TR33 Large LCD Screen Smart Thermostat Instruction Manual
- July 31, 2024
- Thermostat
Table of Contents
TR33 Large LCD Screen Smart Thermostat
“`html
Specifications
- Supply voltage: Variable
- Power consumption: Variable
- Temp. setting range: Variable
- Floor limited range: Variable
- Temp. Dif.: Variable
- Ambient temperature: Variable
- Protection level: Variable
- Shell material: Anti-Flammable PC
Product Overview
This series of thermostat has Floor Heating, Fan Coil, and
Integrated version, meeting the requirements under different
scenarios.
Product Usage Instructions
Version Overview
Different system modes and models are available depending on the
application:
- Floor heating: EP
- Fan Coil: WP, WPA, WPB
- Heating/Cooling/Ventilation: AC2, AC2-485, AC4
- Floor heating & fan coil, weekly programming + Integrated
Ventilation/Floor heating/AWY: AC4
Display Symbols
The thermostat displays various symbols for different functions
such as setting temp, time display, Wi-Fi, timer task, modes like
manual, auto, temporary, ECO, child-lock, etc.
User Operation
-
Power on/off: Press shortly to turn on/off the thermostat.
-
Auto-mode: Press for 3 seconds to edit auto-mode settings.
-
Timer task: Press for 3 seconds to edit timer task.
-
Time setting: Press for 3 seconds to set time.
-
Child-lock: Press + for 3 seconds to activate child-lock.
-
System mode: Press shortly to switch
cooling/heating/ventilation. -
Temp control mode: Press shortly to switch manual/auto
mode. -
Fan speed setting: Press shortly to adjust fan speed.
Auto-mode Setting (Floor Heating/Integrated)
Press for 3 seconds to edit auto-mode setting.
FAQ
How many events can be set per day on the thermostat?
You can set up to 6 events per day on the thermostat for
customized temperature plans.
What is the material of the shell of the thermostat?
The shell material of the thermostat is Anti-Flammable PC.
“`
Large LCD screen smart thermostat
Customized exclusive temperature plan – up to 6 events allowed
to set per day
Sail shape design-delicate and elegant Large LCD screen-better user experience
485 modbus and room card linkage – customized equipment (optional)
Parameter
Supply voltage Power consumption Temp. setting range Floor limited range Temp.
Dif. Ambient temperature Protection level Shell material
AC100~240V; 50/60Hz 1W Max (Wi-Fi 3W Max) 5~9541~99 20~9068~99 0.5~101~10,
Factory setting ±1 -5~5023~99 IP20
Anti-Flammable PC
Version:TR33 1.6(12/2023)
Product Overview This series of thermostat has Floor Heating, Fan Coil, and Integrated version, meeting the requirements under different scenarios.
Version
System mode
Model
Application
Floor heating
Fan Coil
Floor heating
Heating /Cooling / Ventilation
EP
Built-in & floor sensor, floor limit sensor + Weekly programming
WP A NC/NO dual-output + Weekly programming
WPB
A NC/NO dual-output + Weekly programming+ Potential-free output
AC2 Timer task + 2-pipe system
AC2-485
Timer task + 2-pipe system + Potential-free output + Room
485Modbus (optional) card (optional)
AC4
Timer task + 4-pipe system + 485Modbus (optional) + Potential-free output + Room card (optional)
Heating / Cooling /
Floor heating & fan coil, weekly programming +
Integrated Ventilation/Floor heating / AWY Potential-free output + Timer task
Floor heating + Heating
485Modbus (optional) + Room card (optional)
Display Symbols
Setting temp.
Time Display
Wi-Fi Timer Task
Manual Mode
Auto Mode
Temporary Mode
ECO Mode
ECO
Child-lock
Frost Protection Room Temp.
Floor Heating Mode Fan-Coil Heating Mode
Power on/off Mode
Week Display
Wake up; Event 1 Leave (am); Event 2 Return (am); Event 3 Leave (pm); Event 4
Return (pm); Event 5 Sleep; Event 6
Fan Speed Display Room Temp. Floor Temp.
Cooling on Heating on Fan-Coil Ventilation Mode Fan-Coil Cooling Mode
Fan(Integrated)
ECO(Floor heating)
Down Up
Temperature Control Mode(Floor Heating/Integrated)
Manual Mode Thermostat works based on manually-set temperature, disconnecting
from auto mode.
Auto Mode Weekly-circled programme, up to 6 heating events can be set per day.
Heating events, workdays and temperature can be separately customized based on
personal routines.
Temporary Mode Thermostat works based on manually-set temperature temporarily
and then shifts back to auto mode till next event. User Operation Power on/off
: Press ” ” shortly to turn on/off the thermostat.
Auto-mode : Press ” ” for 3 seconds to edit auto-mode settings. (Floor
Heating/Integrated) Timer task: Press ” ” for 3 seconds to edit timer task.
(Integrated)
Time setting: Press ” ” for 3 seconds to set time. (Floor Heating)
Press ” ” twice for 3 seconds to set time. (Automatic time synch for Wi-Fi
version) Temp setting: Press ” ” or ” ” shortly to change setting temperature
by 0.5°C.
Child-lock: Press ” ” + ” ” for 3 seconds to activate child-lock. System mode:
Press ” ” shortly to switch cooling/heating/ventilation (Fan Coil/Integrated)
Press ” ” shortly to switch cooling/heating/ventilation/floor heating/floor
heating + heating. (Integrated) Temp control mode: Press ” ” shortly to switch
manual/auto mode. (Floor heating)
Press ” ” shortly to switch manual/auto mode. (Integrated, floor heating) Fan
speed setting: Press ” ” shortly to adjust fan speed.(Integrated)
ECO mode: Press” “shortly to set to ECO mode 18°C(65°F). (Floor heating)
Auto-mode Setting (Floor Heating/Integrated)
Press ” ” for 3 seconds to edit auto-mode setting.
Events
Time Symbols Default value Modify
1
2
Workdays
3 4
5
6
1 Weekends 2
06:00 08:00 11:30 12:30 17:00 22:00 06:00
20:00
Press ” ”
or
” ”
Temperature
Default value Modify
20(68)
15(59) 15(59) 15(59) 22(72) 15(59)
20(68)
Press ” ”
or
” ”
20(68)
Advanced Setting (Usually for Professional Technicians) Under power-off, press ” ” for 3 seconds to enter advanced setting mode, then re-press ” ” to switch to next mode. Press ” ” to save and exit advanced setting mode.
Code
Meaning
”
“or”
”
00 Postal address(optional) Adjustment range 0x00~0xFA
01 Temp. calibration -9.9~9.9(-9~9)
02 Temp. Dif.
0.5~10(1~10)
Default Integrated Fan Coil
Floor Heating
Value
AWY
AC2- AC4 AC2 EP WP WPB 485
00 ×
-3
±1
03 Temp. upper limit 5~95(41~99) 04 Temp. lower limit 5~47(41~99)
50 5
05 Frost protection
ON: frost protection on OFF: frost protection off
OFF
06 Temperature unit /
07 Sensor selection
IN: Controlled by built-in sensor OUT: Limited by floor sensor ALL: Controlled
by built-in sensor and
limited by floor sensor
IN × × ×
08 Floor limited Value 20~90(68~99)
35 × × ×
09
Weekly programming setting
12345: 5/2 week mode 123456: 6/1 week mode 1234567: 7/0 week mode
12345 × × ×
10 Fan control settings
00: Fan speed controllable 01: Fan speed uncontrollable
00 × × ×
11 Delay time of outputs 0~5min
0 × ××
12 Child-lock
00: Child-lock inactivate when screen off;
lock all when child-lock activate
01: Child-lock activate when screen off;
lock all when child-lock activate
02: Child-lock activate when screen off; lock all except Fan Speed, Up and
00
Down when child-lock activate
03: Child-lock activate when screen off;
lock all except Power on/off when
child-lock activate
13 Boot Status
00: Power OFF 01: Power ON 02: The last status before power loss
02
14 Room card status
00: turn off room card function 01: set to ECO temp. after pulling room
card out 02: stay power-off after pulling room
card out
15
Room card heating ECO temp.
10~21(50-69)
16
Room card cooling ECO temp.
22~32(72-89)
17
Fan coil mode setting
00: Cooling and heating 01: Cooling only
18
Weekly programming 00: turn on
for Integrated
01: turn off
19 Reset
Press ” “for 3 seconds to reset
00 × × × × ×
18 × × × × × 26 × × × × × 00 × × ×
01 × × × × × × /
Large LCD screen smart thermostat
Sensor failure
Please select work mode of sensors correctly. When it shows Er0/Er1 error,
thermostat will stay power-off till the error is eliminated.Er0: built-in
sensor is short-circuited or disconnected. Er1: floor sensor is short-
circuited or disconnected.
Timer Task Setting (Fan Coil / Integrated )
Press ” press ”
” for 3 seconds to enter timer task setting; press ” ” to change settings;
” or ” ” to adjust parameters; press ” ” to save and exit. Implement Day
Timed power-on/off
Task Time
0: No Implement 1: Implement 00: No Effect 01: Take Effect
Dimensions (Unit: mm)
Floor Heating / Fan Coil
EP #WP #WPB #AC2
13.5 32.6
51 51
Fan Coil / Integrated
AC2-485 #AC4 #AWY
13.5 2 4
64 66
Mounting Steps
The thermostat adopt pre-guide and limited snap-fit design. It is easy to
mount. 1Release front cover by inserting a head screw-driver into bottom
crack.
2Insert the wires and then fix these wires with screws. Suggested wire-
stripping length is 7-9mm.
3Mount backing plate into wall-cassette, put screws and then fix thermostat.
Make sure that the thermostat is fixed without deformation. Suggested torque
is 0.2~0.4N.m (2.0~4. 1kgf.cm).
4Re-mount the front cover via snap-fit connection.
Installation instructions
Connecting Diagram
The thermostat operates in full capacity in areas with the altitude of less
than 2500 above sea level. Power rating of external load should be less than
or equal to 80% rated power of the thermostat in areas with altitude of 2500m
to 4200m.
Floor Heating
TR33-WIF-EP # TR33-EP
TR33-WIFI-WP # TR33-WP #TR33-WIFI-WPB # TR33-WPB
L N N1 L1 AC100~240V
NTC
PC1 PC2
LN AC100~240V
Electro thermal actuator or electrical ball valves
Potential-free
(Potential-free output, for model WPB only)
Dry contact signal to control boiler
Linkage control; delay time of linkage control is adjustable
PC1 PC2
LN AC100~240V
Electro thermal actuator or electrical ball valves
Potential-free (Potential-free output, for model WPB only)
Dry contact signal to control boiler
Linkage control; delay time of linkage control is adjustable
PC1 PC2
Fan Coil
LN
Potential-free
AC100~240VThree-wire electrical ball valve with two
(Potential-free output, for model WPB only)
types of control mode
Electro thermal actuator or electrical ball valves
Dry contact signal to control boiler
Linkage control; delay time of linkage control is adjustable
L N H M S OPEN CLOSE
TR33-WIFI-AC2
TR33-AC2
LN AC100~240V
N
Fan
Air conditoner
valve
N #TR33-WIFI-AC2-485
CLOSE OPEN HI MED LOW L
89
TR33-AC2-485
N
Air conditoner valve
L Fan AC100~240V
N
PC1 PC2 CARD RS RG A B
16 15 14 13 12 11 10
TR33-WIFI-AC4 # TR33-AC4
NTC
485A 485B
Dry contact signal
Room card
(optional)
to control heat pump external sensor(optional)
room card linkage(optional)
N CLOSE OPEN CLOSE OPEN HI MED LOW L
89
N
L
Heat valve Cool valve
Fan AC100~240V
N
PC1 PC2 CARD RS RG A B
16 15 14 13 12 11 10
Integrated
TR33-WIFI-AWY # TR33-AWY
NTC
485A 485B
Dry contact signal
Room card
(optional)
to control heat pump external sensor(optional)
room card linkage(optional)
N CLOSE OPEN CLOSE OPEN HI MED LOW L
89
N
Floor heating Air conditoner
valve
valve
Fan
L
AC100~240V
N
PC1 PC2 CARD RS RG A B
Linkage control; delay time of linkage control is adjustable
16 15 14 13 12 11 10
Dry contact signal to control heat pump
NTC Room card
485A 485B (optional)
room card linkage(optional)
01 Shut down thermostat and long press ‘ or
‘ or ` ‘ twice
4 Device sharing
5 App control interface
Fan Coil & Floor Heating
Edit
Slide to adjust temperature
Fan