neptronic AT000 2-Way 1-2 Inch Globe Valve Instruction Manual
- June 3, 2024
- neptronic
Table of Contents
AT000 2-Way 1-2 Inch Globe Valve
Instruction Manual
AT000/AT020/AT060/AT080
Feature:
-
Variable running time.
-
Manuel override.
-
Maintenance free.
-
Fail safe by Enerdrive System¹
(on models 060 & 080). -
Auxiliary switches.
(on models 020 & 080).
Technical Data | AT000 | AT020 | AT060 | AT080 |
---|---|---|---|---|
Auxiliary switches | No | Yes(2) | No | Yes(2) |
Feedback | No | No | No | No |
Fail safe – Enerdrive | No | Yes | ||
Power consumption | 6 VA | 20VA Peak. 6VA | ||
Control signal | 3 wire / 2 position. | |||
3 wire / 3 point floating | 2 wire / 2 position. |
4 wire / 3 point floating
Running time| 60 sec force dependant
Force| 100 lb. [450 N] at rated voltage
Power supply| 22 to 26 VAC or 28 to 32 VDC
Electrical connection| 18 AWG [0.8 mm²] minimum
Inlet bushing| 2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]
Maximum Stroke| 0.5 in [12.7mm]
Direction| Reversible. normally open or normally close (factory set with
normally close direction)
Ambient temperature| 0°F to +122°F [-18°C to +50°C]
Storage temperature| -22°F to +122°F [-30°C to +50°C]
Relative Humidity| 5 to 95 % non condensing.
Weight| 2 lbs. [0.9 kg]
Warning: Do not use automatic screw driver on manual override
Dimensions
Dimension | Inches | Metric (mm) |
---|---|---|
A | 5.93 | 150.6 |
B | 4.8 | 121.9 |
C | 3.6 | 91.4 |
Caution
We strongly recommend that all neptronic® products be wired to a separate
transformer and that transformer shall service only neptronic® products. This
precaution will prevent interference with, and/or possible damage to
incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be
observed. Long wiring runs create voltage drop which may affect the actuator
performance.
¹ Enerdrive Fail-Safe System: US Patent #5,278,454
European Patent #0647366
Mechanical installation
Mounting of the actuator on valve
- Screw completely the valve shaft (C) unto the coupling of the actuator (A).
- Unscrew the coupling (A) for ½ of turn in order to leave a functional play.
- Screw the counter nut (B).
Warning:
Do not over tight coupling of the actuator on the shaft of the valve.
Mounting of the actuated valve on system
- Pay attention to system particularity; be sure that the expansions, contractions of the system and its medium as well as operating pressures are within the tolerances.
- When plumbing, the motorized valve should be situated in an easily accessible place and sufficient space should be allowed for the removal of the actuator.
- To prevent moisture from collecting in the motor casing,install the motorized valve such that the actuator is superior to the valve, at 20-30º / at vertical. Avoid mounting the valve so that the valve stem is below horizontal.
Wiring Diagrams
Models AT000 & 020
3 wire/2 position (ON-OFF)3 wire/3 point floating
Models AT060 & 080
2 wire/2 position (ON-OFF)4 wire/3 point
floating PC Board
Dip switch settings *On AT model:
When switch #3 is “ON”, the running time will be 60 sec.
AT-220119