Archipelago Lighting TubulRCH SMARt8 LED Tube Installation Guide

July 9, 2024
ARCHIPELAGO LIGHTING

Archipelago-Lighting-logo

Archipelago Lighting TubulRCH SMARt8 LED Tube

Archipelago-Lighting-TubulRCH-SMARt8-LED-Tube

INSTALLATION INSTRUCTIONS

THE SMARt8 IS CAPABLE OF EITHER UL TYPE‐A WITH A BALLAST, OR TYPE‐B FOR DIRECT WIRE WITH LINE AND NEUTRAL.

  • The retrofit kit includes one (1) LED tube, one (1) installation instruction, and one (1) field‐applied label.
  • Risk of fire or electric shock – the electrical rating of this product is 120‐277V, the installer must determine whether they have AC120‐277V at the luminaire before installation.
  • Risk of fire or electric shock – retrofit kit installation requires knowledge of florescent lighting luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.
  • Risk of fire or electric shock – install this kit only in the luminaires that have the construction features and dimensions shown in the drawings.
  • Risk of fire or electric shock – do not use this kit in luminaires that employ shunted bi‐pin lamp holders (found in fixtures that use instant start ballasts).
  • Rick of fire or electric shock – luminaires wiring, ballasts, or other electrical parts may be damaged when drilling for installation of retrofit kit hardware. Check for enclosed wiring and components.
  • To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.

FOR DIRECT REPLACEMENT OF FLUORSCENT LAMPS (32W/48T8, 30W/48T8, 28W/48T8, 25W/48T8)

  • STEP 1: Disconnect power from fixture
  • STEP 2: Remove diffuser (if necessary)
  • STEP 3 : Remove the exiting florescent lamps from the luminaire
  • STEP 4: Install the LED T8 replacement lamp.
  • STEP 5: Replace diffuser (if removed in STEP 2)
  • STEP 6: Switch on power to the luminaire

Archipelago-Lighting-TubulRCH-SMARt8-LED-Tube-fig-1

DANGER – RISK OF SHOCK-DISCONNECT POWER BEFORE INSTALLATION.
The retrofit kits including Installation Instructions, LED Lamp, Luminaire Marking Labels. The T8 LED tubes are intended to retrofit Listed surface mounted, type Non-IC or type IC recessed mounted fluorescent luminaires with or without diffuser for maximum four lamps with lamp to lamp distance 11 cm minimum; Or retrofit surface mounted Listed fluorescent luminaires without diffuser for maximum six lamps with lamp to lamp distance 5.5 cm minimum. The products are intended to be used in dry and damp locations only.

ELECTRICAL RATINGS:

Model Number

| Input Ratings| Nominal Length (FT)
---|---|---
Voltage (V)| Frequency (Hz)| Current (mA)| Wattage (W)
LT8F208xxU5| 120‐277V| 50/60Hz| 80mA| 8W| 2FT
LT8F312xxU5| 120‐277V| 50/60Hz| 110mA| 12W| 3FT
LT8F412xxU5| 120‐277V| 50/60Hz| 110mA| 12W| 4FT
LT8F415xxU5| 120‐277V| 50/60Hz| 140mA| 15W| 4FT

  • STEP 1 : Shut OFF power work.
  • STEP 2: Remove existing fluorescent tube(s) and diffuser (if applicable) and open the ballast cover.
  • STEP 3: Disconnect luminaire supply wirings L and N to branch circuit as shown in Figure 2.

Archipelago-Lighting-TubulRCH-SMARt8-LED-Tube-fig-2

  • STEP 4: Original circuit as shown in Figure 3. Cut lamp holder leads “1, 2, 3, 4, L, N”, then check whether the lamp holder is shunted. Cut as far away from the lamp holders to allow for longer lengths of wire at both lamp holders.
    Note : Ballast must be retained in place.Archipelago-Lighting-TubulRCH-
SMARt8-LED-Tube-fig-3

  • STEP 5: Check the lamp holders. If the lamp holders are shunted, go to STEP 6. If the lamp holders are not shunted, go to STEP 7. For “One End” wiring configuration only, “WARNING: To avoid potential fire or shock hazard, do not use this retrofit kit in luminaires employing shunted bi‐pin lamp holders. Note: Shunted lamp holders are found only in fluorescent luminaires with Instant‐Start ballasts. Instant‐start ballasts can be identified by the words “Instant Start” or “I.S.” marked on the ballast. This designation may be in the form of a statement pertaining to the ballast itself, or may be combined with the marking for the lamps with which the ballast is intended to be used, for example F40T12/IS. For more information, contact the LED luminaire retrofit kit manufacturer.”

  • STEP 6: If the lamp holders are shunted, connect one lead from each lamp holder to branch circuit as follows, “Leads 3 and 4” connected to L; “Leads 1 and 2” connected to N as shown in Figure 4Archipelago-Lighting-TubulRCH-SMARt8-LED-Tube-fig-4

  • STEP 7a : The lamp holders are not shunted. “One End” or “Both End” wiring can be selected. For “One End” wiring, connect one lead from each lamp holder to branch circuit as follows, “Leads 1” connected to L; “Leads 2” connected to N. or “Leads 4” connected to L; “Leads 3” connected to N.Archipelago-Lighting-TubulRCH-SMARt8-LED-Tube-fig-5

  • STEP 7b: For “Both Ends” wiring, connect one lead from each lamp holder to branch circuit as follows, “Leads 1 and Leads 2” connected to L; “Leads 3 and Leads 4” connected to N. or “Leads 1” connected to L; “Leads 3” connected to N. as shown in Figure 6.Archipelago-Lighting-TubulRCH-SMARt8-LED-Tube-fig-6

  • STEP 8: Attach the field‐applied label to the luminaire. Install the ballast cover and diffuser (if applicable) back on luminaire, and LED T8 tube as show in Figure 7.Archipelago-Lighting-TubulRCH-SMARt8-LED-Tube-fig-7

SERVICE CONTACT:
Archipelago Lighting, Inc.
Technical Support
866-912-3220
technical@archipelagolighting.com

Documents / Resources

| Archipelago Lighting TubulRCH SMARt8 LED Tube [pdf] Installation Guide
LT8F208xxU5, LT8F312xxU5, LT8F412xxU5, LT8F415xxU5, TubulRCH SMARt8 LED Tube, TubulRCH SMARt8, LED Tube, Tube
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals