ABB Change-over switches Installation Guide

June 7, 2024
ABB

ABB Change-over switches Installation Guide

Installation Instruction, OTM_FC

diagram

OTM30-125-C_

diagram

Mounting Positions

text, whiteboard
a close up of a device

Control Circuit

Only an authorised electrician may perform the electrical installation and maintenance of motorized switch. Do not attempt any installation or maintenance actions when a motorized switch is connected to the electrical mains. Before starting work, make sure that the switch is de-energised.
diagram, engineering drawing

  1. Terminal for motor operator voltage supply

  2. Control terminal for push buttons

  3. Terminal for state information (also used with the automatic control unit)

  4. Control terminal for automatic control unit (If used OMD controller)

Do not couple power for the control terminal. See the correct terminal for the power supply.

Manual operation: Local

a close up of a device
graphical user interface

Electrical operation is prevented when the handle is attached to the switch panel.

Electrical operation: Remote

Never open any covers on the product. There may be dangerous external control voltages inside the motorized switch even if the voltage is turned off.

Never handle control cables when the voltage of the motorized switch or external control circuits are connected.

Exercise sufficient caution when handling the unit.

diagram, engineering drawing
diagram
diagram
Automatic Operation

Resetting Fuse

Impulse Control

diagram

Continuous Control

If a new command is given before the switch has reached the position of the previous command, the internal protection may operate.

Locking

Prevent Manual and Electrical Operation

Locking Possible at any position. Check position before locking.

diagram


diagram

State Information

diagram

Technical Data

Motor operator, control circuit

|

Value

|

Cabling/Rating

---|---|---
Rated operational voltage U [V]| 110-240 Vac/dc 50-60Hz|
| 24 Vdc|
Operating voltage range| 0.85.. 1.1 x U|
Operating angle| 90° 0-I, I-0, 0-II, II-0; 180° I-0-II|
Operating time| See Table 2|
Protection degree| IP 20, front panel|
Rated impulse withstand voltage Uimp| 4 kV|
Voltage supply| PE N L| 1,5 -2,5mm2
F2| Max. MCB 16A|
Control terminal for the push-buttons| C II I 0| 1,5 -2,5mm2
Maximum cable length| 100 m|
Terminal for state information

Also used with the automatic control unit

| | 1,5mm2


3A AC-1/250V

Common, voltage supply| 1|
Position of change-over switch I| 2|
Position of change-over switch II| 3|
Handle attached or motor operator locked| 4|
SCPD| Max. MCB C2A|
Control terminal for automatic control unit If used OMD_ controller|
| 1,5-2,5mm2
Common, voltage supply from motor operator| 1| 24VDC
Close switch I or open switch II| 2| 24VDC 500mW
Close switch II or open switch I| 3| 24VDC 500mW
Operating temperature| -25… +55 °C|
Transportation and storage temperature| -40… +70 °C|
Altitude| Max. 2000m|

Table 1 : General technical data of motor operators.

Type| Voltage

U e [V]

| Nominal current a)

I n [A]

| Current Inrush a)

____A]

| Operating time a)

I-0, 0-I,

0-II, II-0

[s]

| Operating transfer time a) I-II or II-I

[s]

| OFF-time when operating a) I-II or II-I

[s]

---|---|---|---|---|---|---
__

OTM40…125_C

| 110-240 Vac/dc| 0,2 – 0,5| 1,5 – 3,0| 0,5 – 1,0| 1,2 – 1,5| 0,4 – 0,8
24 Vdc| 0,6| 3,6| 0,6 – 1,3| 1,4 – 2,1| 0,6 – 1,0

Table 2: Specified technical data of motor operators.

Terminal clamp sets OZX, Bridging bars OMZC

OZX_


diagram, whiteboard
diagram, engineering drawing

OMZC_



OTS_

diagram
diagram

diagram
diagram
OA_

OTVS0

a close up of a device
OTP_

a screenshot of a cell phone
a close up of a tool
diagram

ABB Oy
Low Voltage Switches
P.O Box 622
FI-65101 VAASA, Finland
Telephone +358 10 22 11
Telefax +358 10 22 45708
www.abb.com