janitza CT27 Current Transformer Installation Guide
- June 3, 2024
- janitza
Table of Contents
CT27 Current Transformer
Installation Guide CT27-35
CT27-64
General
The CT27 is a current transformer and can only be used measuring electrical
alternating currents. The CT27 is suitable only for mounting on insulated
primary conductors in a weather protected and dry location.
Read this installation guide before installing the product.
WARNING
Risk of injury due to electric voltage or electrical current!
When handling electrical currents or voltages, serious personal injuries or
death can occur due to:
- Touching live exposed or stripped cores.
- Device inputs that are dangerous to touch.
Before starting work on your system:
- Disconnect it from the power supply!
- Secure it against being switched back on!
- Verify disconnection from power!
- Ground and short circuit!
- Cover or block off neighboring parts that are under voltage!
Qualified personnel
To prevent personal injuries and property damage, only qualified personnel with electrical engineering training may work on the base unit and its components. They must also have knowledge
- of the national accident prevention regulations.
- of safety technology standards.
- in the installation, commissioning and operation of the device and the components.
Mounting instruction
Tools are only required connecting the primary cable running through the Current Transformer. To connect the CT to the meter correctly, please consult the installation guide of the meter.
Assembly
Under no circumstances the secondary circuit of the CT may be opened when the current is flowing in the primary circuit. High voltages may appear on the secondary leads when this circuit is left open.
- Ensure a safe working area during assembly, maintenance and inspection of the CT. Disconnect the power of the primary circuit and make sure it can not be enabled unintentionally.
- Find the power direction of the cable you want to measure. It is recommended to mount P1 side to power source and P2 side to power consumer. If so the arrow on the CT will indicate the direction of power flow.
- Mount the CT on the cable. The CT27 can be mounted standalone and clicked on each other. Optional: screw mounting or mounting on a DIN-rail via the mounting clip (Snap-on mounting) (09.09.010).
- Reinstall the primary conductor.
- Connect the secondary leads (S1, S2) to the low impedance current input of the measurement instrument (e.g., an ammeter or current input of kWh-meter). For more information about the secondary leads, please consult the specifications table under ‘Technical Specifications’.
- Check if the CT is mounted properly. Check if the secondary leads are connected properly and firmly.
- Enable the primary circuit.
Wiring Diagram
Accuracy
The CT may not meet its accuracy specification when the secondary burden is to
high. For example due to a secondary cable which is too long or too thin.
Maintenance and inspection
- Check whether the secondary leads are connected firmly.
- Check whether the CT is mounted firmly.
- Remove severe pollution on the casing.
Temporarily disconnecting the CT
The secondary leads of the CT always have to be connected to a low impedance
burden such as an ammeter. When, during maintenance, no burden is available to
connect to, the secondary leads of the CT (the two secondary terminals) must
be short-circuited.
Problem solving
Unexpected values, incorrectly values, reversed power
- Check the settings of the meter by using the installation guide of the meter.
- Check whether the CT is mounted on the intended cable in the right direction.
- Check the value of the secondary burden (secondary leads length/diameter and meter impendent). See product/data sheet for the maximum burden value.
Attention
Always follow the disassembling instructions when reversing the C T.
Disassembly instruction
Tools are only required disconnecting the primary cable running through the CT27. To disconnect the meter from the CT, please consult the installation guide of the meter.
- Ensure a safe working area during disassembling the CT. Disconnect the power of the primary circuit and make sure it cannot be enabled unintentionally.
- Dismount the CT from the primary conductor.
- Disconnect the secondary leads from the measurement instrument.
Recycling
When the product has reached ‘end of life’, it must be recycled.
Do not dispose this product as unsorted municipal waste. Contact a qualified
recycler for disposal.
Technical Specifications
Safety and environmental conditions
CE marking| LV directive 2014/35/EU
RoHS directive (EU) 2015/863
---|---
Standard| EN-IEC 61010-1:2010
WEEE directive 2012/19/EU
This product is designed to be safe under the following conditions:
Location | Indoor use |
---|---|
Altitude | Up to 2000 m (1.24 mi) |
Ambient temperature | -10 °C to +55 °C (14 °F to 131 °F) |
Storage temperature | -20 °C to +70 °C (-4 °F to 158 °F) |
Relative humidity | 5% to 85%, non condensing |
Pollution degree | 2 |
Degree of protection | IP20 |
The CT27 is only suitable for insulated primary conductors.
Specifications
Standard | IEC 61869-2:2012 |
---|
Rated short-time thermal
current (Ith)| 60 x Ipr / 1s
Rated dynamic current (Idyn)| 2,5 x Ith
Continuous thermal current (Icth)| 100%
Rated insulation level| 0,72/3/- kV
Rated frequency| 50/60 Hz
Class of insulation| A (105 °C / 221 °F)
Secondary terminal| Female clamping connector, suitable for conductor size:
0,2 to 1,5 mm² solid, stranded or ferruled (Strip length 8 to 9 mm) (0.315 to
0.354 in)
Specifications per type
| CT27
---|---
Secondary leads format*| 0,5 mm2
max. 1,4 m
(55 in)| 0,75 mm2
max. 2,0 m
(79 in)| 1,0 mm2
max 2,8 m
(110 in)| 1,5 mm2
max. 4,0 m
(157 in)
Suitable for cable| o 7,5 mm (0.295 in)
Approximate weight| 40 g (0.088 lb)
- Maximum length secondary leads for 0,1 VA at the end of this leads.
Explanation of symbols
| This product is designed according to the EN-IEC 61010-1:2010 standards and
therefore this product meets the requirements of the Low Voltage Directive
2014/35/EU.
---|---
| Read the installation guide before mounting the product. Unprofessional work
activities on electrical installations may result in a threat of danger to
the life and health of human beings and livestock!
| Under no circumstances the secondary circuit of the CT may be opened when
the CT is mounted on a primary current and current is flowing in the primary
circuit. High voltages may appear on the secondary leads when this circuit is
left open.
| RoHS Directive (EU) 2015/863
Janitza electronics GmbH states that they only uses qualified component in
their products from manufacturers, whose specifications meet or exceed the
requirements of the European Directive for the Restriction of use of certain
Hazardous Substances.
| WEEE Directive 2012/19/EU
The ‚crossed out wheeled bin‘ symbol indicates that the equipment should not
be disposed as unsorted municipal waste. Contact a qualified recycler for
disposal.