EMERSON E2 Setup with RTD-Net Interface MODBUS Device for 527-0447 User Guide
- June 3, 2024
- Emerson
Table of Contents
E2 Setup with RTD-Net Interface MODBUS
Device for 527-0447
Quick Start Guide
This document will guide you through setting up and commissioning the RTD-Net
Interface MODBUS device in the E2 controller.
Note: Open MODBUS Description files require E2 firmware version 3.01F01
or higher.
E2 Setup with RTD-Net Interface MODBUS Device for 527-0447
STEP 1: Upload the Description File to the E2 Controller
- From UltraSite, connect to your E2 controller.
- Right-click on the E2 icon and select Description File Upload.
- Browse to the location of the description file and click Upload.
- After uploading, reboot the E2 controller. (The button labeled “RESET” on the main board resets the controller. Pressing and holding this button for one second will cause the E2 to reset and retain all programmed applications, logs, and other data stored in memory.) For more information on rebooting the E2, refer to the E2 User Manual P/N 026-1614.
STEP 2: Activate the License of the Device
- From the E2 front panel (or via Terminal Mode), press , (System Configuration), and (Licensing).
- Press (ADD FEATURE) and enter your license key.
STEP 3: Add the Device to the E2 Controller
- Press , (System Configuration), (Network Setup), (Connected I/O Boards and Controllers).
- Press (NEXT TAB) to go to the C4: Third Party tab. The name of the device should be displayed in the list. Enter the number of devices to add and press to save changes.
STEP 4: Assign a MODBUS Port
- Press , (System Configuration), (Remote Communications), (TCP/IP Setup).
- Select the COM port the device is connected to, press (LOOK UP) and select the appropriate MODBUS selection.
- Set Data Size, Parity, and Stop Bits. Press (LOOK UP) to select the appropriate values.
Note: RTD-Net has a factory standard setting of 9600, 8, N, 1. The MODBUS Address range 0 to 63 is set using SW1. For more information, refer to the manufacturer’s installation instructions.
STEP 5: Commission the Device onto the E2 Controller
- Press , (System Configuration), (Network Setup), (Network Summary).
- Highlight the device and press (COMMISSION). Select the MODBUS port where you will assign the device, then select the MODBUS device address.
STEP 6: After Assigning the MODBUS Address of the Device and Verifying that the Connections are Wired Properly, the Device Should Appear Online Make sure that the polarity is reversed on the E2 Controller.
RTD-Net is a trademark and/or registered trademark of RealTime Control Systems
Ltd. in the United States and other countries.
This document is not intended as an official Technical/Service Bulletin of
Emerson Climate Technologies. It is a helpful advisory on field service issues
and resolutions. It does not pertain to all firmware, software and/or hardware
revisions of our products. All information contained is intended as an
advisory and no assumption on warranty or liability should be assumed.
We reserve the right to make modifications to the products described herein as
part of our continuous improvement process to achieve customer goals.
Document Part # 026-4956 Rev 0 05-MAR-2015
This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical
documentation and updates.
Join Emerson Retail Solutions Technical Support on Facebook.
http://on.fb.me/WUQRnt
The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any product remains solely with the purchaser and end-user.
026-4956 05-MAR-2015 Emerson is a trademark of Emerson Electric Co.
©2015 Emerson Climate Technologies Retail Solutions, Inc. All rights reserved.
EMERSON. CONSIDER IT SOLVED™
Documents / Resources
|
EMERSON E2 Setup with RTD-Net Interface MODBUS Device for
527-0447
[pdf] User Guide
E2 Setup with RTD-Net Interface MODBUS Device for 527-0447, E2 Setup with RTD-
Net Interface MODBUS Device, RTD-Net Interface MODBUS Device, MODBUS Device,
MODBUS Device E2 Setup, RTD-Net Interface MODBUS Device E2 Setup, E2 Setup,
MODBUS Device for 527-0447
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>