HearthRite HB06MN-1 Blue Flame Vent Free Natural Gas Space Heater Installation Guide
- July 9, 2024
- HearthRite
Table of Contents
- HB06MN-1 Blue Flame Vent Free Natural Gas Space Heater
- IMPORTANT SAFETY INFORMATION
- PRODUCT FEATURES
- FRESH AIR FOR COMBUSTION AND VENTILATION
- INSTALLATION
- OPERATING YOUR HEATER
- CLEANING AND MAINTENANCE
- TROUBLESHOOTING
- SPECIFICATIONS
- ILLUSTRATED PARTS
- WARRANTY INFORMATION
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
This Owner’s Manual is provided and hosted by Appliance Factory Parts.
EMPIRE HB06MN-1
Owner’s Manual
Shop genuine replacement parts for EMPIRE
HB10MN-1
HB06MN-1 HB10MN-1 HB10TN-1
Find Your EMPIRE Fireplace Parts – Select From 642
Models
– ——- Manual continues below ——–
BLUE FLAME VENT-FREE
NATURAL GAS
SPACE HEATER
HB06MN-1 Blue Flame Vent Free Natural Gas Space Heater
OWNER’S OPERATION AND INSTALLATION MANUAL
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air For Combustion and Ventilation section on page 4 of this manual.
Do not store, or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or gas supplier.
WARNING: Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage.
Refer to this manual for correct installation and operational procedures. For
assistance or additional information consult a qualified installer, service
agency, or gas supplier.
This appliance may be installed in an aftermarket* permanently located,
manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating
plate.
This appliance is not convertible for use with other gases.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
Water vapor is a by-product of gas combustion. An unvented room heater
produces approximately one (1) ounce (30ml) of water for every 1,000 BTU’s
(.3KW’s) of gas input per hour. Refer to page 3.
Installer: Please leave these instructions with the consumer.
Consumer: Please retain these instructions for future use.
IMPORTANT SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and completely before
trying to assemble, operate, or service this heater. Improper use of this
heater can cause serious injury or death from burns, fire, explosion,
electrical shock, and carbon monoxide poisoning.
**WARNING: Do not use any accessory not approved for use with this
heater.
WARNING:** Any change to this heater or its controls can be dangerous.
Do not place clothing or other flammable material on or near the appliance.
Never place any objects on the heater.
Due to high temperatures, heater should be kept out of traffic and away from
furniture and draperies. Surface of heater becomes very hot when running
heater.
Keep children and adults away from hot surface to avoid burns or clothing
ignition. Heater will remain hot for a time after shut down. Allow surface to
cool before touching.
Carefully supervise young children when they are in the same room with heater.
Make sure grill guard is in place before running heater.
Keep the appliance area clear and free from combustible materials, gasoline,
and other flammable vapors and liquids.
-
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
-
If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch, do not use any phone in your building.
• Immediately call your gas sup plier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department. -
This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensor (ODS) safety shutoff system.
The ODS shuts down the heater if not enough fresh air is available. See Fresh Air For Combustion And Ventilation pages 4 through 6. -
Keep all air openings in the front and bottom of heater clear and free of debris. This will insure enough air for proper combustion.
-
If heater shuts off. Do not relight until you provide fresh outside air. If heater keeps shutting off, have it serviced.
-
Do not operate heater
• where flammable liquids or vapors are used or stored under dusty conditions -
Turn heater off before using furniture polish, wax, carpet cleaner, or similar products, If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
-
Do not use heater if any part has been under water.
Immediately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water. -
Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
-
Operating heater above elevations of 4,500 feet could cause pilot outage.
-
Do not install in a bathroom except model HB06MN.
DANGER: Carbon monoxide poisoning may lead to death!
Carbon Monoxide Poisoning:
Early signs of carbon monoxide poisoning resemble the flu with headaches,
dizziness, or nausea.
If you have these signs, the heater may not be working properly. Get fresh air
at once! Have heater serviced. Some people are more affected by carbon
monoxide than others. These include pregnant women, persons with heart or lung
disease or anemia, those under the influence of alcohol, and those at high
altitudes.
Natural Gas: Natural gas is odorless.
An odor-making agent is added to natural gas. The odor helps you detect a
natural gas leak . However, the odor added to natural gas can fade. Natural
gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for
reference. It is your guide to safe and proper operation of this heater.
PRODUCT FEATURES
Figure1-Vent-Free Natural Gas Heater
SAFETY DEVICE
A standard requirement for all vent-free room heaters. This heater has a pilot
with an Oxygen Depletion Sensor(ODS) safety shutoff system.
The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater is equipped with a piezo ignitor.
This system requires no matches, batteries, or other sources to light heater.
THERMOSTATIC HEAT CONTROL ON THERMOSTAT MODELS
These heaters have a control valve with a thermostat sensing bulb. This
results in the greatest heater comfort and may result in lower gas bills.
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of
local codes, use the latest edition of National Fuel Gas Code ANSZ223.1, also
known as NFPA 54.
Available from :
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
QUALIFIED INSTALLING AGENCY
Installation and replacement of gas piping, gas utilization equipment or
accessories and repair and servicing of equipment shall be performed only by a
qualified agency. The term “qualified agency” means any individual, firm,
corporation, or company that either in person or through a representative is
engaged in and is responsible for (a) the installation, testing, or
replacement of gas piping or (b) the connection, installation, testing,
repair, or servicing of equipment; that is experienced in such work; that is
familiar with all precautions required, and that has complied with all the
requirements of the authority having jurisdiction.
State of Massachusetts: The installation must be made by a licensed
plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters
shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
In the state of Massachusetts, unvented propane or nature gas-fired space
heaters shall be prohibited in bedrooms and bathrooms.
UNPACKING
- Remove heater from carton.
- Remove all protective packaging applied to heater for shipment.
- Check heater for any shipping damage. If heater is damaged. promptly inform dealer where you bought heater.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
Water vapor is a by-product of gas combustion. An unvented room heater
produces approximately one (1) ounce (30ml) of water for every 1,000 BTU’s
(.3KW’s) of gas input per hour.
Unvented room heaters are recommended as supplemental heat (a room) rather
than a primary heat source (an entire house). In most supplemental heat
applications, the water vapor does not create a problem. In most applications,
the water vapor enhances the low humidity atmosphere experienced during cold
weather.
The following steps will help insure that water vapor does not become a problem.
- Be sure the heater is sized properly for the application, including ample combustion air and circulation air.
- If high humidity is experienced, a dehumidifier may be used to help lower the water vapor content of the air.
- Do not use an unvented room heater as the primary heat source.
FRESH AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code. NFPA 54/ANS Z223.1,
Section 5.3. Air for Combustion and Ventilation. All spaces in homes fall into
one of the three following ventilation classifications:
- Unusually Tight Construction
- Unconfined Space
- Confined Space
The information on pages 4 through 6 will help you classify your space and
provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for
combustion and ventilation.
However, in buildings of unusually tight construction. you must provide
additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the outside atmosphere have a continuous
water vapor retarder with a rating of one perm (6×10 -11 kg per pa-sec-m2) or
less with openings gasketed or sealed and
b. weather stripping has been added on openable windows and doors and
c. caulking or sealants are applied to areas such as joints around window and
door frames, between sole plates and floors, between wall-ceiling joints,
between wall panels, at penetrations for plumbing, electrical, and gas lines,
and at other openings. If your home meets all of the three criteria above, you
must provide additional fresh air.
See Ventilation Air From Outdoors, page 6.
If your home does not meet all of the three criteria above see
Determining Fresh-Air Flow for Heater Location, page 5.
Confined and Unconfined Space
The National Fuel Gas Code ANS Z223.1 defines a confined space as a space
whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances installed in that space and an
unconfined space as a space whose volume is not less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all
appliances installed in that space.
Rooms communicating directly with the space in which the appliances are
installed*, through openings not furnished with doors, are considered a part
of the unconfined space.
This heater shall not be installed in a confined space or unusually tight
construction unless provisions are provided for adequate combustion and
ventilation air.
- Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if you have a Confined or Unconfined Space*
Use this worksheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
-
Determine the volume of the space (length×width×height).
Length×Width×Height= cu.ft. (volume of space)
Example: Space size 18ft. (length)×16ft.( width)×8ft. (ceiling height)=2304cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space. -
Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
(volume of space) 50 cu. ft.=(Maximum Btu/Hr the space can support)
Example: 2304 cu. ft. (volume of space) 50 cu.ft.=46.1 or 46.100(maximum Btu/Hr the space can support)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes. -
Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater ………….Btu/Hr
Gas water heater……………. Btu/Hr
Gas furnace …………………Btu/Hr
Vented gas heater ………………..Btu/Hr
Gas Fireplace logs …………………Btu/Hr
Other gas appliances + ………………Btu/Hr
Total =…………………………….. Btu/Hr
Example:
Gas water heater 44,000 Btu/Hr
Vent free heater + 10,000 Btu/Hr
Total = 54,000 Btu/Hr
*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors. -
Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
Btu/Hr (maximum the space can support)
Btu/Hr (actual amount of Btu/Hr used)
Example : 46,080 Btu/Hr(maximum the space can support)
54,000 Btu/Hr(actual amount of Btu/Hr used)
The space in the above example is a confined space because the actual Btu/Hr
used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh are. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space
provides an unconfined space, remove door to adjoining room or add ventilation
grills between rooms. See Ventilation Air From inside Building, page 5.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page
6 .
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.
AIR FOR COMBUSTION AND VENTILATION Continued
VENTILATION AIR
Ventilation Air From Inside Building This fresh air would come from an
adjoining unconfined space. When ventilating to an adjoining unconfined space,
you must provide two permanent openings: one within 12″ of the ceiling and one
within 12″ of the floor on the wall connecting the two spaces (see options 1
and 2, Figure 2). You can also remove door into adjoining room (see option 3,
Figure 2). Follow the National Fuel Gas Code NFPA 54/ANS Z223.1. Section 5.3,
Air for Combustion and Ventilation for required size of ventilation grills or
ducts
WARNING: Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
VENTILATION AIR
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts: You must provide
two permanent openings: one within 12″ of the ceiling and one within 12″ of
the floor.
Connect these items directly to the outdoors or spaces open to the outdoors.
These spaces include attics and crawl spaces. Follow the National Fuel Gas
Code NFPA 54/ANS Z223.1, Section 5.3.
Air for Combustion and Ventilation for required size of ventilation grills or
ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic if
attic has a thermostat-controlled power vent.
Heated air entering the attic will activate the power vent.
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified service person must install heater. Follow all local
codes.
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural, do not install
heater. Call dealer where you bought heater for proper type heater.
INSTALLATION NEEDS
Before installing heater, make sure you have the items listed below:
- piping (check local codes)
- sealant (resistant to natural gas)
- equipment shutoff valve*
- ground joint union
- test gauge connection*
- sediment trap
- tee joint
- pipe wrench
*A CSA/AGA design-certified equipment shutoff valve with 1/8″ NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA/AGA design certified equipment shutoff valve from your dealer.
LOCATING HEATER
This heater is designed to be mounted on a wall.
For convenience and efficiency, install heater
- where there is easy access for operation, inspection, and service
- in coldest part of room
CAUTION: If you install the heater in a home garage
- heater pilot and burner must be at least 18 inches above floor.
- locate heater where moving vehicle will not hit it.
WARNING: Never install the heater
- in a bathroom (Models HB10MN and HB10TN, only HB06MN is allowed in bathroom. Check local codes.)
- in a recreational vehicle.
- where curtains, furniture, clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the heater.
- as a fireplace insert.
- in high traffic areas.
- in windy or drafty areas.
When the HB06MN is installed in bathrooms,do not use flammable products such as aerosol hair spray, foot spary or any product that contains flammable vapors and keep towels away from heater.(only HB06MN is allowed in a bathroom.)
**CAUTION:** This heater creates warm air currents.These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist may discolor walls.
**WARNING:** Maintain the minimum clearances shown in Figure 4. If you can, provide greater clearances from floor, ceiling, and joining wall.
INSTALLING THERMOSTAT SENSING BULB
For T-Stat Model Only
- Pull out the sensing bulb from the two clips located in the shippng position according to the direction as shown by the arrow. There is no need to take out the two bulb clips.
- Take out the bulb clip from the hardware package and insert it into the square hole and then insert the sensing bulb into the bulb clip (see Figure 5).
FASTENING HEATER TO WALL Mounting Bracket
The mounting bracket is located on back panel of heater (see Figure 6). It has
been taped there for shipping. Remove mounting bracket from back panel.
Removing Lower Front Panel Of Heater
- Remove two Screws near bottom corners of lower front panel.
- Pull bottom of lower front panel forward, then down (see Figure 7).
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket to wall.
Attach mounting bracket to wall only in one of two ways:
- Attaching to wall stud
- Attaching to wall anchor
Attaching to Wall Stud: This method provides the strongest hold. Insert mounting screws through mounting bracket and into wall studs.
Attaching to Wall Anchor: This method allows you to attach mounting bracket to
hollow walls (wall areas between studs) or to solid walls (concrete or
masonry).
Decide which method better suits your needs. Either method will provide a
secure hold for the mounting bracket.
Marking Screw Locations
-
Tape mounting bracket to wall where heater will be located.
Make sure mounting bracket is level.
WARNING: Maintain minimum clearances shown in Figure 4. If you can, provide greater clearances from floor and joining wall. -
Mark screw locations on wall. (see Figure 8)
Note: Only mark last hole on each end of mounting bracket. Insert mounting screws through these holes only. -
Remove tape and mounting bracket from wall.
Attaching Mounting Bracket To Wall
Note: Wall anchors, mounting screws, and spacers are in hardware package. The
hardware package is provided with heater.
Attaching to Wall Stud Method
For attaching mounting bracket to wall studs
- Drill holes at marked locations using 9/64″ drill bit.
- Place mounting bracket onto wall. Line up last hole on each end of bracket with holes drilled in wall.
- Insert mounting screws through bracket and into wall studs.
- Tighten screws until mounting bracket is firmly fastened to wall studs.
Attaching to Wall Anchor Method
For attaching mounting bracket to hollow walls (wall areas between studs) or
solid walls (concrete or masonry)
-
Drill holes at marked locations using 5/16″ drill bit. For solid walls (concrete or masonry), drill at least 1″ deep.
-
Fold wall anchor as shown in Figure 9 below.
-
Insert wall anchor (wings first) into hole. Tap anchor flush to wall.
-
For thin walls (1/2″ or less), insert red key into wall anchor. Push red key to “pop” open anchor wings. (see Figure 10)
IMPORTANT: Do not hammer key! For thick walls (over 1/2″ thick) or solid walls, do not pop open wings. -
Place mounting bracket onto wall. Line up last hole on each end of bracket with wall anchors.
-
Insert mounting screws through bracket and into wall anchors.
-
Tighten screws until mounting bracket is firmly fastened to wall.
Placing Heater On Mounting Bracket
- Locate two horizontal slots on back panel of heater (see Figure 11).
- Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket.
Installing Bottom Mounting Screw
- Locate bottom mounting hole. This hole is near bottom on back panel of heater (see Figure 12).
- Mark screw locations on wall.
- Remove heater from mounting bracket.
- If installing bottom mounting screw into hollow or solid wall, install wall anchors. Follow steps 1 through 4 under Attaching To Wall Anchor Method. If installing bottom mounting screw into wall stud, drill hole at marked locations using 9/64″ drill bit.
- Replace heater onto mounting bracket.
- Place spacer between bottom mounting holes and wallanchor or drilled hole.
- Hold spacer in place with one hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole.
- Tighten screw until heater is firmly secured to wall. Do not over tighten.
Note: Do not replace lower front panel at this time. Replace lower front panel after making gas connections and checking for leaks (see page 9).
CONNECTING TO GAS SUPPLY
WARNING: A qualified service person must connect heater gas supply.
Follow all local codes.
WARNING: This appliance requires a 3/8″ NPT (National Pipe Thread) inlet
connection to the pressure regulator.
WARNING: Never connect heater to private (non-utility) gas well. This gas
is commonly known as well-head gas.
IMPORTANT: Check your gas line pressure before connecting heater to gas
line. Gas line pressure must be no greater than 10.5 inches of water.
If gas line pressure is higher, heater regulator damage could occur.
CAUTION: Use only new, black iron or steel pipe.
Internally-tinned copper tubing may be used in certain areas.
Check your local codes. Use pipe of large enough diameter to allow proper gas
volume to heater.
If pipe is too small, undue loss of pressure will occur.
Typical Inlet Pipe Diameters
All models up to 20,000 BTU’s use 3/8’’ or greater pipe;
All models 25,000 BTU’s and higher, use 1/2” or greater pipe.
Installation must include an equipment shutoff valve, union, and plugged 1/8″
NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be
up stream from heater (see Figure 13).
*A CSA/AGA design-certified equipment shutoff valve with 1/8″ NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA/AGA design-certified equipment shutoff valve from your dealer.
IMPORTANT: Install an equipment shutoff valve in an accessible location.
The equipment shutoff valve is for turning on or shutting off the gas to the
appliance.
Apply pipe joint sealant lightly to male threads. This will prevent excess
sealant from going into pipe. Excess sealant in pipe could result in clogged
heater valves.
CAUTION: Use pipe joint sealant that is resistant to natural gas.
Install sediment trap in supply line as shown in Figure 13. Locate sediment
trap where it is within reach for cleaning. Locate sediment trap where trapped
matter is not likely to freeze. A sediment trap traps moisture and
contaminants. This keeps them from going into heater controls. If sediment
trap is not installed or is installed wrong, heater may not run properly.
IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping and/or fittings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections for leaks after installing
or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a mixture of
liquid soap and water to all joints. Bubbles forming show a leak. Correct all
leaks at once.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 K Pa)
- Disconnect appliance with its appliance main gas valve (control valve) and equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.
- Cap off open end of gas pipe where equipment shutoff valve was connected.
- Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.
- Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
- Correct all leaks at once.
- Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 K Pa)
-
Close equipment shutoff valve (see Figure 14).
-
Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.
-
Check all joints from gas meter to equipment shutoff valve (see Figure 15).Apply mixture of liquid soap and water to gas joints.
Bubbles forming show a leak. -
Correct all leaks at once.
Pressure Testing Heater Gas Connections
- Open equipment shutoff valve (see Figure 14).
- Open main gas valve located on or near gas meter.
- Make sure control knob of heater is in the OFF position.
- Check all joints from equipment shutoff valve to control valve (see Figure 15 ). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
- Correct all leaks at once.
- Light heater (see Operating Heater, pages 10 and 11 for non-thermostat models or page 12 for thermostat model).Check the rest of the internal joints for leaks.
- Turn off heater (see To Turn Off Gas to Appliance, page 11 for non-thermostat models or page 12 for thermostat model).
- Replace lower front panel.
In the State of Massachusetts the gas cock must be a T handle type.
The State of Massachusetts requires that a flexible appliance connector cannot
exceed three feet in length.
OPERATING YOUR HEATER
NON-THERMOSTAT MODEL
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. When lighting the pilot, follow , these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to
smell next to the floor because some gas is heavier than air and will settle
on the floor .
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electric switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use
tools. If the knob will not push in or turn by hand, don’t try to repair it,
call a qualified service technician or gas supplier. Force or attempted repair
may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control which has been under water.
OPERATING YOUR HEATER
Manual Control Models
LIGHTING
INSTRUCTIONS
-
STOP! Read the safety information on the side of heater.
-
Check that gas supply to heater is on.
-
Push in gas control knob slightly and turn clockwise to the OFF position.
-
Wait five (5) minutes to clear out any air. Then smell for gas, including near the floor.
If you smell gas, STOP! Follow “B” in the safety information on the side of the heater. If you do not smell gas, go to the next step. -
Push in gas control knob slightly and turn counter clock wise to “PILOT/IGN” and depress for five(5) seconds
NOTE: The first time that the heater is operated after connecting the gas supply , the control knob should be depressed for about thirty (30) seconds. This will allow air to bleed from the gas system. -
With control knob pressed in, push down and release the ignitor button. This will light pilot. If needed, keep pressing ignitor button until pilot lights.
-
Keep control knob depressed for ten (10) seconds after lighting pilot. If pilot goes out, repeat steps 5,6 and 7.
-
To select the desired heating level, partially press down the control knob slightly and rotate counterclockwise . Release the downward pressure on the knob while continuing to turn until the knob locks at the desired setting position. Do not operate between locked positions.
- Set control knob to desired heating position.
NOTE: Both HIGH and LOW are locked positions. You must press in control knob before turning it from these positions.
CAUTION: Do not try to adjust heating levels by using the equipment shutoff valve.
TO TURN OFF
GAS TO APPLIANCE
Shutting Off Heater
- Turn control knob clockwise to the OFF position.
- Turn off all electric power to the appliance if service is to be performed.
Shutting Off Burner Only (Pilot Stays Lit)
Turn control knob clockwise to the PILOT/IGN position.
MANUAL LIGHTING
PROCEDURE
- Remove lower front panel(see Figure 7 page 7).
- Follow steps 1 through 5 under Lighting Instructions.
- With control knob pressed in, strike match. Hold match to pilot until pilot lights.
- Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob. Follow step 8 under Lighting Instructions.
- Replace lower front panel.
THERMOSTAT MODEL
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas.
Be sure to smell next to the floor because some gas is heavier than air and
will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.
- Do not touch any electric switch, do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand, don’t try to
repair it , call a qualified service technician or gas supplier.
Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately
call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
-
STOP! Read the safety information on the side of heater.
-
Make sure equipment shutoff valve is fully open.
-
Turn control knob clockwise to the OFF position.
-
Wait five(5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information on the side of heater. If you don’t smell gas, go to the next step.
-
Turn control knob counterclockwise to the PILOT position. Press in control knob for five(5) seconds. (see Figure18).
Note: You may be running this heater for the first time after hooking up to gas supply.
If so, the control knob may need to be pressed in for 30 seconds. This will allow air to bleed from the gas system.
If control knob does not pop up when released, contact a qualified service person or gas supplier for repairs. -
With control knob pressed in, push down and release ignitor button. This will light pilot. The pilot is attached to the front of burner. The pilot can be seen through the glass panel. If needed, keep pressing ignitor button until pilot lights.
Note: If pilot does not stay lit, refer to Troubleshooting, pages 14 through -
Also contact a qualified service person or gas supplier for repairs. Until repairs are made, light pilot with match.To light pilot with match, see Manual Lighting Procedure.
-
Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
If control knob does not pop up when released, contact a qualified service person or gas supplier for repairs.
Note: If pilot goes out,repeat steps 3 through 7.This heater has a safety interlock system. Wait one(1) minute before lighting pilot again. -
Turn control knob counterclockwise to desired heating level. The main burner should light. Set control knob to any heat level between HI and LO.
CAUTION: Do not try to adjust heating levels by using the equipment shutoff valve.
THERMOSTAT CONTROL OPERATION
The thermostatic control used on this model differs from standard
thermostats.Standard thermostats simply turn on and off the burner. The
thermostat used on this heater senses the room temperature. At times the room
may exceed the set temperature.
If so,the burner will shut off. The burner will cycle back on when room
temperature drops below the set temperature.
The control knob can be set to any comfort level between HI and LO.
Note: The thermostat sensing bulb measures the temperature of air near
the heater cabinet.This may not always agree with room temperature(depending
on housing construction, installation location, room size, open air
temperatures,etc.)
Frequent use of your heater will let you determine your own comfort levels.
TO TURN OFF GAS
TO APPLIANCE
Shutting Off Heater
- Turn control knob clockwise to the OFF position.
- Turn off all electric power to the appliance if service is to be performed.
Shutting Off Burner Only (pilot stays lit )
Turn control knob clockwise to the PILOT position.
MANUAL LIGHTING
PROCEDURE
-
Remove lower front panel (see Figure 7 page 7).
-
Follow steps through 5 under Lighting Instructions on page12.
-
With control knob pressed in, strike match. Hold match to pilot until pilot lights.
-
Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
Follow step 8 under Lighting Instuctions on page 12. -
Replace lower front panel.
INSPECTING BURNER
Check pilot flame pattern and burner flame pattern often.
PILOT FLAME PATTERN
Figure 20 shows a correct pilot flame pattern. Figure 21 shows an incorrect
pilot flame pattern. The incorrect pilot flame is not touching thermocouple.
This will cause the thermocouple to cool. When the thermocouple cools, the
heater will shut down. If pilot flame pattern is incorrect, as shown in Figure
21.
- turn heater off (see To Turn Off Gas to Appliance on page 11 for non-thermostat models or page 12 for thermostat models.)
- see Troubleshooting. pages 14 through 16.
BURNER FLAME PATTERN
Figure 22 shows a correct burner flame pattern. Figure 23 shows an incorrect
burner flame pattern. If burner flame pattern is incorrect, as shown in Figure
23.
WARNING: If yellow tipping occurs, your heater could produce increased
levels of carbon monoxide. If burner flame pattern shows yellow tipping,
follow instructions at bottom of this page.
Notice: Do not mistake orange flames with yellow tipping. Dirt or other
fine particles enter the heater and burn causing brief patches of orange
flame.
- turn heater off (see To Turn Off Gas to Appliance pages10 & 11 for non-thermostat models and page 12 for thermostat models)
- see Troubleshooting. pages 14 through 16
CLEANING AND MAINTENANCE
WARNING: Turn off heater and let cool before servicing.
CAUTION: You must keep control areas, burner, and circulating air
passageways of heater clean.
Inspect these areas of heater before each use. Have heater inspected yearly by
a qualified service person.
Heater may need more frequent cleaning due to excessive lint from carpeting,
bedding material, pet hair, etc.
ODS/PILOT AND BURNER
- Use a vacuum cleaner, pressurized air or a small, soft bristled brush to clean.
CLEANING BURNER PILOT AIR INLET HOLE
We recommend that you clean the unit every 2,500 hours of operation or every
three months. We also recommend that you keep the burner tube and pilot
assembly clean and free of dust and dirt. To clean these parts we recommend
using compressed air no greater than 30 PSl. Your local computer store,
hardware store, or home center may carry compressed air in a can. You can use
a vacuum cleaner in the blow position. If using compressed air in a can,
please follow the directions on the can. If you don’t follow directions on the
can, you could damage the pilot assembly.
- Shut off the unit, including the pilot. Allow the unit to cool for at least thirty minutes.
- Inspect burner and pilot for dust and dirt.
- Blow air through the ports/slots and holes in the burner.
Also clean the pilot assembly. A yellow tip on the pilot flame indicates dust
and dirt in the pilot assembly. There is a small pilot air inlet hole about
two inches from where the pilot flame comes out of the pilot assembly (see
Figure 24).
With the unit off , lightly blow air through the air inlet hole.
You may blow through a drinking straw if compressed air is not available.
CABINET
Air Passageways
- Use a vacuum cleaner or pressurized air to clean.
Exterior
- Use a soft cloth dampened with a mild soap and water mixture.
Wipe the cabinet to remove dust.
TROUBLESHOOTING
Note : All troubleshooting items are listed in order of operation.
WARNING: Only a qualified service person should service and repair
heater.
CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot.
This can damage ODS/pilot unit.
OBSERVED PROBLEM | POSSIBLE CAUSE | REMEDY |
---|
When ignitor button is pressed in,
there is no spark at ODS/pilot.| 1. Ignitor electrode is positioned
wrong.
2. Ignitor electrode is broken.
3. Ignitor electrode is not connected to ignitor cable.
4. Ignitor cable is pinched or wet.
5. Broken ignitor cable.
6. Bad piezo ignitor.| 1. Replace ignitor.
2. Replace ignitor.
3. Reconnect ignitor cable.
4. Free ignitor cable if pinched by any metal or tubing. Keep
ignitor cable dry.
5. Replace ignitor cable.
6. Replace piezo ignitor.
When ignitor button is pressed in,
there is a spark at ODS/pilot but no
ignition.| 1. Gas supply turned off or equipment shutoff valve is closed.
2. Control knob not fully pressed in while pressing ignitor button.
3. Air in gas lines when installed.
4. ODS/pilot is clogged.
5. Gas regulator setting is not cor rect
6. Control knob not in PILOT position.| 1. Turn on gas supply or open
equipment shutoff valve.
2. Fully press in control knob while pressing ignitor button.
3. Continue holding down control knob. Repeat igniting operation until
air is removed.
4. Clean ODS/pilot (see Cleaning and Maintenance Page 13) or
replace ODS/pilot assembly.
5. Replace gas regulator.
6. Turn control knob to PILOT position.
ODS/pilot lights but flame goes out when control knob is released.| 1.
Control knob is not fully pressed in.
2. Control knob is not pressed in long enough.
3. Equipment shutoff valve is not fully open.
4. Thermocouple connection is loose at control valve.
5. Thermocouple damaged.
6. Control valve damaged.| 1. Press in control knob fully.
2. After ODS/pilot lights, keep control knob pressed in 30 seconds.
3. Fully open equipment shutoff valve.
4. Hand tighten until snug, then tighten 1/4 turn more.
5. Replace thermocouple.
6. Replace control valve.
Burner(s)does not light after
ODS/pilot is lit.| 1. Burner orifice is clogged.
2. Burner orifice diameter is too small.
3. Inlet gas pressure is too low.| 1. Clean burner orifice (see
Cleaning and Maintenance Page 13) or replace burner orifice.
2. Replace burner orifice.
3. Contact local natural gas company.
Delayed ignition of burner(s).| 1. Manifold pressure is too low.
2. Burner orifice is clogged.| 1. Contact local natural gas company.
2. Clean burner (see Cleaning and Maintenance Page 13) or replace burner
orifice.
Burner backfiring during combustion.| 1. Burner orifice is clogged or
damaged.
2. Burner is damaged.
3. Gas regulator is defective.| 1. Clean burner orifice (see Cleaning
and Maintenance Page 13) or replace.
2. Replace burner.
3. Replace gas regulator.
Yellow flame during burner combustion.| 1. Not enough air.
2. Gas regulator is defective.
3. Inlet gas pressure is too low .| 1. Check burner for dirt and
debris.
If found, clean burner(see Cleaning And Maintenance Page 13).
2. Replace gas regulator.
3. Contact local natural gas company.
Slight smoke or odor during initial operation.| 1. Residues from
manufacturing processes| 1. Problem will stop after a few hours of
operation.
Heater produces a whistling noise when burner is lit.| 1. Turning
control knob to HI position when burner is cold.
2. Air in gas line.
3. Air passageways on heater blocked.
4. Dirty or partially clogged burner orifice.| 1. Turn control knob
to LO position and let warm up for a minute.
2. Operate burner until air is removed from line. Have gas line
checked by local natural gas company.
3. Observe minimum installation clearances (see Figure 4, Page 7).
4. Clean burner (see Cleaning and Maintenance Page 13) or replace burner
orifice.
Heater produces a clicking/ticking
noise just after burner is lit or shut off.| 1. Metal is expanding while
heating or contracting while cooling.| 1. This is common with most
heaters. if noise is excessive,
contact qualified service person.
White powder residue forming within
burner box or on adjacent walls or furniture.| 1. When heated the vapors
from furniture polish, wax, carpet cleaners, etc. turn into white powder
residue.| 1. Turn heater off when using furniture polish, wax, carpet
cleaner or similar products.
WARNING: If you smell gas
- Shut off gas supply.
- Do not try to light any appliance.
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
IMPORTANT: Operating heater where impurities in air exist may create
odors.
Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues,
new carpet ortextiles, etc., create fumes. These fumes may mix with combustion
air and create odors.
OBSERVED PROBLEM | POSSIBLE CAUSE | REMEDY |
---|---|---|
Heater produces unwanted odors. | 1.Heater is burning vapors from paint, hair |
spray, glues, etc. (See IMPORTANT statement above).
2.Gas leak. See Warning Statement at top of page.| 1.Ventilate room. Stop
using odor causing products while heater is running.
2.Locate and correct all leaks(see Checking Gas Connections, page 10).
Heater shuts off in use (ODS operates).| 1. Not enough fresh air is
available.
2. Low line pressure.
3. ODS/pilot is partially clogged.| 1. Open window and/or door for
ventilation.
2. Contact local natural gas company.
3. Clean ODS/pilot (see Cleaning page 12).
Gas odor exists even when control knob is in OFF position.| 1. Gas leak. See
Warning Statement at top of page.
2. Control valve is defective.| 1. Locate and correct all leaks(see Checking
Gas Connections, page 10).
2. Replace control valve.
Gas odor during combustion.| 1.Foreign matter between control valve and
burner.
2.Gas leak. See Warning Statement at top of page.| 1.Take apart gas tubing and
remove foreign matter.
2.Locate and correct all leaks (see Checking Gas Connections, page 10).
Moisture/condensation noticed on
windows.| 1. Not enough combustion/ventilation
air.| 1. Refer to Air for Combustion and Ventilation requirements, page 4.
SPECIFICATIONS
| HB06MN| HB10MN| HB10TN
---|---|---|---
Btu(available)| 6,000| 6,000/10,000| 10,000
Gas Type| Natural Only| Natural Only| Natural Only
Ignition| Piezo| Piezo| Piezo
Pressure Regulator setting| 3″W.C| 3″W.C| 3″W.C
Inlet Gas Pressure* (inches of water)| |
Maximum| 10.5″| 10.5″| 10.5″
Minimum| 4″| 4″| 4″
Dimensions, Inches (HxWxD)| | |
Heater| 19×14-1/4×7| 19×14-1/4×7| 19×14-1/4×7
Carton| 22×16-3/4×8-1/8| 22×16-3/4×8-1/8| 22×16-3/4×8-1/8
Weight (pounds)| | |
Heater| 12| 13| 14
Shipping| 15| 16| 17
Note: Dimensions listed are outer most points on the heater (includes control knobs and grill).
- For purposes of input adjustment.
REPLACEMENT PARTS
Note: Use only original replacement parts. This will protect your
warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized dealer from whom you purchased this product.
If they are unable to supply original replacement part(s), call the number on
the front of this manual.
When contacting your dealer or HearthRite, have ready:
- your name
- your address
- model and serial numbers of your heater
- how heater was malfunctioning
- type of gas used (propane/LP or natural gas)
- purchase date
- warranty card
Usually, we will ask you to return the defective part to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized dealers of this product. If they can’t supply original
replacement part(s), contact HearthRite at (800)851-3153.
TECHNICAL SERVICE
You may have further questions about installation, operation, or
troubleshooting. If so, contact HearthRite at (800)851-3153.
SERVICE HINTS
When Gas Pressure Is Too Low
- Pilot will not stay lit
- Burner will have delayed ignition
- Heater will not produce specified heat
When Gas Quality Is Bad
- Pilot will not stay lit
- Burner will produce flames and soot
- Heater will backfire when lit
You may feel your gas pressure is too low or the gas quality is poor. If so, contact your local natural gas supplier.
ACCESSORIES
Purchase these heater accessories from your local dealer. If they can not
supply these accessories, contact HearthRite for information.
You can also write to the address listed on the front of this manual.
FLOOR MOUNTING STAND
For locating heater on the floor away from a wall. Complete installation
instructions provided with floor mounting stand.
ILLUSTRATED PARTS
BREAKDOWN HB06MN
PARTS LIST HB06MN
This list contains replaceable parts for your heater. When ordering replacement parts, follow the instructions listed under Replacement Parts on page17 of this manual.
KEY NO. | PART NO. | DESCRIPTION | QTY. |
---|---|---|---|
1 | MB10008E | Cabinet Assembly | 1 |
2 | MB09003E | Lower Front Panel Assembly | 1 |
3 | MB11005E | Reflector Unit | 1 |
4 | ML086-03 | Glass | 1 |
5 | ML087-03 | Upper Glass Retainer | 1 |
6 | ML088-03 | Lower Glass Retainer | 1 |
7 | ML069-02 | Self Tapping Screw | 12 |
8 | NV2020-12 | Control Valve | 1 |
9 | ML073-01 | Ignitor Line | 1 |
10 | ML029-01 | Control Valve Fixed Nut | 1 |
11 | MB16002 | Control Knob Assembly | 1 |
12 | NRV81FI-3 | Pressure Regulator | 1 |
13 | ML079-01 | Self Locking Screw | 2 |
14 | ML119-01 | Pressure Tap | 1 |
15 | MB40033 | Main Inlet Tube Assembly | 1 |
16 | MB40045 | ODS Line Assembly | 1 |
17 | MB40043 | Gas Outlet Tube Assembly | 1 |
18 | NBB10-000M1 | Burner | 1 |
19 | ML101-02 | Burner Connector | 1 |
20 | ML091-06 | Injector | 1 |
21 | ML103-02 | Left Burner Support Bracket | 1 |
22 | ML129-02 | Regulator Mounting Bracket | 1 |
23 | ND1103x600x9 | ODS/Pilot Assembly | 1 |
23-1 | ND0803-6 | Thermocouple | 1 |
23-2 | ND0807-B2 | Ignitor Electrode | 1 |
24 | ML105-01 | ODS Deflector | 1 |
25 | 6170-5Z | Nut | 2 |
26 | ML057-05 | Grill Guard | 1 |
27 | ML084-03 | Middle Panel | 1 |
28 | ML060-02 | Mounting Bracket | 1 |
29 | ML083-03 | Ignitor Assembly | 1 |
PARTS AVAILABLE NOT SHOWN
MB28001 | Assembly Hardware | 1 |
---|---|---|
ML070-11E | CSA/AGA Label | 1 |
ML071-01 | Gas Instruction Decal | 1 |
ILLUSTRATED
PARTS BREAKDOWN HB10MN
PARTS LIST HB10MN
This list contains replaceable parts for your heater. When ordering replacement parts, follow the instructions listed under Replacement Parts on page17 of this manual.
KEY NO. | PART NO. | DESCRIPTION | QTY. |
---|---|---|---|
1 | MB10008E | Cabinet Assembly | 1 |
2 | MB09003E | Lower Front Panel Assembly | 1 |
3 | MB11005E | Reflector Unit | 1 |
4 | ML086-03 | Glass | 1 |
5 | ML087-03 | Upper Glass Retainer | 1 |
6 | ML088-03 | Lower Glass Retainer | 1 |
7 | ML069-02 | Self Tapping Screw | 12 |
8 | NV2020-1213 | Control Valve | 1 |
9 | ML073-01 | Ignitor Line | 1 |
10 | ML029-01 | Control Valve Fixed Nut | 1 |
11 | MB16002 | Control Knob Assembly | 1 |
12 | NRV81FI-3 | Pressure Regulator | 1 |
13 | ML079-01 | Self Locking Screw | 2 |
14 | MB40034 | Main Inlet Tube Assembly | 1 |
15 | MB40045 | ODS Line Assembly | 1 |
16 | MB40054 | Gas Outlet Tube Assembly | 1 |
17 | NBB10-000M1 | Burner | 1 |
18 | ML101-02 | Burner Connector | 1 |
19 | ML091-05 | Injector | 1 |
20 | ML103-02 | Left Burner Support Bracket | 1 |
21 | ML129-02 | Regulator Mounting Bracket | 1 |
22 | ND1103x600x9 | ODS/Pilot Assembly | 1 |
22-1 | ND0803-6 | Thermocouple | 1 |
22-2 | ND0807-B2 | Ignitor Electrode | 1 |
23 | ML105-01 | ODS Deflector | 1 |
24 | 6170-5Z | Nut | 2 |
25 | ML057-05 | Grill Guard | 1 |
26 | ML084-03E | Middle Panel | 1 |
27 | ML060-02 | Mounting Bracket | 1 |
28 | ML083-03 | Ignitor Assembly | 1 |
PARTS AVAILABLE NOT SHOWN
MB28001 | Assembly Hardware | 1 |
---|---|---|
ML070-13 | CSA/AGA Label | 1 |
ML071-01 | Gas Instruction Decal | 1 |
ILLUSTRATED PARTS
BREAKDOWN HB10TN
PARTS LIST
HB10TN
This list contains replaceable parts for your heater. When ordering
repalcement parts, follow the instructions listed under Replacement Parts on
page17 of this manual.
KEY NO. | PART NO. | DESCRIPTION | QTY. |
---|---|---|---|
1 | MB10007E | Cabinet Assembly | 1 |
2 | MB09003E | Lower Front Panel Assembly | 1 |
3 | MB11005E | Reflector Unit | 1 |
4 | ML086-03 | Glass | 1 |
5 | ML087-03 | Upper Glass Retainer | 1 |
6 | ML088-03 | Lower Glass Retainer | 1 |
7 | ML069-02 | Self Tapping Screw | 12 |
8 | SIT544-130 | SIT Thermostat Valve Assembly | 1 |
9 | ML111-02 | Thermostat Valve Base/Bracket | 1 |
10 | 6170-5Z | NUT | 2 |
11 | 845-4.8x60Z | Screws | 2 |
12 | ML057-05 | Grill | 1 |
13 | ML079-01 | Self Locking Screw | 2 |
14 | ML084-03E | Middle Panel | 1 |
15 | NRV81FI-3 | Pressure Regulator | 1 |
16 | ML073-01 | Ignitor Line | 1 |
17 | ML060-02 | Mounting Bracket | 1 |
18 | MB40048 | Main Inlet Tube Assembly | 1 |
19 | MB40049 | ODS Line Assembly | 1 |
20 | MB40050 | Burner Inlet Tube Assembly | 1 |
21 | NBB10-000M1 | Burner | 1 |
22 | ML101-01 | Burner Connector | 1 |
23 | ML091-05 | Injector | 1 |
24 | ML103-02 | Left Burner Support Bracket | 1 |
25 | ML129-02 | Regulator Mounting Bracket | 1 |
26 | ND1103x800x9 | ODS/Pilot Assembly | 1 |
26-1 | ND0803-8 | Thermocouple | 1 |
26-2 | ND0807-B2 | Ignitor Electrode | 1 |
27 | ML105-01 | ODS Upper Deflector | 1 |
28 | ML083-03 | Ignitor Assembly | 1 |
PARTS AVAILABLE NOT SHOWN
MB28001 | Assembly Hardware | 1 |
---|---|---|
ML160-19E | CSA/AGA Label | 1 |
ML071-01 | Gas Instruction Decal | 1 |
ML065-01 | Thermostat Sensing Bulb Clip | 1 |
WARRANTY INFORMATION
KEEP THIS WARRANTY
SERIAL NUMBER
LABEL
Always speafy model and serial numbers when communicating with the factory
We reserve the right lo amend these specifications al any time without notice.
The only warranty applicable is our standard written warranty. We make no
other warranty, expressed or implied.
LIMITED WARRANTY HEARTHRITE VENT-FREE GAS SPACE HEATERS
HearthRite warrants this product to be free from defects in materials,
components and limited labor for (3) three years from the date of first
purchase, provided that the product has been properly installed, operated and
maintained in accordance with all applicable instructions. To make certain
under this warranty, the Bill of Sale or cancelled check musi be presented.
This warranty is extended only to the original retail purchaser. This warranty
covers the cost of part(s) required to restore this heater to proper operating
condition and an allowance for labor when provided by a HearthRite Authorized
Service Center. Warranty part(s) MUST be obtained through authorized dealers
of this product and/or HearthRile who will provide original factory
replacement parts. Failure to use original factory replacement parts voids
this warranty. The heater MUST be installed by a qualified installer in
accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts thal are not in original condition
because of normal wear and tear or parts that fail or become damaged as a
result of misuse, accidents, lack of proper maintenance or defects caused by
improper installation.
Some States do not allow a limitation on how long an implied warranty lasts or
an exclusion of limitation of inadental or consequential damages, so the above
limitation on impled warranties, or exclusion of limitation on damages may not
apply lo you.
This warranty gives you specific legal nghts, and you may also have other
rights that vary from state to state. For information about this warranty,
please write to:
A Division of Empire Comfort Systems, Inc.
918 Freeburg Avenue
Belleville, IL 62220
Phone : 618-233-7420 or
1-800-851-3153
Fax : 618-233-7097 or
1-800-443-8648
www.hearthrite.com