multi-Kit Total Indoor Unit HP No. of Header Branches
MW-NP2682A3 Model
Max. 8
4
MH-NP224A
Max. 10
8
MH-NP288A
2.6 Factory-Supplied Accessories
Check to ensure that the following accessories are packed with the outdoor unit. (Refer to page 15 for NOTE.) Table 2.3 Factory-Supplied Accessories (CNCCLW)
Accessory
8HP
10HP
12HP
14HP
16HP
18HP
Remarks
Accessory Pipe
Connection for Refrigerant Gas Pipe
ID 22.4 OD 19.05
Connection for
Refrigerant
–
Liquid Pipe
Cord Clamp
For Fixing Power Source Wire
Cable Clamp
For Fixing Power Source Wire
×2
For Power Source Wire
Outlet (Bottom Base, Piping
×2
Cover)
Rubber Bush
For Communication Wire Outlet (Bottom Base, Piping
×2
Cover)
For Comm. Wire Outlet
(Bottom Base, Piping
×2
Cover)
Rubber cap *3
Attach to the bottom base.
×2
Packing *3
Attach to the bottom base.
×1
Screw
×3
Combination For Indication of
Unit Model Combination Unit
×3
Label
Model
Open/Close Indication for Stop Valve
For Indication of “Open”
×2
Ferrite Core White
×1
14
–
ID 22.4 ID 22.4 ID 25.6 ID 25.6
OD 25.4 OD 25.4 OD 28.58 OD 28.58
– OD 9.52 OD 9.52 – OD 12.7
OD 12.7 OD 12.7
OD 15.88
×2
×2
×2
×2
×2
×2
×2
×2
×2
×2 70 mm
×2
×2
×2
×2
×2 62 mm
×2
×2
×2
×2
×2 38 mm
×2
×2
×2
×2
×2 *1
×1
×1
×1
×1
×1 *2
×3
×3
×3
×3
×3
For fixing Cord Clamp and Spare
×3
×3
×3
×3
Attach to ×3 Outdoor Unit A
(Main Unit)
×2
×2
×2
×2
×2 With Fixing Band
×1
×1
×1
×1
×1
2. Before Installation
Accessory
20HP
22HP 24HP
26HP
28HP
30HP
Remarks
Accessory Pipe
Cord Clamp Cable Clamp
Rubber Bush
Connection for Refrigerant Gas Pipe
ID 25.6 OD 28.58
Connection for Refrigerant Liquid Pipe
OD 12.7 OD 15.88
For Fixing Power Source Wire
For Fixing Power Source Wire
×2
For Power Source Wire
Outlet (Bottom Base, Piping
×2
Cover)
For Communication
Wire Outlet (Bottom Base, Piping
×2
Cover)
For Comm. Wire Outlet
(Bottom Base, Piping
×2
Cover)
Rubber cap *3
Attach to the bottom base.
×2
Packing *3
Attach to the bottom base.
×1
Screw
×3
Combination For Indication of
Unit Model Combination Unit
×3
Label
Model
Open/Close Indication for Stop Valve
For Indication of “Open”
×2
Ferrite Core White
×1
–
–
×2 ×2
×2 ×2 ×2 ×1 ×3 ×3 ×2 ×1
–
ID 28.8 ID 28.8 ID 28.8
OD 31.75 OD 31.75 OD 31.75
–
ID 15.88 ID 15.88 ID 15.88
OD 19.05 OD 19.05 OD 19.05
×2
×2
×2
×2
×2
×2
×2
×2 70 mm
×2
×2
×2
×2 62 mm
×2
×2
×2
×2 38 mm
×2
×2
×2
×2 *1
×1
×1
×1
×1 *2
×3
×3
×3
×3
For fixing Cord Clamp and Spare
Attach to
×3
×3
×3
×3 Outdoor Unit A
(Main Unit)
×2
×2
×2
×2 With Fixing Band
×1
×1
×1
×1
NOTE:
· If any of these accessories is not packed with the unit, please contact your
contractor.
*3. Attach the rubber cap and packing as shown in the figure below.
RAS-080 to 140CNCCLW
RAS-160 to 200CNCCLW
Bottom Base
Bottom Base
*1. Attach a rubber cap. RAS-220 to 300CNCCLW
Bottom Base
1. Attach a rubber cap. 2. Attach a packing. *1. Attach a rubber cap.
*1. Attach a rubber cap.
15
3. Selection of Installation Location
3. Selection of Installation Location
WARNING
· Provide a sufficiently strong foundation. If not, the unit may fall down and
it may lead to injuries.
· Do not install the outdoor unit where the flammable gases may occur or leak.
Otherwise, it may cause a fire.
· If the indoor unit is installed in a small room and the refrigerant gas
leakage occurs, the leaked refrigerant gas fills the room and it may cause
suffocation. Do not exceed the maximum permissible concentration of the
refrigerant gas in the room. Consult with distributor for countermeasure such
as ventilation system, etc.
3.1 Installation Location
1. Install the outdoor unit in a well dried, ventilated environment.
2. Install the outdoor unit where it is in the shade or it will not be
exposed to direct sunshine or direct radiation from high temperature heat
source.
3. Install the outdoor unit where the sound or the discharge air from the
outdoor unit does not affect neighbors or surrounding ventilation. The
operating sound at the rear or right/left sides is 3 to 6dB(A) higher than the
sound at the front side indicated in the technical catalog.
4. Install the outdoor unit in a space with limited access to general public.
5. Check to ensure that the foundation is flat, level and sufficiently
strong. (Perform the foundation work in order to fix firmly the outdoor unit
to avoid inclining, abnormal sound or falling down due to a strong wind or
earthquake.)
6. Do not install the outdoor unit where dust or other contaminations could
block the outdoor heat exchanger.
7. Provide adequate drainage around the foundation. If installing the unit on
a roof or a balcony, provide the additional drainage around the foundation to
prevent water dripping on a person or forming ice in winter.
8. Do not install the outdoor unit where a seasonal wind directly blows to
the outdoor heat exchanger or where strong winds through the tall buildings
directly blows to the outdoor fan.
NOTES:
· Do not install the outdoor unit where there is a high level of oil mist,
flammable gases, salty air or harmful gases such as sulfur and an acid or
alkaline environment.
· Do not install the outdoor unit where the electromagnetic wave is radiated
directly to the electrical box.
· Install the outdoor unit as far from the electromagnetic wave radiator as
possible, at least 3 meters away from it.
Seasonal Wind
Seasonal Wind
Air Outlet Hood
Air Inlet Hood
Snow attaches directly to the heat exchanger.
Provide a base which has approximately twice the height of forecast snow accumulation.
3.2 Service Space and Installation Area
Make the service space when outdoor unit is installed as follows. If the
service spaces for air inlet and outlet are insufficient, it may cause a
performance degradation and some abnormalities due to insufficient air intake.
Additionally, the service space is required for facilitating the maintenance.
(Unit: mm)
Min. 1500 h1
h2
1500
Front Side
Rear Side
500
765
Min. 500 + h 2/2
< Side View >Min. 300 + h 1/2
16
· In the case of no walls on the front side and the rear side, the service space is required as follows.
Front Side: Min. 500mm Rear Side: Min. 300mm Right and Left Sides: Min. 10mm
(In the case
that the field-supplied snow protection food or the air outlet duct is
amounted to the unit, the spaces of min. 50mm are required.)
· If the wall on the front side is over 1,500mm high, the space of (500 +
h2/2) mm for the front side is required.
· If the wall on the rear side is over 500mm high, the space of (300 + h1/2)
mm for the rear side is required.
· When the units are surrounded by walls on more than 2 sides, the space
indicated on the previous page is required.
· For walls on more than 2 sides, secure the service space as shown in the
following figures.
· If the space between the unit and an obstacle above the unit is less than
1,500mm or the space above the unit is closed, set up the duct at the air
outlet side in order to prevent short circuit.
· When there are obstacles above the unit, the four (front, rear, right and
left) sides of the unit shall be open in principle.
1. Walls on 2 Sides
In case that the units are installed adjacent to tall buildings and there are
no walls on 2 sides, the minimum rear side space must be 300mm.
· Single Installation
No limit for side wall height.
(Unit: mm)
Min. 10*1)
Min. 300 (Rear Side Space)
3. Selection of Installation Location
· Multiple / Serial Installation
(Unit: mm) No limit for side wall height.
Min. 200
Min. 300 (Rear Side Space)
Front Side Front Side Min. 400
Min. 300 (Rear Side Space)
Front Side Front Side Min. 400
Min. 500 + h2/2
“” This indicates the direction of the unit (Front Side) when installing the units.
2. Walls on 3 Sides
· Single Installation
(Unit: mm)
Min. 300 + h1/2
Min. 10*1)
Front Side
Min. 500 + h2/2
No limit for side wall height.
Front Side
17
3. Selection of Installation Location
· Multiple / Serial Installation (Unit: mm) < Installation in the Same Direction >
Min.10*1)
Min. 300 + h1/2
Front Side
Min. 500
Min.20*1)
Front Side
Min.20*1)
Min. 500 + h2/2
No limit for side wall height.
Min.10*1) (Side Space)
Front Side
Min. 500 + h2/2
Min. 900
Min.20*1)
Front Side
Min.20*1)
Min. 500 + h2/2
No limit for side wall height.
*1): In the case that the field-supplied snow protection hood or the air outlet duct is adopted, the space of minimum 50mm is required.
3. Walls on 4 Sides
· Single Installation
No limit for side wall height.
Min. 200
Min. 800*2) Open
Front Side
(Unit: mm)
Min. 300 + h1/2 Min. 200 No limit for side wall height.
Min. 500 + h2/2
· Multiple / Serial Installation
(Unit: mm)
Min. 200
No limit for side wall height.
Min. 800*2) Open
Min. 300 + h1/2
Min. 200
Front Side
Min. 900 No limit for side wall height.
Front Side
Min. 800*2) Open
Min. 200 Min. 200
Min. 500 + h2/2
< Rear to Rear Installation >Min. 200 (Side Space)
Front Side
Min. 500 + h2/2 Min. 200
No limit for side wall height.
Min. 800*2) Open
Front Side
Min. 1600
No limit for side wall height.
Min. 800*2) Open
Min. 200 Min. 200
Min. 500 + h2/2
*2): Partly open a wall if the unit is surrounded by walls on four sides.
NOTES:
· Keep the upper side open to prevent mutual interference of inlet and outlet
air of each outdoor unit.
· The figure dimensions indicate sufficient spaces around outdoor units for
operation and maintenance at typical installation conditions as follows. [
Operation Mode: Cooling Operation, Outside Temp.: 35 °C ] In case that the
outdoor unit ambient temperature is higher and also the short circuit is
likely to occur compared to the installation condition, find an appropriate
dimension by calculating air flow current.
· For the multiple installation, 1 group shall consist of 6 outdoor units
(max.). Keep 1-meter interval between each unit group.
1 Group (Max. 6 Outdoor Units)
Min. 1m
18
4. Installation Work 4.1 Transportation and Handling
4.1.1 Transportation
Transport the product as close to the installation location as practical
before unpacking. When using a crane, hang the unit according to the
description of the label attached to the outdoor unit.
WARNING
· Do not hang the unit with the sling belts at the wooden base. CORRECT Sling
Belt
Wooden Base
For Sling Belt and Fork For Fork For Sling Belt
INCORRECT
Sling Belt
Wooden Base
CAUTION
· The unit shall not be handled by one person. Do not use the PP band to move
the unit although the unit is packed by PP band. Additionally, do not touch
the heat exchanger with bare hands. The fin of heat exchanger may cause
injuries.
· Transportation and Storage The corrugated paper frame is not sufficiently
strong. Therefore, follow the instructions below in order to prevent the unit
deformation. Do not step or put any material on the product. It may cause
injury. Apply two sling belts onto the outdoor unit, when lifting it with a
crane.
· Transportation and Wire Rope To protect the unit, do not remove any packing.
Do not stack or put any material on the product. Apply wire ropes on both
sides of the unit as shown in the figure.
Plastic Bands Corrugated Paper Frame
Do not remove corrugated paper frame and plastic bands.
4. Installation Work
Attach four 15mm thick corrugated corner pads as shown.
Banding Wire Wire ropes should be placed on the le /right side of the plastic bands.
Wooden Base
Take special care when hanging or moving the outdoor unit because its center of mass is eccentric as shown in the figure below.
· Center of Gravity
a d
e b Front Side of Unit
Center of Gravity fc
< CNCCLW >(mm)
Model
380 – 415V/50Hz 380V/60Hz
abcde f RAS-080CNCCLW 1795 950 765 690 535 330 RAS-100CNCCLW 1795 950 765 690 535 330 RAS-120CNCCLW 1795 950 765 690 535 330 RAS-140CNCCLW 1795 950 765 690 535 330 RAS-160CNCCLW 1795 1210 765 735 635 345 RAS-180CNCCLW 1795 1210 765 735 635 345 RAS-200CNCCLW 1795 1210 765 735 635 345 RAS-220CNCCLW 1795 1600 765 700 830 320 RAS-240CNCCLW 1795 1600 765 700 830 320
RAS-260CNCCLW 1795 1600 765 700 830 320 RAS-280CNCCLW 1795 1600 765 700 830 320 RAS-300CNCCLW 1795 1600 765 700 830 320
19
4. Installation Work
4.1.2 Handling of Outdoor Unit
· Hanging Method
Hang the unit under packing condition with 2 sling belts as shown in Fig. 4.1.
Do not use a wire rope. Ensure a balance of unit. Check the safety and lift up
the unit gently
in order not to incline the unit.
Sling Belt Corrugated Paper Frame
Do not remove corrugated paper frame and plastic bands.
Do not apply any force to surface. (Both Sides)
Min. 2.0m
Angle of sling belt is more than 60o.
Apply sling belt on the splints or corrugated cardboard pads more than 15mm
thickness. Wooden Base
When using forklift, do not insert forks into the holes on the unit side. The unit may be damaged.
The holes on the unit side
Forks
Do not apply excessive force to the square holes
with forks or other materials. The bottom of the
unit may be deformed.
· Do not push the bottom base by a fork. · Do not use a roller.
Apply sling belt through the long hole.
Fig. 4.1 Hanging Work for Transportation
(kg)
380 – 415V/50Hz, 380V/60Hz HP
8 10 12 14 16 18 20 22 24 26 28 30
Net Weight
187 192 208 212 253 259 259 336 336 355 355 355
Gross Weight
203 208 224 228 273 279 279 359 359 378 378 378
Hang the unit without wooden base with 2 sling belts as shown in Fig. 4.2.
Sling Belt Corrugated Paper Frame
Min. 2.0m
Do not remove corrugated paper frame.
Do not apply any force to surface. (Both Sides)
Angle of sling belt is more than 60o.
Apply sling belt on the splints or corrugated cardboard pads more than 15mm
thickness.
Apply sling belt through the long hole.
Do not apply an excessive force. (Both Sides)
· Wooden Base Removal Method
Remove the hexagon head bolt using the ratchet wrench.
Suspend the unit from the wooden base in its packing with two sling belts.
Ensure safety while hoisting the unit gently to prevent the unit from tipping
over as shown in Fig. 4.3.
Ratchet Wrench
CORRECT
INCORRECT Wrench
Outdoor Unit
Wooden Base
Sling Belt Position Sling Belt Long Hole
CORRECT
Sling Belt Long Hole
INCORRECT
Outdoor Unit Wooden Base
Fig. 4.2 Hanging Work without Wooden Base 20
Fig. 4.3 Wooden Base Removal Method
4. Installation Work
NOTE:
· In case of transportation after unpacking, protect the unit with corrugated paper boards
or cloths.
Outdoor Unit Backrest
Keep distance more than 50mm between the outdoor unit and the backrest.
Mast
Provide concrete foundation as shown in the figure.
Front Side of Unit
Front Side of Unit
Correct
Correct
Foot Foundation
Foot
Min. 100mm
Foundation
Min. 100mm
The concrete foundations are installed along the outdoor unit width direction.
Min. 100mm
Min. 100mm
Min. 100mm (Center of Outdoor Unit)
The concrete foundations are installed along the outdoor unit depth direction.
Fork Outdoor unit is Contacted to Backrest
CAUTION
Outdoor unit is NOT Contacted to Backrest
Do not provide concrete foundation as shown below. The foot of the outdoor
unit may be deformed.
Front Side of Unit
· Prevent the outdoor unit from contacting to the backrest of forklift during
transportation. If not, the heat exchanger fin may be broken due to sudden
starting or stopping.
WARNING
· Do not put any foreign material into the outdoor unit and check to ensure
that nothing exists in the outdoor unit before the installation and test run.
Otherwise, a fire or failure, etc. may occur.
4.2 Outdoor Unit Installation
4.2.1 Foundation
· Concrete Foundations
1. The height of the foundation should be over 150mm above the ground.
2. Provide a drainage around the foundation for smooth drainage.
Incorrect
Foot Foundation
The concrete foundations are installed to each corner of the outdoor unit. In
this case, the foot of the outdoor unit may be deformed.
3. Install the outdoor unit in the front-rear and rightleft direction
horizontally. (Use a level gauge.) Check to ensure that the gradient in four
directions (front, rear, right and left) is within 10mm.
Min. 150 100
Details of Anchor Bolt Installing (Example)
83
5 73 20.5
Anchor Bolt (M12) (Field-Supplied) Nut (Field-Supplied) Washer (Field-
Supplied) Vibration Proof Mat(Field-Supplied)
The corner of the outdoor unit anchoring foot must be located on the vibration
proof mat.
Filling Mortar Hole for Mortar ( 100 x Depth 150) Foundation
Drainage
Min. 100 Drainage (Example) (Width 100 x Depth 20)
(Unit: mm)
Right Side and Left Side
Front Side and Rear Side
4. Provide a strong and correct foundation so that: a. The outdoor unit does not incline. b. Abnormal sound does not occur. c. The outdoor unit will not fall down due to a strong wind or earthquake.
20.5
(729)
20.5
73
624
73
770
21
4. Installation Work
5. When installing the outdoor unit, fix the unit with anchor bolts and vibration proof mat (fieldsupplied). Refer to Fig. 4.4 regarding the location of fixing holes.
· Standard Type (8 to 14 HP)
(Unit: mm)
131 Min.80
688
131
(For Anchor Bolt)
18
Min.80
(For Anchor Bolt)
729
18
Hole for M12 Anchor Bolt (4-18×15 Long Hole)
Vibration Proof Mat 6 Positions (Front and Rear side)
· Standard Type (16 to 20 HP)
(Unit: mm)
18
131 Min.100
948
131
(For Anchor Bolt)
4.2.2 Drain Water Treatment
Rain water is discharged during raining. Comply with the following conditions.
1. Choose a place where good drainage is available, or provide a drain ditch.
2. Do not install the unit over the walkways. Condensation water may fall on
people. In case of installing the unit in such a place, provide the additional
drain pan.
3. (When drain piping is necessary for the outdoor unit, use the drain
adapter set (Optional, DBSTP10A). Do not use drain adapter and drain pan kit
in the cold area. The drain water in the drain pipe may be frozen and then the
drain pipe may crack.
NOTE: Even when the drain adapter set is used, the water may drain slightly
from the screw holes. Provide a second drain pan under the outdoor unit as
necessary.
· Standard Type (8 to 14 HP)
(Unit: mm)
Power Source Wiring Outlet (65 Knockout Hole) Comm. Wiring Outlet (55 Knockout Hole) Comm. Wiring Outlet (33 Knockout Hole)
Hole for Drain (26 x 2 Positions) Positions of Drain Boss (Optional)
Min.80
(For Anchor Bolt)
729
18
Hole for M12 Anchor Bolt (4-18×15 Long Hole)
Vibration Proof Mat 6 Positions (Front and Rear side)
· Standard Type (22 to 30 HP) (Unit: mm)
131 Min.120
669 (For Anchor Bolt)
669
131
(For Anchor Bolt)
*This hole is not used.
Refrigerant Piping Outlet (Knockout Square Hole)
·
Power Source Wiring Outlet (65 Knockout Hole) Comm. Wiring Outlet (55 Knockout
Hole) Comm. Wiring Outlet (33 Knockout Hole)
Standard Type (16 to 20 HP)
(Unit: mm)
Hole for Drain (26 x 2 Positions) Positions of Drain Boss (Optional)
18
Min.80
Hole for Drain (26 x 2 Positions) Positions of Drain Cap (Optional)
*This hole is Refrigerant Piping Outlet not used. (Knockout Square Hole)
729
(For Anchor Bolt)
18
Hole for M12 Anchor Bolt (6-18×15 Long Hole)
Vibration Proof Mat 6 Positions(Front and Rear side)
Fig. 4.4 Position of Anchor Bolts
22
· Standard Type (22 to 30 HP)
Power Source Wiring Outlet (65 Knockout Hole) Comm. Wiring Outlet (55 Knockout
Hole)
Comm. Wiring Outlet (33 Knockout Hole)
4. Installation Work
(Unit: mm) Hole for Drain (26 x 2 Positions) Positions of Drain Cap (Optional)
Hole for Drain (26 x 2 Positions) Positions of Drain Boss (Optional)
Refrigerant Piping Outlet (Knockout Square Hole)
*This hole is not used.
Fig. 4.5 Position of Drain Water Treatment
· Drain adapter (Optional Parts) The drain adapter is for the drain pipe connection in order to use outdoor unit bottom base as a drain pan.
Name Drain adapter
Model DBS-TP10A
Model Parts Name
DBSTP10A
Drain adapter Drain Cap Rubber Cap
Material / Color
PP / Black
PP / Black CR / Black
Q’ty
Application
2
Connecting for Drain Piping
2
Embolization for Drain Hole
4 Sealing for Boss and Cap
NOTE:
When installing the unit above a passage way, drain water sometimes turns to
ice on a cold morning. Therefore, avoid discharging the water into places
which people often pass through, because it is slippery.
When drain piping is necessary for the outdoor unit, use the drain adapter set (Optional, DBS-TP10A). Do not use drain adapter and drain pan kit in the cold area. The drain water in the drain pipe may be frozen and then the drain pipe may crack.
23
5. Refrigerant Piping Work
5. Refrigerant Piping Work
WARNING
· Use the specified non-flammable refrigerant R410A to the outdoor unit in the
refrigerant cycle. Do not charge material other than R410A into the unit such
as hydrocarbon refrigerants (propane or etc.), oxygen, flammable gases
(acetylene or etc.) or poisonous gases when installing, maintaining and moving
the unit. These flammables are extremely dangerous and may cause an explosion,
fire, and injury.
· Check to ensure that no pressure exists inside the stop valve before
removing the flange.
· Make sure that the refrigerant leakage test is performed. The refrigerant
(Fluorocarbon R410A) for this unit is nonflammable, non-toxic and odorless.
However, if the refrigerant leaks and contacts fire, toxic gas will generate.
Also, because the fluorocarbon is heavier than air, the floor surface will be
filled with it, which could cause suffocation.
· For installation, firmly connect the refrigerant pipe before the compressor
starts operating. For maintenance, relocation and disposal, remove the
refrigerant pipe after the compressor stops. If the compressor is operated
under the condition that the stop valves are opened without refrigerant pipe,
it may cause abnormal high pressure in refrigerant cycle and may cause an
explosion, fire or injury.
· Before performing any brazing work, check to ensure that there is no
flammable material around. If not, it may cause a fire.
· If the indoor unit is installed in a small room and the refrigerant gas
leakage occurs, the leaked refrigerant gas fills the room and it may cause
suffocation. Do not exceed the maximum permissible concentration of the
refrigerant gas in the room. Consult with your distributor for an appropriate
ventilation system, etc.
· The design pressure for this product is 4.15MPa. The pressure of refrigerant
R410A is 1.4 times higher than that of refrigerant R407C. The thickness of
copper pipe differs
24
depending on its materials, so use the specified piping. If the specified
materials are not used, it may cause explosion, injury, leakage, or fire.
CAUTION
· Ensure to connect the piping among the units in the same refrigerant cycle.
· Wear leather gloves when handling the refrigerant. If the refrigerant
splashes directly to hands, it may be the cause of frostbite.
· Do not apply excessive force to the flare nut when tightening it. Otherwise,
the flare nut may crack due to aged degradation and refrigerant leakage may
occur. Use the specified tightening torque.
NOTICE
· The refrigerant R410A is adopted. The refrigerant R410A and the refrigerant
oil tend to be affected by foreign matters such as moisture, oxide film, or
fat. Perform the installation work with care to prevent moisture, dust or
different refrigerant from entering the refrigerant cycle. Otherwise, foreign
materials may get mixed into the cycle from such parts as expansion valve and
the operation may be unavailable.
· Perform the drain piping work in order to drain water securely. If not, the
drain water can flow back to the unit and it may cause leakage to the room.
5.1 Piping Materials
1. Prepare locally-supplied copper pipes. 2. Use the phosphorus-deoxidized
copper pipe
for refrigerant piping, which is based on the JIS H3300 “Copper and copper
alloy seamless pipes and tubes.” 3. Select the piping size from Tables 5.1 and
5.2. Pay attention to pipe selection, because the thickness of copper pipe
differs depending on its material. 4. Use clean copper pipes. Make sure there
is no dust and moisture inside the pipes. Blow nitrogen or dry air into the
pipes to remove any dust or foreign materials before connecting pipes. Do not
use any tools which produce a lot of swarf such as a saw or a grinder. 5. Take
special care to prevent contaminations and
moisture from entering the pipe interior during the piping work. 6. Avoid performing the piping connection work for outdoor unit in the rain.
· Cautions for Refrigerant Pipe Ends
When installing pipe through the wall, secure a cap at the end of the pipe.
Correct
Incorrect
Do not place the pipe directly on the ground.
Correct
Incorrect
Hole
Hole
Attach a cap or vinyl tape.
Attach a cap or vinyl tape.
Correct
Incorrect
Rain water can enter.
Attach a cap or vinyl bag with rubber band.
· Brazing Work
1. The brazing work must be performed by an authorized installer in order to
prevent any trouble.
2. For piping connection, perform securely non-oxidation brazing with
nitrogen substitution. If brazing the pipes without the nitrogen substitution,
a large amount of oxidized scale will be generated in the pipes. This oxidized
scale may cause clogging in the expansion valve, solenoid valve, accumulator
and compressor, which can prevent the unit from operating properly. Do not use
field-supplied antioxidant, etc., which may corrode pipes and deteriorate the
refrigerant oil.
Brazing Part Nitrogen Gas
Pressure Reducing Valve (Stop Valve)
Nitrogen Gas Pressure < 0.02 MPa
Piping Connection on-site
Pipe Valve (f6.35)
NOTE:
Cover the gap with taping or a rubber plug to prevent air from entering the pipe interior.
Nitrogen Gas
Do not cover the outlet. If the inner pressure exceeds
atmospheric pressure, a pinhole may generate and
the refrigerant gas will leak from the brazing part.
NOTES:
· Make sure to use nitrogen. Nitrogen gas pressure shall be 0.02 MPa or less.
DO NOT use the following gases.
Oxygen: flammable and causes oxidation degradation of the refrigerant oil.
Carbon Dioxide: may cause decrease in drier performance.
Freon Gas: emits harmful gases if exposed to fire.
· Make sure to use the pressure reducing valve. · Do not use field-supplied
antioxidant.
5. Refrigerant Piping Work
3. Use a quality brazing filler metal specified in JIS. Select a flux whose
chlorine concentration is low.
4. Remove the flux completely after the brazing work.
NOTE:
When the brazing work is performed, perform brazing to minimum portion by
appropriate temperature to suppress generating oxidized scale.
· Cautions for Piping Connection Work
1. Connect the indoor and the outdoor units with refrigerant pipes. Fix the
pipes and prevent the pipes from contacting weak portions such as wall,
ceiling, etc. (Otherwise, abnormal sound may be heard due to vibration of the
piping.) NOTE:
When on-site piping with joint such as elbow or socket is buried, provide a
service access door to facilitate the check for connecting part. 2. Check that
there are no scratch, swarf, deformation, gap, etc. at the flaring part,
before the connecting work. 3. Apply refrigerant oil slightly on the sheet
surface of the pipe and flare nut before the flaring work. And then tighten
the flare nut with the specified tightening torque using two spanners. Perform
the flaring work on the liquid piping side before the gas piping side. Check
that no gas leakage occurred after the flaring work. NOTE: Refrigerant oil is
field-supplied. [Ethereal Oil: FVC68D (Idemitsu Kousan Co. Ltd.)] Apply
Refrigerant Oil.
Do not apply the refrigerant oil to the outside of the flaring part.
4. Be sure to use the accessory flare nuts for indoor unit connections.
5. In case that the temperature and humidity inside the ceiling exceeds
27°C/RH80%, apply additional insulation (approx. 10mm in thickness) to the
accessory insulation. It prevents dew condensation on the surface of the
insulation (refrigerant pipe only).
6. Perform the air-tight test (4.15MPa for the test pressure).
7. Perform cold insulation work by insulating and taping the flare connection
and reducer connection. Also insulate all the refrigerant pipes.
25
5. Refrigerant Piping Work
· When tightening the flare nut, use two spanners.
Required Tightening Torque (JIS B8607)
Pipe Size (mm)
Tightening Torque (N·m)
6.35
(1/4)
14 to 18
9.52
(3/8)
34 to 42
12.7
(1/2)
49 to 61
15.88 (5/8)
68 to 82
19.05
(3/4)
100 to 120
Do not put two spanners here. Refrigerant leakage may occur.
Two Spanners Work Tightening Work for Stop Valve (Liquid)
Table 5.1 Piping Size of Outdoor Unit
<2 Pipes System>(Standard Type)
Outdoor Unit HP
Gas
(mm) Liquid
8
19.05
9.52
10
22.2
9.52
12, 14
25.4
12.7
16
28.58
12.7
18 – 24
28.58
15.88
26 – 34
31.75
19.05
36 – 54
38.1
19.05
56 – 66
44.45
19.05
68 – 72
44.45
22.2
74 – 88
50.8
22.2
90 – 96
50.8
25.4
98 – 112
54.0
25.4
114 – 120
54.0
28.58
Table 5.2 Piping Size of Indoor Unit
Indoor Unit HP
1.5 or less 2.0, 2.3 2.5 to 6.0 8.0 10.0 16.0 20.0
Diameter (mm)
Gas Pipe 12.7
Liquid Pipe 6.35 *1
12.7 *2
6.35 *1
15.88
9.52
19.05
9.52
22.2
9.52
28.58
12.7
28.58
15.88
26
1. When the liquid piping length is longer than 15m, use 9.52 pipe and a reducer (field-supplied).
2. As for some of the indoor unit types, if 12.7 pipe is not available, 15.88 pipe should be used. Make sure to check the indoor unit specifications.
· Piping Thickness and Material Use the pipe as below. The thickness of
refrigerant pipe differs depending on design pressure. For copper pipe, pay
attention to pipe selection, because the piping thickness differs depending on
its material.
Outer Diameter
6.35 9.52 12.7 15.88
19.05
22.2 25.4 28.58 31.75 34.92 38.1 41.28 44.45 50.8 54.0
(mm)
R410A
Thickness
Material
0.8
O material
0.8
O material
0.8
O material
1.0
O material
1.2
O material
1.0
1/2H material
1.0
1/2H material
1.0
1/2H material
1.0
1/2H material
1.1
1/2H material
1.2
1/2H material
1.35
1/2H material
1.4
1/2H material
1.55
1/2H material
1.5
1/2H material
1.5
H material
5.2 Flaring and Joint
· Flaring Dimension Perform the flaring work as shown below.
(mm)
90° ± 2° 45° ± 2°
A
Diameter (d)
+0 A -0.4 R410A
6.35
9.1
9.52
13.2
R0.4 ~ R0.8
12.7
16.6
15.88
19.7
d
19.05
– *1
*1. It is impossible to perform the flaring work with 1/2H material. In this case, use an accessory pipe (with a flare).
· Joint Selection If 1/2H material is used, the flaring work cannot be performed. In this case, use a joint selected from the table below.
< Minimum Thickness of Joint (mm) >
Diameter
R410A
6.35
0.5
9.52
0.6
12.7
0.7
15.88
0.8
19.05
0.8
22.2
0.9
25.4
0.95
28.58
1.0
31.75
1.1
34.92
1.2
38.1
1.35
41.28
1.45
44.5
1.55
50.8
1.65
54.0
1.75
NOTE:
· Do not use a thin joint other than the ones in the table.
B
< Flare Nut Dimension B (mm) >
Flare Nut
Diameter 6.35 9.52 12.7 15.88 19.05
R410A 17 22 26 29 36
· Processing at Brazing Connection To prevent gas leakage at the brazing
connection, refer to the table for the insertion depth and the gap for joint
pipe.
B
ID IA
(mm)
Diameter (D)
5 D< 8 8 D < 12 12 D < 16 16 D < 25 25 D < 35 35 D < 45 45 D
Min. Insertion Depth (B) 6 7 8 10 12 14 16
Gap (A – D) 0.05 – 0.35
0.05 – 0.45
0.05 – 0.55 0.05 – 0.6
5. Refrigerant Piping Work
5.3 Caution about Outdoor Unit Installation
When the installation and piping work for the multiple outdoor units are
performed, it is required that the arrangement for outdoor units and piping
length be determined. Perform securely the installation work according to the
following restrictions. If the arrangement for outdoor units is incorrect, it
may cause flow back of the refrigerant and result in failure of outdoor unit.
<Restrictions for 2 and 3 Unit Combination>
1. For 2 and 3 outdoor units combination, align the outdoor units from
largest capacity to smallest as A > B > C and outdoor unit “A” should be
connected to the piping connection kit 1.
2. The piping length between the piping connection kit 1 and the outdoor unit
should be La < Lb < Lc < 25m.
3. For maintenance, attach “Main unit label” to the service cover (back side
surface) of the outdoor unit “A”.
A >B>C
Outdoor Unit A
Outdoor Unit Outdoor Unit
B
C
Piping Outlet Direction
Indoor Unit
Side
Piping Connection Kit 2
Lb
Piping
La
Connection Kit 1
Lc
: Keep the straight-line distance of 500mm or more for piping a er the piping connection kit.
C <B < A
Outdoor Unit Outdoor Unit
C
B
Outdoor Unit A
Piping Outlet Direction
Piping Connection Kit 2
La
Lc
Lb
Indoor Unit Side
Piping Connection Kit 1
: Keep the straight-line distance of 500mm or more for piping a er the piping
connection kit.
27
5. Refrigerant Piping Work
<Restrictions for 4 Unit Combination>
1. For 4 outdoor unit combination, align the outdoor units from largest
capacity to smallest as A > B > C > D. The outdoor units “A” and “B” should be
connected to the piping connection kit 2 and the outdoor units “C” and “D”
should be connected to the piping connection kit 3.
2. The piping length between the piping connection kit 1 and each outdoor
unit should be La < Lb < Lc < Ld < 25m.
3. For maintenance, attach the main unit label to the service cover (back
side surface) of the outdoor unit “A”.
A > B> C > D
Piping Outlet Direction
Outdoor Unit A
Outdoor Unit Outdoor Unit Outdoor Unit
B
C
D
Indoor Unit Side
La
Lb
Lc
Ld
5.4.1 Removing of Closing Pipes
Step1. Make sure that all the valve stems are closed completely.
Step2. Connect the charging hose to the service port and release the gas
inside the piping from the gas pipe.
Step3. Cut the end of the closing pipe and check that no gas exists inside the
gas pipe.
Step4. Remove the stop valve cover. Step5. Remove the closing pipe from the
brazing
portion with a burner. Pay attention to the flame from the burner not to burn
the stop valve body.
Liquid Valve
Service Port Gas Valve
Stop Valve Cover (Read the precautions.)
Piping Connection Kit 1
Piping Connection Kit 2
Piping Connection Kit 3
: Keep the straight-line distance of 500mm or more for piping a er the piping connection kit.
D<C< B < A
Outdoor Unit Outdoor Unit Outdoor Unit
D
C
B
Outdoor Unit A
Ld
Lc
Lb
La
Piping Outlet Direction
Indoor Unit Side
Cutting Portion (6.35 Pipe) Cut Here
End of Closing Pipe (6.35) Closing Pipe
Heat Exchanger Fin Heat Exchanger
Metal Plate for Protection
Closing Pipe
Liquid Valve Gas Valve (Body)
Field Piping Connecting Portion of Gas Valve
Valve Stay
Burner
Piping Connection Kit 3
Piping Connection Kit 2
Piping Connection Kit 1
: Keep the straight-line distance of 500mm or more for piping a er the piping connection kit.
5.4 Piping Connection Work
Comply with the restrictions for refrigerant piping (permissible length,
height difference) in item 5.4.2 Piping Connection Method. If not, the outdoor
unit may be damaged or fail. The stop valves shall be closed completely
(factory setting) when the refrigerant piping connection is performed. Do not
open the stop valves until all the refrigerant piping connections, air-tight
test and vacuuming have been completed.
28
Fig. 5.1 Brazing of Closing Pipe
CAUTION
· Ensure that there is no gas inside the pipe when removing the closing pipe.
Otherwise, the pipe may be blown out and it may lead to injury.
· Do not expose surrounding parts and the oil return pipe of the compressor to
flames when torch is used. If the oil return piping is exposed to the fire,
high temperature oil will spurt and cause a fire or injury.
5. Refrigerant Piping Work
· The details of stop valves is as follows.
Type HP Tightening Torque (N·m) Valve Type
8 – 14
33 – 42
A
Standard 16 – 20
50 – 62
B
22 – 30
68 – 84
C
Do not put two spanners here. Refrigerant leakage may occur.
Hexagonal Wrench Wrench Size:10mm
Cap Tightening Torque: 42.0 – 48.0 N-m
Spindle Valve Counterclockwise…Open Clockwise……………Close Tightening Torque:
22.0 – 28.0 N-m
Check Joint for Service Port
Tightening Torque: 9.0 – 14.0 N-m
Refrigerant Pressure
Two Spanners Work Tightening Work for Stop Valve (Liquid)
Do not put two spanners here.
A
B
C
Flare Nut Flare Nut
Flare Nut
Check Joint for Service Port
Only the charging hose can be connected. Tightening Torque: 14.0 – 18.0 N-m
Cap Tightening Torque: (b) N-m
Hexagonal Wrench To open or close spindle valve
Wrench Size: (e)
O-ring
Spindle Valve
Counterclockwise…Open Clockwise……………Close Tightening Torque: (c) N-m
Refrigerant Piping
Refrigerant Pressure
Flare Nut Tightening Torque: (d) N-m
Put two spanners here.
CAUTION · Do not apply an excessive force to the
spindle valve after fully opening the spindle. The back seat construction is
not provided.
· At the test run, fully open the spindle. If it is not fully opened, the
devices will be damaged.
Outdoor Unit (Base Unit)
Tightening Torque (N·m)
Wrench
Cap Spindle Valve Flare Nut Size
(b)
(c)
(d) (e) (mm)
8 – 14 33.0 – 42.0 7.0 – 9.0 33.0 – 42.0 4
Standard Type
16 – 20
33.0 – 42.0
7.0 – 9.0 50.0 – 62.0
4
22 – 30 50.0 – 62.0 9.0 – 11.0 68.0 – 84.0 5
CAUTION
· Do not apply excessive force to the spindle valve after fully opening the
spindle. The back seat construction is not provided.
· At the test run, fully open the spindle. If it is not fully opened, the
devices will be damaged.
29
5. Refrigerant Piping Work
5.4.2 Piping Connection Method
Perform the piping connection work for each outdoor unit. NOTE:
· Ensure that the refrigerant pipe should be connected to the same refrigerant
cycle unit.
Prepare the refrigerant pipe in the field for the piping work. Refer to Fig. 5.2 for the position of piping connection.
Unit (mm)
Communication Wiring Outlet (I33 Knockout Hole)
Communication Wiring Outlet
(I55 Knockout Hole)
K
65
Gas Piping Connection A
J
Liquid Piping Connection B
Piping Cover
E (Liquid Piping Connection) F (Gas Piping Connection) 293 288 133 100
C
G (Liquid Piping Connection)
D
H (Gas Piping Connection)
Power Source Wiring Outlet
I
(I65 Knockout Hole)
Gas Piping and Liquid Piping Outlet
(Knockout Square Hole)
127 This hole is not used.
The figures illustrate the examples of a small cabinet.
< CNCCLW >Model
Piping Diameter
Dimension (mm)
Gas Liquid A
B
C
DE
F
GH
I
J
K
RAS-080CNCCLW 19.05 9.52 RAS-100CNCCLW 22.2 9.52 RAS-120CNCCLW 25.41 12.7 22.2 9.52 269 331 268 163 117 131 240 225 305 RAS-140CNCCLW 25.41 12.7 RAS- 160CNCCLW 28.58 12.7
RAS-180CNCCLW 28.58 15.88 25.4 12.7 178 239 263 160 112 130 147 132 212
RAS-200CNCCLW 28.58 15.88
RAS-220CNCCLW 28.58 15.88
RAS-240CNCCLW 28.58 15.88
RAS-260CNCCLW 31.752 19.05 28.58 15.88 177 239 259 160 132 152 147 132 212 RAS-280CNCCLW 31.752 19.05 RAS-300CNCCLW 31.75*2 19.05
1. If 25.4 piping is not available, use 28.58 piping and a reducer (field-supplied). 2. If 31.75 piping is not available, use 34.93 piping and a reducer (field-supplied).
Fig. 5.2 Position of Piping Connection
30
· Piping Direction Fix the pipes adequately in order to avoid vibration and
excessive force to the valve.
Step1. The pipes can be installed in four directions (front, rear, right or
bottom side). For vibration protection, properly fix the piping connection and
check that no excessive force is applied to the stop valve.
Front Side
Bottom Side
Bottom Base Rear Side
Step2. Operation of the stop valve should be performed according to item
5.4.1.
Step3. Connect the pipes according to Fig. 5.2. Step4. Completely seal the
penetration part at
the bottom of the pipes with insulation in order to prevent rain water from
entering the conduit.
For Piping from Bottom Base
Liquid Pipe
Communication Wiring
Gas Pipe
Power Source Wiring
Cover gaps with packings (field-supplied). Install accessory rubber bushes to
the wiring outlets.
For Piping from Front or Rear Side Piping Cover Cover gaps with packings
(field-supplied). Install accessory rubber bushes to the wiring outlets.
Piping Cover
Power Source Wiring
Liquid Pipe
Communication Wiring Gas Pipe
5. Refrigerant Piping Work
NOTICE
· After removing the pipes and completing insulation work, cover the gap between the pipe cover and the pipes with packing (field-supplied). If the gap is not covered, the unit may be damaged if snow, rain water or animals enter the unit.
5.4.3 Piping Connection
After connecting the pipes, remove the caps of stop valves for gas and liquid. Tighten the open-close spindle in the closing direction according to the following tightening torque.
Step1. Make sure that the stop valves are closed completely.
Step2. Protect the compressor and sound-proof cover with a metal plate when
brazing the gas pipe as shown in Fig. 5.1. Pay attention to the flame from the
burner not to burn the stop valve body.
Step3. Connect the indoor unit and outdoor units with refrigerant piping. Fix
the pipes and take special care not to contact with weak portions such as
wall, ceiling, etc. (Otherwise, abnormal sound may be heard due to vibration
of the piping.)
NOTE:
· When on-site piping with joint such as elbow or socket is buried, provide a
service access door to facilitate the check for connecting part.
Step4. As for the flaring work of the field pipe, use the specified tightening
torque in Table 5.3. Put nitrogen gas into the pipe when brazing the piping.
Step5. Insulate the gas pipe and liquid pipe completely.
Step6. Mount the piping cover equipped with the outdoor unit after the piping
connection. If not, the unit may be damaged due to snow or rain water entering
the piping.
Table 5.3 Tightening Work of Flare Nut
Required Tightening Torque
(JIS B8607)
Pipe Size mm (in)
Tightening Torque (N·m)
6.35 9.52 12.7 15.88 19.05
(1/4)
14 to 18
(3/8)
34 to 42
(1/2)
49 to 61
(5/8)
68 to 82
(3/4)
100 to 120
31
5. Refrigerant Piping Work
· When connecting the indoor unit and outdoor unit refrigerant pipes, the
refrigerant pipes must be supported appropriately. Do not let them come into
contact with the weak strength portion of a wall or a ceiling. If not, it may
cause abnormal sound due to piping vibration.
· Precautions during installing and fixing the pipes.
Outdoor Unit
Piping Support Parts (to support pipes at appropriate intervals)
Fireproof Compartment Construction
Indoor Unit
Multi-Kit Install multi-kits horizontally.
CORRECT
within + 15o
INCORRECT
< Supporting Liquid Piping and Gas Piping >Gas Piping
Piping Supporting Parts
Liquid Piping
NOTE: Temperature changes in refrigerant during operation of the unit can
cause pipes to expand or contract. Tying the gas piping and liquid piping
together with taping may cause piping deformation.
Example: Recommended
From each Indoor Unit to Multi-Kit, use hard copper pipes that bend to prevent kinking.
Hard Copper Piping will expand and contract due to temperature changes in piping.
Multi-Kit
Connection Pipe
Bending Pipe
Outdoor Unit Multi-Kit Install Horizontally
Indoor Unit
NOTICE:
When on-site piping is installed using so or hard copper, make sure that the
piping is installed to allow for movement of the piping. Temperature changes
cause contraction and expansion of the piping.
NOTE:
· When on-site piping with joint such as elbow or socket is buried, provide a
service access door to facilitate a check of connecting parts.
CAUTION
· Do not apply excessive force to the flare nut when tightening it. Otherwise, the flare nut may crack due to aged deterioration and refrigerant leakage may occur. Use the specified tightening torque.
· Details of Stop Valve Piping Connection
< CNCCLW >RAS-080CNCCLW
RAS-100CNCCLW
Stop Valve (Liquid)
Flaring
Liquid Pipe (Field-Supplied)
Stop Valve (Gas)
Stop Valve (Liquid)
Flaring
90o Elbow B
Liquid Pipe
(Field-Supplied) (Field-Supplied)
Stop Valve (Gas)
90o Elbow A (Field-Supplied)
Accessory Pipe (Gas Line)
Gas Pipe (Field-Supplied)
RAS-120CNCCLW
RAS-140CNCCLW
Stop Valve (Liquid)
Flaring Accessory Pipe (Liquid Line)
90o Elbow A (Field-Supplied)
Stop Valve (Gas)
Stop Valve (Liquid)
90o Elbow B (Field-Supplied)
Flaring
Liquid Pipe (Field-Supplied)
Accessory Pipe (Gas Line)
Stop Valve (Gas)
90o Elbow A (Field-Supplied)
Gas Pipe (Field-Supplied)
RAS-160CNCCLW
RAS-180, 200CNCCLW
Stop Valve (Liquid)
Flaring
Liquid Pipe (Field-Supplied)
Stop Valve (Gas)
Stop Valve (Liquid)
90o Elbow B (Field-Supplied)
Accessory Pipe (Gas Line)
Flaring
Accessory Pipe (Liquid Line) 90o Elbow A (Field-Supplied)
Stop Valve (Gas)
90o Elbow B (Field-Supplied)
Accessory Pipe (Gas Line)
RAS-220, 240CNCCLW RAS-260, 280, 300CNCCLW
Stop Valve (Liquid)
Flaring
Liquid Pipe (Field-Supplied)
Stop Valve (Gas)
Stop Valve (Liquid)
Flaring
90o Elbow A (Field-Supplied)
Gas Pipe (Field-Supplied)
Accessory Pipe (Liquid Line) 90o Elbow A (Field-Supplied)
Stop Valve (Gas)
90o Elbow B (Field-Supplied)
Accessory Pipe (Gas Line)
NOTES:
· Ensure that the closing pipe of the gas stop valve is removed firstly.
· Refer to item 5.2 for the flaring work.
NOTICE
· When connecting the outdoor unit gas stop valve and the field-supplied refrigerant pipe, do not apply excessive force to the stop valve pipe as illustrated below. This may loosen the stop valve spindle.
32
5. Refrigerant Piping Work
· Construction Example The following figures show the examples of 3 unit
combination. Regarding the piping work for Combination Unit, refer to
Installation and Maintenance Manual attached to the piping connection kit.
Front Side Piping Connection
Liquid Piping (Field-Supplied)
Piping Connection Kit 1 (Liquid)
Accessory Pipe (L-Shape)
Perform the piping connection between outdoor units according to this figure.
Outdoor Unit A
Gas Piping (Field-Supplied)
Piping Connection Kit 1 (Gas)
Accessory Pipe (L-Shape)
Outdoor Unit B
Accessory Pipe (L-Shape)
Liquid Piping (Field-Supplied)
Gas Piping (Field-Supplied)
Piping Connection Kit 2 (Gas)
Accessory Pipe (L-Shape)
Gas Piping (Field-Supplied)
Piping Connection Kit 2 (Liquid)
Liquid Piping (Field-Supplied)
Outdoor Unit C Foundation
View from P
Connecting Piping (Field-Supplied)
Keep the same heights when removing the gas piping and the liquid piping from the piping cover.
min.500mm
Connecting Piping (Attached to Piping Connection Kit)
Downward Piping Connection
Perform the piping connection between outdoor units according to this figure.
Base (Field-Supplied)
Gas Piping (Field-Supplied)
Liquid Piping (Field-Supplied)
Accessory Pipe (Z-Shape)
Outdoor Unit A
Liquid Piping (Field-Supplied)
Accessory Pipe (Z-Shape)
Outdoor Unit B
Liquid Piping (Field-Supplied)
Outdoor Unit C
Piping Connection Kit 1 (Liquid)
Piping Connection Kit 1 (Gas)
Accessory Pipe (L-Shape)
Gas Piping (Field-Supplied)
Piping Connection Kit 2 (Liquid)
Accessory Pipe (L-Shape)
Piping Connection Kit 2 (Gas)
Gas Piping (Field-Supplied)
NOTE:
· The figure shows the case that the refrigerant pipes are pulled out from the front side piping cover. They can be also pulled out from the bottom base hole. 33
5. Refrigerant Piping Work
5.5 Piping Work between Outdoor Units
The optional piping connection kit is required to combine base units. It is
NOT required for the base units.
Indoor Unit Side
Outdoor Unit A
Outdoor Unit B
Outdoor Unit C
Outdoor Unit D
LA
LB
LC
LD
< Standard Type: RAS-080 to H20CNCCLW>Applicable Outdoor Unit
Outdoor Outdoor Unit Unit
HP Number
Model
32 – 48 2 MC-NP21SA1
50 – 60 2
MC-NP22TA
62 – 90 3
MC-NP31TA
92 – 120 4
MC-NP40TA
Piping Set
Remarks
1
for Gas: 1 for Liquid: 1
1
for Gas: 1 for Liquid: 1
1
for Gas: 2 for Liquid: 2
1
for Gas: 3 for Liquid: 3
Select the pipe size according to items 5.5.1 to 5.5.4 “Piping Size between Outdoor Units”. For refrigerant piping work, the optional piping connection kit is required to branch the pipe between outdoor units. The arrangement for outdoor units should be determined depending on the piping direction when the refrigerant piping work and installation work are planned. When the outdoor unit is installed, perform the installation work according to the following restrictions.
1. Piping length between piping connection kit 1 and each outdoor unit should be LA < LB < LC < 25m, LD – LA 10m, LC – LA 10m, LB – LA 10m. Keep the straight-line distance of 500mm or more after the piping connection kit 1.
Piping Connection Kit 1
Piping Connection Kit 2
Piping Connection Kit 3
Keep the straight-line distance of 500mm or more for piping a er the piping connection kit.
Outdoor Unit A
Outdoor Unit B
Outdoor Unit C
Upstream Side
Outdoor Unit D
The height difference between outdoor units must be 2.0m or less. If it exceeds 100mm, follow 7.*1
Indoor Unit Side
Piping
Piping
Connection Kit 2
Connection Kit 1
Piping Connection Kit 3
*1. Refer to 7. on page 36.
2. Place the piping connection kit lower than the outdoor unit piping
connection. In case that the piping connection kit is placed higher than the
outdoor unit piping connection, keep 300mm (max.) between the piping
connection kit and the bottom of the outdoor unit. Also, provide the oil trap
(min. 200mm) for the gas piping between the piping connection kit and the
outdoor unit.
CORRECT
Outdoor Unit A
Indoor Unit Side LA
Outdoor Unit B
Outdoor Unit C
LB
LC
Indoor Unit Side INCORRECT
Piping Connection Kit 1
Keep the straight-line distance of 500mm or more for piping a er the piping connection kit.
Outdoor Unit A
Indoor Unit Side Piping Connection Kit 1
Piping Connection Kit 2
Outdoor Unit B
Upstream Side
Outdoor Unit C
The height difference between outdoor units must be 2.0m or less. If it exceeds 100mm, follow 7.*1
Piping Connection Kit 2
Indoor Unit Side The refrigerant oil is stagnated to the unit stopped.
CORRECT
Oil Trap Min. 200mm
Indoor Unit Side
Oil Trap Min. 200mm
Max. 300mm
Max. 300mm
Oil Trap Min. 200mm
Max. 300mm
34
CORRECT
Indoor Unit Side
INCORRECT
Indoor Unit Side
The refrigerant oil is stagnated to the unit stopped.
CORRECT
Oil Trap Min. 200mm Indoor Unit Side
Max. 300mm
Oil Trap Min. 200mm
Max. 300mm
Oil Trap Min. 200mm
Oil Trap Min. 200mm
Max. 300mm
Max. 300mm
The refrigerant oil stagnates in the stopped outdoor unit during system
operation.
3. Install an oil trap for the gas piping when the piping length between the
piping connection kits, or the outdoor unit and the piping connection kit is
2m or more to prevent any accumulation of refrigerant oil.
· Less than 2m
CORRECT
Indoor Unit Side
Less than 2m
· 2m or more
CORRECT
Less than 2m
Indoor Unit Side
Oil Trap Min. 200mm
Oil Trap Min. 200mm
Less than 2m
2m or more
Less than 2m
25m or less
2m or more
5. Refrigerant Piping Work
· Less than 2m
CORRECT
Indoor Unit Side
Less than 2m
Less than 2m Less than 2m
· 2m or more
CORRECT
Less than 2m
Indoor Unit Side
Oil Trap Min. 200mm
Oil Trap Min. 200mm
Oil Trap Min. 200mm
Less than 2m
Less than 2m
2m or more
Less than 2m
2m or more
25m or less
Less than 2m
2m or more
4. Place the outdoor unit pipe horizontally or with the pipe slanted downward towards the indoor unit side so that accumulation of refrigerant oil may not occur in the pipe.
INCORRECT
Indoor Unit Side
Refrigerant oil accumulates in the pipe. CORRECT
Indoor Unit Side
INCORRECT
Indoor Unit Side
CORRECT
Indoor Unit Side
Refrigerant oil accumulates in the pipe.
35
5. Refrigerant Piping Work
5. For servicing, in case that the pipe is placed frontward of the outdoor
unit, secure min. 500mm between the outdoor unit and piping connection kits.
(When the compressor is replaced, a space of min. 500mm is required.)
Outdoor Unit Outdoor Unit Outdoor Unit
INCORRECT
100mm or more
Outdoor Unit A
Outdoor Unit B
Min. 500mm
Piping Connection Kit
Piping Connection Kit
Outdoor Unit Outdoor Unit Outdoor Unit Outdoor Unit
Min. 500mm
Piping Connection Kit
Piping Connection Kit
6. Direction of Piping Connection Kit Place the piping connection kit parallel to the ground (the slope must be within +15°) as shown in the figure.
CORRECT
INCORRECT
within + 15o
NOTICE
· The refrigerant system may be damaged if the slope of the piping connection
kit exceeds ±15°.
7. When the height difference between the outdoor units exceeds 100mm, there
are restrictions depending on the number of connected outdoor units. Incorrect
positioning of the outdoor units may cause failure of outdoor units due to
flowing back of the refrigerant. a. Two Outdoor Unit Combination Outdoor Unit
A must be lower than Outdoor Unit B.
CORRECT
Outdoor Unit A
Outdoor Unit B
Max. 2m
36
b. Three Outdoor Unit Combination Two outdoor units must be lower than the
third outdoor unit.
CORRECT
Outdoor Unit A
Outdoor Unit B
Outdoor Unit C
Max. 2m
NOTE: The example shows Outdoor Units A and B
are lower than Outdoor Unit C.
INCORRECT
Outdoor Unit A
Outdoor Unit B
Outdoor Unit C
100mm or more
c. Four Outdoor Unit Combination Three outdoor units must be lower than the
fourth outdoor unit.
CORRECT
Outdoor Unit A
Outdoor Unit B
Outdoor Unit C
Outdoor Unit D
Max. 2m
NOTE: The example shows Outdoor Units A , B and C
are lower than Outdoor Unit D.
INCORRECT
Outdoor Unit A
Outdoor Unit B
Outdoor Unit C
Outdoor Unit D
100mm or more
5.5.1 Piping Size between Outdoor Units (Base Unit)
· Standard Type: RAS-080 to 300CNCCLW
Outdoor Unit
5. Refrigerant Piping Work
a To Indoor Units
Refrigerant Piping
Standard Type: RAS-080 to 300CNCCLW
(mm)
Model
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
080CNCCLW 100CNCCLW 120CNCCLW 140CNCCLW 160CNCCLW 180CNCCLW 200CNCCLW
Gas 19.05
22.2
25.4*1
25.4*1
28.58
28.58
28.58
Piping Size a
Liquid 9.52
9.52
12.7
12.7
12.7
15.88
15.88
Model Piping Size a
RAS-
RAS-
RAS-
RAS-
RAS-
220CNCCLW 240CNCCLW 260CNCCLW 280CNCCLW 300CNCCLW
Gas 28.58
28.58
31.75*2
31.75*2
31.75*2
Liquid 15.88
15.88
19.05
19.05
19.05
1. If 25.4 piping is not available, use 28.58 piping and a reducer (field-supplied). 2. If 31.75 piping is not available, use 34.93 piping and a reducer (field-supplied).
5.5.2 Piping Size between Outdoor Units (2 Unit Combination)
· Standard Type: RAS-320 to 600CNCCLW
(Indoor Unit on Left Side)
Outdoor Unit A
Outdoor Unit B
(Indoor Unit on Right Side)
Outdoor Unit B
Outdoor Unit A
a To Indoor Units
b
c
Piping Connection Kit 1
c
b
a
Piping Connection Kit 1 To Indoor Units
37
5. Refrigerant Piping Work
Standard Type: RAS-320 to 600CNCCLW
(mm)
Model
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
320CNCCLW 340CNCCLW 360CNCCLW 380CNCCLW 400CNCCLW 420CNCCLW 440CNCCLW
Comb. Unit
Outdoor Unit A Outdoor Unit B
RAS180CNCCLW
RAS140CNCCLW
RAS180CNCCLW
RAS160CNCCLW
RAS180CNCCLW
RAS180CNCCLW
RAS220CNCCLW
RAS160CNCCLW
RAS220CNCCLW
RAS180CNCCLW
RAS-
RAS-
240CNCCLW 220CNCCLW
RAS-
RAS-
180CNCCLW 220CNCCLW
Piping Connection Kit
MC-NP21SA1
Gas a
Liquid
31.75*1 19.05
31.75*1 19.05
38.1*2 19.05
38.1*2 19.05
38.1*2 19.05
38.1*2 19.05
38.1*2 19.05
Piping Size
b
c
Gas Liquid
Gas Liquid
Refer to item 5.5.1 for the piping size for the base units to be combined.
Model
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
460CNCCLW 480CNCCLW 500CNCCLW 520CNCCLW 540CNCCLW 560CNCCLW 580CNCCLW 600CNCCLW
Outdoor Unit RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
Comb.
A
240CNCCLW 240CNCCLW 260CNCCLW 260CNCCLW 280CNCCLW 280CNCCLW 300CNCCLW 300CNCCLW
Unit Outdoor Unit RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
B
220CNCCLW 240CNCCLW 240CNCCLW 260CNCCLW 260CNCCLW 280CNCCLW 280CNCCLW 300CNCCLW
Piping Connection Kit
MC-NP21SA1
MC-NP22TA
Gas a
Liquid
Piping Size b
Gas
Liquid
38.1*2 19.05
38.1*2 19.05
38.1*2 19.05
38.1*2 19.05
38.1*2 19.05
44.45*3 19.05
44.45*3 19.05
44.45*3 19.05
Refer to item 5.5.1 for the piping size for the base units to be combined.
c Gas
1. If 31.75 piping is not available, use 34.93 piping and a reducer (field-supplied). 2. If 38.1 piping is not available, use 41.28 piping and a reducer (field-supplied). *3. If 44.45 piping is not available, use 41.28 piping and a reducer (field-supplied).
NOTE:
· Perform the installation of the outdoor unit and piping connection according
to the figure. Refer to the table for the outdoor unit model, the piping
connection kit model and the piping diameter.
5.5.3 Piping Size between Outdoor Units (3 Unit Combination)
· Standard Type: RAS-620 to 900CNCCLW
(Indoor Unit on Left Side)
(Indoor Unit on Right Side)
Outdoor Unit A
Outdoor Unit B Outdoor Unit C
Outdoor Unit C
Outdoor Unit B
Outdoor Unit A
a
cb
Piping Connection Kit 1 To Indoor Units
38
d e
Piping Connection Kit 2
e
d
bc
Piping Connection Kit 2 Piping Connection Kit 1
a To Indoor Units
5. Refrigerant Piping Work
Standard Type: RAS-620 to 900CNCCLW
(mm)
Model
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
620CNCCLW 640CNCCLW 660CNCCLW 680CNCCLW 700CNCCLW 720CNCCLW 740CNCCLW
Outdoor Unit A
RAS220CNCCLW
RAS240CNCCLW
RAS240CNCCLW
RAS240CNCCLW
RAS240CNCCLW
RAS240CNCCLW
RAS260CNCCLW
Combination Unit
Outdoor Unit B
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
220CNCCLW 220CNCCLW 240CNCCLW 220CNCCLW 240CNCCLW 240CNCCLW 240CNCCLW
Outdoor Unit C
RAS180CNCCLW
RAS180CNCCLW
RAS180CNCCLW
RAS220CNCCLW
RAS220CNCCLW
RAS240CNCCLW
RAS240CNCCLW
Piping Connection Kit
MC-NP31TA
Gas a
Liquid
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 22.2
44.45*2 22.2
44.45*2 22.2
50.8*3 22.2
Gas b
Liquid
38.1*1 19.05
38.1*1 19.05
38.1*1 19.05
38.1*1 19.05
38.1*1 19.05
38.1*1 19.05
38.1*1 19.05
Gas Piping Size c
Liquid
Gas d
Liquid
Refer to item 5.5.1 for the piping size for the base units to be combined.
Gas e
Liquid
(mm)
Model
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
760CNCCLW 780CNCCLW 800CNCCLW 820CNCCLW 840CNCCLW 860CNCCLW 880CNCCLW 900CNCCLW
Outdoor Unit
A
RAS260CNCCLW
RAS260CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS300CNCCLW
RAS300CNCCLW
RAS300CNCCLW
Combination Unit
Outdoor Unit B
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
260CNCCLW 260CNCCLW 260CNCCLW 280CNCCLW 280CNCCLW 280CNCCLW 300CNCCLW 300CNCCLW
Outdoor
Unit
C
RAS240CNCCLW
RAS260CNCCLW
RAS260CNCCLW
RAS260CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS300CNCCLW
Piping Connection Kit
MC-NP31TA
Gas a
Liquid
50.8*3 22.2
50.8*3 22.2
50.8*3 22.2
50.8*3 22.2
50.8*3 22.2
50.8*3 22.2
50.8*3 22.2
50.83 25.44
Gas b
Liquid
38.1*1 19.05
38.1*1 19.05
38.1*1 19.05
38.1*1 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
Piping Size c
Gas Liquid
Gas d
Liquid
Refer to item 5.5.1 for the piping size for the base units to be combined.
Gas e
Liquid
1. If 38.1 piping is not available, use 41.28 piping and a reducer (field-supplied). 2. If 44.45 piping is not available, use 41.28 piping and a reducer (field-supplied). 3. If 50.8 piping is not available, use 54.0 piping and a reducer (field-supplied). 4. If 25.4 piping is not available, use 28.58 piping and a reducer (field-supplied).
NOTE:
· Perform the installation of the outdoor unit and piping connection according
to the figure. Refer to the table for the outdoor unit model, the piping
connection kit model and the piping diameter. 39
5. Refrigerant Piping Work 5.5.4 Piping Size between Outdoor Units (4 Unit
Combination)
· Standard Type: RAS-920 to H20CNCCLW
(Indoor Unit on Left Side)
Outdoor Unit A
Outdoor Unit B
Outdoor Unit C Outdoor Unit D
Piping Connection Kit 1
b
d
a
e c
Piping Connection Kit 2
To Indoor Units
f
g
Piping Connection Kit 3
(Indoor Unit on Right Side)
Outdoor Unit D Outdoor Unit C
Outdoor Unit B
Outdoor Unit A
g
f
Piping Connection Kit 3
Piping
Connection
Kit 1
e
d
b
c
a
Piping Connection Kit 2
To Indoor Units
40
5. Refrigerant Piping Work
Standard Type: RAS-920 to H20CNCCLW
(mm)
Model
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
920CNCCLW 940CNCCLW 960CNCCLW 980CNCCLW H00CNCCLWH02CNCCLWH04CNCCLW
Outdoor Unit A
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
240CNCCLW 240CNCCLW 240CNCCLW 260CNCCLW 260CNCCLW 260CNCCLW 260CNCCLW
Combination Unit
Outdoor Unit B
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
240CNCCLW 240CNCCLW 240CNCCLW 240CNCCLW 260CNCCLW 260CNCCLW 260CNCCLW
Outdoor Unit C
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
220CNCCLW 240CNCCLW 240CNCCLW 240CNCCLW 240CNCCLW 260CNCCLW 260CNCCLW
Outdoor Unit D
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
220CNCCLW 220CNCCLW 240CNCCLW 240CNCCLW 240CNCCLW 240CNCCLW 260CNCCLW
Piping Connection Kit
MC-NP40TA
Gas a
Liquid Gas
b Liquid Gas
c Liquid
50.83 25.44 38.11 19.05 38.11 19.05
50.83 25.44 38.11 19.05 38.11 19.05
50.83 25.44 38.11 19.05 38.11 19.05
54.0 25.44 38.11 19.05 38.1*1 19.05
54.0 25.44 38.11 19.05 38.1*1 19.05
54.0 25.44 38.11 19.05 38.1*1 19.05
54.0 25.44 38.11 19.05 38.1*1 19.05
Piping Size
Gas d Liquid
Gas e
Liquid
f
Gas
Liquid
Refer to item 5.5.1 for the piping size for the base units to be combined.
g
Gas Liquid
(mm)
Model
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
H06CNCCLW H08CNCCLW H10CNCCLW H12CNCCLW H14CNCCLW H16CNCCLW H18CNCCLW H20CNCCLW
Outdoor Unit
A
RAS-
RAS-
280CNCCLW 280CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS300CNCCLW
RAS-
RAS-
300CNCCLW 300CNCCLW
RAS300CNCCLW
Combination
Outdoor Unit B
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
RAS-
260CNCCLW 280CNCCLW 280CNCCLW 280CNCCLW 280CNCCLW 300CNCCLW 300CNCCLW 300CNCCLW
Unit
Outdoor
Unit
C
RAS260CNCCLW
RAS260CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS300CNCCLW
RAS300CNCCLW
Outdoor
Unit
D
RAS260CNCCLW
RAS260CNCCLW
RAS260CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS280CNCCLW
RAS300CNCCLW
Piping Connection Kit
MC-NP40TA
Gas 54.0 a Liquid 25.4*4
54.0 25.4*4
54.0 25.4*4
54.0 25.4*4
54.0 28.58
54.0 28.58
54.0 28.58
54.0 28.58
Gas 38.1*1 b
Liquid 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
Gas 38.1*1 c
Liquid 19.05
38.1*1 19.05
38.1*1 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
44.45*2 19.05
Piping Size
Gas d
Liquid
e
Gas Liquid
Gas f
Liquid
Refer to item 5.5.1 for the piping size for the base units to be combined.
g
Gas Liquid
1. If 38.1 piping is not available, use 41.28 piping and a reducer (field-supplied). 2. If 44.45 piping is not available, use 41.28 piping and a reducer (field-supplied). 3. If 50.8 piping is not available, use 54.0 piping and a reducer (field-supplied). 4. If 25.4 piping is not available, use 28.58 piping and a reducer (field-supplied).
NOTE:
· Perform the installation of the outdoor unit and piping connection according
to the figure. Refer to the table for the outdoor unit model, the piping
connection kit model and the piping diameter. 41
5. Refrigerant Piping Work
5.6 Piping Size, Piping Connection and Multi-Kit Selection
For selecting the pipe sizes between the outdoor unit and the piping
connection kit 1 , between the piping connection kits 2 and for piping
connection kit A , refer to items from 5.5.1 to 5.5.4 “Piping Size between
Outdoor Units”.
< For 2 and 3 Units Combination >
Upstream Side
2 Piping Connection Kit 1 A
Outdoor Unit A
1 La
Outdoor Unit B
1 Lb
Piping Connection Kit 2 A
Outdoor Unit C
1 Lc
< For 4 Units Combination >
Piping
Connection
3 Kit 1
A
B First Branch
Outdoor Unit A
Outdoor Unit B
Outdoor Unit C
1 2
2
1 La
Piping A Connection Kit 2
1
Lb
Lc
Piping A Connection Kit 3
Upstream Side
Outdoor
Unit
D
H5
1
Ld
4
D
L3
5
5
5
H1
Indoor
Indoor
Indoor
4
Unit
Unit
Unit
4
C L3
C L3
5
Indoor Unit
5
Indoor Unit
L3
5 Indoor
Unit
H2 L1 L2
Keep the straight line distance of 500mm or more a er the piping connection kit.
Term
Symbol
Description
Total Piping Length
Example 1 Example 2
a+b+c Total length of all liquid pipes (sum)
d+e+f+g+h
Maximum Piping Length Example 1 Example 2
a+c
Actual length of the liquid pipe from outdoor unit stop
f+h
valve or piping connecting kit to the terminal unit.
Piping Length
–
Actual length of liquid pipe out of consideration of local resistance, such as bent or elbow.
Equivalent Length
42
–
This length is obtained by converting local resistance, such as bent or elbow, to straight pipe length.
5. Refrigerant Piping Work
< Example 1 > Line Branch (Including Main Pipe Branch)
Outdoor Unit A
a
First Branch Multi-Kit
b
Indoor Unit
A
c
Terminal Indoor Unit
B
< Example 2 > Using Piping Connection Kit
Outdoor Outdoor
Unit B
Unit A
e
d
Piping Connection Kit
First Branch Multi-Kit
f
h
g
Indoor Unit
Terminal Indoor Unit
A
B
NOTE: The main pipe branch is the piping branch method where Multi-Kits are connected to the pipes both a er the first branch.
Main Pipe Branch
a
b
c
de
f
Indoor Unit
5.6.1 Connection between Outdoor Units and Connection Kit
Multi-Kit (Optional Parts)
< Line Branch > (Standard Type)B First Branch
C Multi-Kit after First Branch
Outdoor Unit HP
Model
Total Indoor Unit HP
Model
8, 10 MW-NP282A3
<12 MW-NP282A3
12 – 16 MW-NP452A3 12 – 17.99 MW-NP452A3
18 – 24 MW-NP692A3 18 – 25.99 MW-NP692A3
26 – 54 MW-NP902A3 26 – 55.99 MW-NP902A3
56 – 120 MW-NP2682A3
56 MW-NP2682A3
< D Header Branch >Total Indoor Unit No. of Header Branches
HP
Max. 8
4
Max. 10
8
Model
MH-NP224A MH-NP288A
Piping Size (mm)
3 Main Pipe Diameter (Base Unit or Piping Connection Kit 1 to First Branch)
[Multi-Kit of First Branch] < 2 Pipes System >
(Standard Type) Outdoor Unit HP 8 10 12, 14 16 18 – 24 26 – 34 36 – 54 56 – 66 68 – 72 74 – 88 90 – 96 98 – 120
Gas Pipe 19.05 22.2 25.41 28.58 28.58 31.752 38.13 44.54 44.54 50.85 50.8*5 54.0
(mm) Liquid Pipe
9.52 9.52 12.7 12.7 15.88 19.05 19.05 19.05 22.2 22.2 25.41 25.41
1. If 25.4 piping is not available, use 28.58 piping and a reducer (field-supplied).
2. If 31.75 piping is not available, use 34.93 piping and a reducer (field-supplied).
3. If 38.1 piping is not available, use 41.28 piping and a reducer (field-supplied).
4. If 44.45 piping is not available, use 41.28 piping and a reducer (field-supplied).
*5. If 50.8 piping is not available, use 54.0 piping and a reducer (field-supplied).
NOTE:
· When the maximum length of the equivalent refrigerant pipe (L1) from the
piping connection kit 1 to the indoor unit is over 100m, the pipe size of gas
and liquid lines from the piping connection kit 1 to first branch should be
increased by one size (with limitation of Max. 54.0mm) with reducers (field-
supplied).
4 [Pipe Diameter after First Branch]
(Standard Type)
Total Indoor Unit HP
Diameter (mm)
Gas Pipe
Liquid Pipe
< 6
15.88
9.52
6 – 8.99
19.05
9.52
9 – 11.99
22.2
9.52
12 – 15.99
25.4*1
12.7
16 – 17.99
28.58
12.7
18 – 25.99 26 – 35.99
28.58 31.75*2
15.88 19.05
43
5. Refrigerant Piping Work
36 – 55.99 56 – 67.99 68 – 73.99 74 – 89.99 90 – 97.99
98
38.13 44.454 44.454 50.85 50.8*5
54.0
19.05 19.05 22.2 22.2 25.41 25.41
1. If 25.4 piping is not available, use 28.58 piping and a reducer (field-supplied).
2. If 31.75 piping is not available, use 34.93 piping and a reducer (field-supplied).
3. If 38.1 piping is not available, use 41.28 piping and a reducer (field-supplied).
4. If 44.45 piping is not available, use 41.28 piping and a reducer (field-supplied).
*5. If 50.8 piping is not available, use 54.0 piping and a reducer (field-supplied).
NOTES:
· In the case that the piping length from the Multi-Kit at the first branch to
the terminal indoor unit is over 40m, the size of the piping between Multi-
Kits should be increased by one size with reducers (field-supplied). Refer to
item 5.7 Piping Branch Restrictions for details.
· Even if the equivalent refrigerant piping length is more than 100m, there is
no need to increase the pipe size after first branch. If the multi-kit size is
larger than the first branch, adjust the multi-kit size to the first branch.
In case that the selected pipe size after the first branch is larger than the
pipe size before the first branch, use the same pipe size as before the
branch.
5 [Pipe Diameter between Multi-Kit and Indoor Unit]
Indoor Unit HP
1.5 or less 2.0, 2.3 2.5 to 6.0 8.0 10.0 16.0 20.0
Diameter (mm)
Gas Pipe 12.7 12.7 *2
Liquid Pipe 6.35 1 6.35 1
15.88
9.52
19.05
9.52
22.2
9.52
28.58
12.7
28.58
15.88
1. When the liquid piping length is longer than 15m, use 9.52 pipe and a reducer (field-supplied).
2. As for some of the indoor unit types, if 12.7 pipe is not available, 15.88 pipe should be used. Make sure to check the indoor unit specifications.
NOTE:
· The pipe diameter should be the same as the indoor unit piping connection
size.
5.6.2 Connection between Outdoor Units, Multi-Kits and Indoor Units
Piping Work Conditions
Item
Total Piping Length
Maximum Piping Length
Actual Length
Equiv. Length
Mark
Allowable Piping
Length (m)
Total Liquid Piping
Actual Length
1000
200 L1
225
Maximum Piping Length
between Multi-kit of 1st
L2
Branch and Each Indoor Unit
100
Maximum Piping Length
between Each Multi-kit and
L3
40
Each Indoor Unit
Piping Length between Piping Connection Kit 1 and Each Outdoor Unit
La, Lb, Lc, Ld
25 *6
Height Difference O.U. is
between
Higher
Outdoor Units O.U. is
and Indoor Units Lower
H1 *4
50 1 40 2
Height Difference between Indoor Units
H2 3, 5
40
Height Difference between Outdoor Units
H5
2.0
*1. The maximum piping length of 110m is available on request. The following restrictions apply when the height difference between the outdoor units and the indoor units (the outdoor unit is higher) are 50m or more.
· The maximum outdoor temperature during cooling operation is 43°C.
· The connectable indoor unit capacity ratio is 100%.
· To protect the system, the thermo OFF may be activated to turn the system
off when the
outside temperature is 38°C or more.
· Performance priority mode is disabled.
*2. The maximum piping length of 110m is available on request. The following restrictions apply when the height difference between the outdoor units and the indoor units (the outdoor unit is lower) are 40m or more.
· The maximum outdoor temperature during cooling operation is 43°C.
44
· The minimum outdoor temperature during cooling operation is 10°C.
· The connectable indoor unit capacity ratio
is 130%.
3. The piping length must be 15m or less when even one dedicated outside air system (DOAS) is connected to the system.
4. When there are height differences between outdoor units, use the outdoor unit that has the largest height difference from the indoor unit as the height reference.
5. When H2 is 30m or more, the connectable indoor unit capacity ratio is 100%.
6. The piping length between outdoor units should be La Lb Lc Ld 25m. Lb – La 10m, Lc – La 10m, Ld – La 10m. (If the piping length is incorrect, it may cause failure of outdoor unit due to flowing back of the refrigerant.)
NOTES:
· For 2, 3 and 4 outdoor unit combination, the outdoor unit “A” should be
connected to the piping connection kit 1. (Refer to items 5.6.1 and 5.6.2 for
the outdoor unit models.) For the details of piping connection, refer to the
Installation Manual for Piping Connection Kit.
· Keep the straight line distance of 500mm or more after the piping connection
kit.
· Allowable total piping length may become shorter than 1000m due to the
limitation of maximum additional refrigerant amount as following table.
(Standard Type)
HP
8, 10 12, 14 16 – 20 22 – 24 26 – 30 32 – 66
Max.
Additional Refrigerant
28.0
36.0
40.0
46.0
56.0
63.0
Charge (kg)
HP 68 – 88 90 – 120
Max.
Additional Refrigerant
73.0
93.0
Charge (kg)
· If the piping length (L3) between each multi-kit and indoor unit is considerably longer than that of other indoor units, refrigerant may not flow well and also performance may be deteriorated compared to other models. (Recommended Piping Length: within 15m)
5. Refrigerant Piping Work
· The piping connection kit is counted from the indoor unit side (as Piping
Connection Kit 1).
· Check the gas pipe and liquid pipe are equivalent in terms of the piping
length and piping system.
· Use a multi-kit (system components) for the branch pipe of indoor unit.
· Install the indoor unit and multi-kit according to each Installation and
Maintenance Manual.
· When connecting units in the field, use bent pipes or (horizontal) elbow
pipes to absorb the expansion and contraction of pipes caused by pipe
temperature change.
5.7 Piping Branch Restrictions
The number of the main piping branches is not limited under the following
restrictions. In the case that the piping length L2 from the Multi-Kit at the
first branch
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>