BASEN GREEN BR-OW-LV 11.77KWH Wall Mounted Battery Pack Instruction Manual
- July 24, 2024
- BASEN GREEN
Table of Contents
- BASEN GREEN BR-OW-LV 11.77KWH Wall Mounted Battery Pack
- Product Information
- Preface
- Safety Instructions
- Label Explanation
- Product Description
- Product Advantages
- Product Technical Parameters
- Interface Overview
- Installation and configuration
- Connection
- Operation
- Operation of Bluetooth
- Operation of Upper System
- Communication Compatible List
- Storage
- Warning Instruction
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BASEN GREEN BR-OW-LV 11.77KWH Wall Mounted Battery Pack
Product Information
Specifications
- Product Name: Wall-Mounted Battery Pack
- Models Available: BR-OW-LV 11.77KWH, BR-OW-LV 14.33KWH, BR-OW-LV 15.36KWH
- Battery Voltage: 43.2Vdc-58.4Vdc
- Maximum Charge Current: 200A
- Maximum Discharge Current: 200A
- Rated Capacity: 230Ah/51.2V/11776Wh
- Ingress Protection: IP55
- Protective Class: 1
- Certifications: CE, UN38.3
Product Description
The Wall Mounted Battery Pack is a rechargeable LiFePO4 battery designed for
efficient energy storage and usage.
Product Advantages
- High voltage operation range for optimal performance.
- Maximum charge and discharge currents ensure a reliable power supply.
- Durable construction with IP55 protection for safe outdoor use.
- Easy installation on walls for space-saving and convenient access.
Operation
Check Before Power On
- Ensure all connections are secure and properly insulated.
- Verify the power supply voltage is within the specified range.
- Check for any visible damage to the battery pack.
Power On
- Turn on the power source supplying the battery pack.
- Monitor the battery status indicators for proper functioning.
FAQ
-
What should I do in case of a DC short circuit?
In case of a DC short circuit, immediately disconnect the power supply and contact a professional for assistance. Do not attempt to repair the equipment yourself to avoid personal injury or damage to the battery pack. -
How can I ensure proper communication with the upper system?
To ensure proper communication with the upper system, follow the login process as outlined in the manual and verify compatibility with the communication protocol switch. Refer to the communication compatible list for supported systems.
Models
- BR-OW-LV 11.77KWH
- BR-OW-LV 14.33KWH
- BR-OW-LV 15.36KWH
Preface
- This manual will provide detailed product information and installation instructions for users of the wall-mounted series products of SHENZHEN BASENGREEN TECHNOLOGY CO.LTD (hereinafter referred to as BASENGREEN). Please read this manual carefully, and put this manual in a place where you can install, operate, and obtain it conveniently.
- The safety precautions mentioned in the manual do not represent all the safety matters that should be observed but are only supplementary to the safety precautions. When installing, operating, and maintaining equipment, local safety regulations and norms should be followed. Only trained professionals can install, operate, and maintain equipment. Our company does not assume any responsibility for losses caused by violation of general safety operation requirements or violation of safety standards for the design, production, and use of equipment. Installation and maintenance personnel must have high-voltage and AC power operation skills. When installing, operating, and maintaining equipment, they must not wear any conductive objects, such as watches, bracelets, bracelets, and rings, and prevent moisture from entering the equipment.
Safety Instructions
-
High Voltage Danger
The high-voltage power supply provides power for the operation of the equipment. Direct contact or indirect contact with a high-voltage power supply through wet objects will cause fatal danger. -
Use Professional Tools
Always use professional tools instead of personal tools when working with high-voltage and AC power -
Anti-static
The static electricity generated by the human body will damage the electrostatic-sensitive components on the board. Before touching the plug-in, circuit board, or chip, make sure to take proper anti-static measures. -
Operate Attention
The power must be cut off first before operation, do not hot-line work. -
DC short circuit Danger
The power system provides a DC-regulated power supply, and a DC short circuit will damage the equipment and cause personal injury.
Label Explanation
The label contains the following information
Product Description
This product is a lithium iron phosphate battery (LFP LiFePO4) composed of 16 cells in series. Which is suitable for home energy storage systems. It can be customized according to customer needs to meet diverse application scenarios and provide stable power for various equipment of users.
Product Advantages
- Built-in Battery Management System (BMS): Overcharge, over-discharge, overcurrent, temperature control, short circuit, and other protection functions.
- Passive Balance Function: There is a voltage equalization function during the charging.
- High-Cost Performance: High safety performance, long service life, stable and reliable quality.
- Expandable: Equipped with RS232/ RS485/ CAN bus ports, support up to 15 units in parallel.
- Wide Working Temperature: -20℃ to 60℃, excellent high-temperature discharge performance.
- Convenient: Modular design, small size and lightweight, easy to install and maintain.
Product Technical Parameters
Specification
Item
|
Specifications
---|---
Model
|
BR-OW-LV 11.77KWH
|
BR-OW-LV 14.33KWH
|
BR-OW-LV 15.36KWH
Nominal Voltage| 51.2V| 51.2V| 51.2V
Operating Voltage| 43.2V-57.6V| 43.2V-57.6V| 43.2V-57.6V
Nominal Capacity| 230AH| 280AH| 300AH
Total Energy| 11776Wh| 14336Wh| 15360Wh
Configuration| 1P16S| 1P16S| 1P16S
Charging Cut-off Voltage| 58.4V| 58.4V| 58.4V
Discharge Cut-off Voltage| 43.2V| 43.2V| 43.2V
Operation Temperature| -20℃~60℃| -20℃~60℃| -20℃~60℃
Standard Charging Current
|
50A
|
50A
|
50A
Max Continuous Charging Current
|
200A
|
200A
|
200A
Max Continuous Discharge Current
|
200A
|
200A
|
200A
Dimension| 500232670mm| 500255770mm| 500255770mm
Net weight| 98KG| 112KG| 112KG
Interface Overview
Position
| Item|
Description
---|---|---
1
|
P+
| The positive terminal of the battery can be connected to the positive pole of the inverter through a cable for DC output.
2
|
P-
| The negative terminal of the battery can be connected to the negative pole
of the inverter through a cable for DC output.
3| Power Indicator| Turn on then light-on, turn off then light-off
4| RST| Manual-return switch button
5| ADD| Setting up battery parallel communication and inverter communication
6| RUN| Indicating the normal operation status of the battery
7
|
Alarm
|
Indicating the abnormal state of the battery, if there is a low voltage or over voltage, the alarm will sound.
8| SOC| 6 indicators, indicating the remaining power status.
9| RS485 A| RS485 port for the inverter or the upper system communication
10| CAN| CAN port for the inverter communication
11| RS232| Communication port for the upper system.
12| RS485 B/C| RS485 port for parallel communication
13| Power switch| The switch for turn on/turn off the battery pack.
---|---|---
14| LCD Screen| Display battery voltage, SOC, temperature, etc.
Battery Management System(BMS)
-
Overcharge Protection
When the voltage of any single cell or whole battery pack is higher than the set value during the charging, and the duration reaches the limited time, the system enters the overcharging protection state automatically, and the charging MOS is turned off at the same time, and the battery cannot be charged. After the voltage of each cell and the whole battery pack drops below the cell over charging recovery value, the overcharging protection state is released. It can also be released by discharging to return to normal state. -
Over-discharge Protection
When the voltage of any single cell or whole battery pack is lower than the set value during discharging, and the duration reaches the limited time, the system enters the over-discharge protection state, the discharge MOS is turned off, and the battery cannot be discharged. After the over-discharge protection of the battery pack occurs, it can be released by charging the battery pack. -
Overcurrent Protection
During charging and discharging, when the current exceeds the set value of the protection current, and the duration reaches the limited time, the system enters the overcurrent protection state, the charging and discharging MOS will be turned off automatically, and the battery cannot be charged and discharged, charging and discharging the battery pack can release the overcurrent protection state. -
Over Temperature Protection
When the NTC detects the temperature of the battery cell surface is higher than the setting value of over temperature protection during charging and discharging, the management system enters the over temperature protection state, the charging or discharging MOS is turned off, and the battery pack cannot be charged or discharged in this state. -
Low-Temperature Protection
When the NTC detects that the temperature of the cell surface is lower than the setting value of low-temperature protection during charging and discharging, the management system enters the low-temperature protection state, the charging or discharging MOS is turned off, and the battery pack cannot be charged or discharged in this state.
Installation and configuration
Packing
- After receiving the battery, open the box to check the battery surface if get any broken, cracked, or other bad phenomena; if get that, please do not install it, need to contact the supplier, and wait for the supplier’s reply before proceeding to the next step.
- Please ensure that the following items are included in the packaging:
Recommended Tools
Before installing the battery pack, the user needs to have the tools as the
following list:
Notice for Installation
- The wall for installation should be a solid brick or cement wall with a strong load-bearing capacity, and the thickness of the wall should not be less than 100mm.
- In indoor installation, it needs to leave enough space to be installed and operated easily and pay attention to ventilation. Do not place flammable materials around the battery.
- In outdoor installation, it needs to be surrounded by protective measures and make rain protection.
Installation Procedure
- Mark the drilling position using the wall mounting plate, and level using a spirit level.
- Place the wall mounting plate close to the wall firmly, mark the drilling position, and remove the wall mounting plate.
- Drill holes in the wall using the driller. The hole diameter is 12mm and the depth is 60mm.
- Fix the M8 Expansion bolts, tightening torque: 20N.m
- Loosen the 4 wheels on the battery, lift the battery parallel to the ground, and hang the battery module on the bracket as shown in the following figure:
Installation Diagram
Connection
Precautions Before Connecting The Inverter
- Use a multimeter to measure whether the connection of the positive and negative cables are conducting, and check whether the connections are loose.
- The battery should be switched off before wiring to ensure that there is no DC output from the battery.
- Connect the positive terminals of the battery and the inverter with a red power cable, and then connect the negative terminals of both sides with a black power cable.
- Connect both communication ports of the battery(RS485A/CAN) and the inverter(BMS port) with the communication cable, The BMS ports of the inverter have different definitions for some brands, please check the inverter manual.
Communication cable connection Pin definition is as follows:
RS485A Port | PIN | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
---|---|---|---|---|---|---|---|---|---|
Define | RS485-B | RS485-A | GND | NC | NC | GND | RS485-A | RS485-B | |
CAN Port | PIN | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Define | NC | NC | NC | CAN-H | CAN-L | NC | GND | NC |
RJ45 Connector Diagrams of Inverter’s port
Precautions Before Connecting The Inverter with The Battery Pack in Parallel
- Use a multimeter to measure whether the connection of the positive and negative cables are conduct-ing, and check whether the connections are loose.
- The battery should be switched off before wiring to ensure that there is no DC output from the battery.
- Lock the parallel cable wires to the positive terminal of the battery pack first, then connect another end to the negative terminal.
- Parallel communication cable to the RS485 port of the battery pack.
- Connect the positive terminals of the battery and the inverter with the red power cable, and then connect the negative terminals of both sides with the black power cable.
- Connect both communication ports of the battery(RS485A/CAN) and the inverter(BMS port) with the communication cable, The BMS ports of the inverter have different definitions for some brands, please check the inverter manual.
Parallel communication cable connection Pin definition is as follows:
RS485| PIN| 1| 2| 3| 4| 5| 6| 7| 8|
---|---|---|---|---|---|---|---|---|---|---
Parallel
comment-
|
Define| RS485| RS485| GND| NC| NC| GND| RS485| RS485|
cation| | | | | | | | | |
interface| | -B| -A| | | | | -A| -B|
definition| | | | | | | | | |
Battery & Inverter Connection
Connect the positive and negative cables of the battery to the positive and
negative terminals of the DC input of the inverter, insert the RJ45 crystal
plug at one end of the distributed inverter communication cable to the RS485
of the battery, and connect the other end to the BMS terminal of the inverter
according to the defined line voltage, and then connect the battery to the
inverter.
Dip Code Switch Definition and Setting
- ADD switch is a 4-bit DIP switch to manually distribute the communication address of parallel batteries.
- The BMS will only recognize the DIP address once it is reset, so please reset the BMS when the DIP address is changed (the BMS must be reset in the standby state). When the DIP address is 0, the battery is configured as the stand-alone working mode; when the DIP address is 1, the BMS is configured as the master working mode; when the DIP address is 2 to 6, the BMS is configured as the slave working mode.
- Please refer to the table below to set the DIP switch for parallel connection of different batteries.
Operation
Check Before Power on
- Check all positive, and negative cables and communication lines are connected correctly and safely.
- Check the battery is firmly installed, easy to operate and maintain, and check ventilation.
- Insulate the unused ports.
Power on
- Turn on the switch on the battery.
- The green running LED is normal (Check the status of the LED indicators)
- If it fails to switch on the battery system, check if all the electrical connections are correct.
- If the electrical connection is correct, but the battery system is still unable to switch on, contact our after-sale service within 48 hours
LED Indicator Status
Flashing Definition
Item | Light | OFF |
---|---|---|
Flash 1 | 0.25 s | 3.75 s |
Flash 2 | 0.5 s | 0.5 s |
Flash 3 | 0.5 s | 1.5 s |
Status
| Normal/warning/protection| RUN| ALM| Battery capacity LED|
Specification
---|---|---|---|---|---
| | | | | | | |
Power off| Sleep| OFF| OFF| ALL OFF|
Stand by| Normal| Flash1| OFF| |
Warning| Flash1| OFF|
| Normal| Flash2| OFF| |
| Warning| | | |
| (Not including| Flash2| OFF|
| temperature )| | |
Charging| Overcharging protection| Flash1| OFF| | ALM OFF when protected
during overcharging
| Over Temperature,
Low-temperature,
Over current protection
|
Flash1
|
Flash2
| |
| Limited charging| Light| OFF| |
| Normal| Light| OFF| Display according|
| | | | to the actual SOC| ALM OFF when
| Warning| Light| Flash3| | discharge over
| | | | | current
| Over-discharge Protection| Flash1| OFF| | ALM OFF when protected during
overcharging
Discharging| Over| | | |
| Temperature,| | |
| Low-temperature| | |
| 、Over current、| Flash1| Flash2|
| Shot Circuit、| | |
| Reverse Polarity| | |
| Protection| | |
Invalidation| Error| OFF| Light| ALL OFF| The error refers to hardware
defection such as BMS voltage sampling device, charging MOS damage,
temperature sensor disconnection, etc.
Operation of Bluetooth
BASENGREEN 48V battery pack is equipped with a Bluetooth function and supports APP monitoring battery statuses. All information available in the battery, such as the state of charge, voltage, operating current, temperature, and other operating information is transmitted in real-time via the Bluetooth transmitter. The parameters can be made visible with the BASENGREEN App.
Download: Android: “BASENGREEN” in Play Store
- iOS: “BASENGREEN” in Apple Store
Bluetooth
-
For Android users, please visit the Google Play Store and search for ‘BASENGREEN’. For iOS users, go to the Apple Store and look up ‘BASENGREEN’.
-
Turn on Bluetooth and search for the corresponding product’s Bluetooth code
NOTE:- If you selected a battery to connect to and the app doesn’t confirm the connection, it might be someone else is already connected to the battery. Only one device connects to the battery at the same time.
- The Bluetooth app supports status monitoring only. It does not support any modified operation except communication protocol switching
-
Menu
- Bluetooth list: Check the Device list and connect it.
- Homepage: Check the status of battery-SOC, Volt, Current, Temperature, etc.
- Historical Data: Not available
- Setting: Base Message: Check the pack voltage, current, cycle time, etc.
- Cell Voltage: Check the cell voltage.
- Language: English/Chinese switching.
- Fault Data: Not available
- System Parameter: Not available
- Set up WiFi: Setup WiFi function(Not available)
- Inverter configuration: Communication protocol switching(Chapter 9.2)
Operation of Communication Protocol Switch(Via Bluetooth App)
- Connect to the Bluetooth app first(Chapter 9.1)
- Swipe left to find ‘Inverter Configuration’. The set unlock code is 888888
- Choose the communication protocol and set it, the battery pack will restart after a few seconds with a “bee” sound. Then setup is successful.
Operation of Upper System
BASEN 48V battery pack supports connecting with our upper system to monitor the status of the battery and modify the communication protocol, please contact our sales representative or visit our website to get the latest upper system software.
Log in
- The upper system communication cable connects to the RS485 port on the battery and then to the USB port on the PC/Laptop
- Download and open the upper system software
- Modify the language
- Updated the status of the battery automatically
Notice:
If it fails to connect to the upper system, check if all the connections is
correct. If the connection is correct, but the upper system is still unable to
work, please contact our after-sale service
Operation of The Communication Protocol Switch
Connect to the upper system and follow the path:
- INFO—Parallel Group Display—CAN Type/RS485 Type—Read—Choose the protocol—Set
Communication Compatible List
Storage
- External terminals of the battery pack are insulated and protected.
- If the battery pack is stored for a long period without use, it is recommended that it be charged 30%-60%, and it is prohibited to store it completely uncharged.
- Batteries that have been in storage for more than 3 months should be recharged for 2-3 hours at 0.2C~0.3C.
- Batteries should be stored in a dry, clean, ventilated, non-corrosive gas environment, away from sources of ignition, to avoid exposure to the sun.
- Do not store or put in high temperatures over 60°C for a long period, otherwise, it will cause function deterioration and life span reduction.
Warning Instruction
To prevent possible battery leakage, heat generation, and explosion, please observe the following warning:
Warning!
- It is strictly forbidden to immerse the battery in seawater or water. When not in use, it should be placed in a cool and dry environment;
- It is strictly forbidden to reverse the positive and negative poles to use the battery;
- It is forbidden to use metal to directly connect the positive and negative electrodes of the battery to a short circuit;
- It is forbidden to transport or store batteries together with metals, such as hairpins, necklaces, etc;
- It is forbidden to knock or throw, step on the battery, etc.;
- It is forbidden to directly weld the battery and pierce the battery with nails or other sharp objects.
Attention!
- It is forbidden to use or place the battery under high temperatures (in the hot sun or a very hot car), otherwise, it may cause the battery to overheat, catch fire, or fail to function, and shorten its life; the recommended temperature for long-term battery storage is 10-45°C;
- It is forbidden to throw batteries into fires or heaters to prevent fire, explosion, and environmental pollution. Scrapped batteries should be returned to the supplier or battery recycling point for disposal;
- Do not use it in places with strong static electricity and strong magnetic fields, otherwise it will easily damage the battery safety protection device and bring unsafe hidden dangers;
- If the battery leaks and the electrolyte enters the eyes, do not rub it. Immediately rinse the eyes with clean water and send them to the hospital for treatment, otherwise, the eyes will be hurt. If the battery emits an odor, heats up, discolors, deforms, or has any abnormality during use, storage, or charging, immediately remove the battery from the device or charger and stop using it;
- It is forbidden to insert the positive and negative poles of the battery directly into the power socket, and a special charger for lithium-ion batteries must be used;
- Check the battery voltage and connectors before installation, and use it only after everything is normal;
- The battery is stored in half power. If the battery has not been used for three months, it needs to be recharged once;
- If the electrode is dirty, it should be wiped with a dry cloth before use. Otherwise, it may cause poor contact and function failure;
Need additional information?
Just Contact BASEN!
BASENGREEN
YOUR RELIABLE POWER
- Fax: (+86)0755-84737145
- Tex: (+86)130 0887 9993
- Email: info@Basengroup.com
- Shenzhen Basen Technology Co., Ltd.
- Add: Room 303, Building 3, 1980 Culture and Technology Industrial Park, Donghuan Road, Longhua District, Shenzhen.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>