EMERSON EC3-XM678D CONTROLLERS FOR MULTIPLEXED CABINETS Installation Guide
- June 7, 2024
- Emerson
Table of Contents
EC3-XM678D CONTROLLERS FOR MULTIPLEXED CABINETS
CONTROLLERS FOR MULTIPLEXED CABINETS
EC3-XM678D
REL. 5.4
The same recommendations apply to probes. Let air circulate by the cooling holes.
1. GENERAL WARNING
1.1
PLEASE READ BEFORE USING THIS MANUAL
· This manual is part of the product and should be kept near the instrument
for easy and quick reference.
· The instrument shall not be used for purposes different from those described
hereunder. It cannot be used as a safety device.
· Check the application limits before proceeding.
· Emerson reserves the right to change the composition of its products, even
without notice, ensuring the same and unchanged functionality.
1.2
SAFETY PRECAUTIONS
· Check the supply voltage is correct before connecting the instrument. · Do
not expose to water or moisture: use the controller only within the operating
limits avoiding sudden temperature changes with high atmospheric humidity to
prevent formation of condensation · Warning: disconnect all electrical
connections before any kind of maintenance.
· Fit the probe where it is not accessible by the End User. The instrument
must not be opened.
· In case of failure or faulty operation send the instrument back to the
distributor or to Emerson (see address) with a detailed description of the
fault.
· Consider the maximum current which can be applied to each relay (see
Technical Data).
· Ensure that the wires for probes, loads and the power supply are separated
and far enough from each other, without crossing or intertwining.
· In case of applications in industrial environments, the use of mains filters
(our mod. FT1) in parallel with inductive loads could be useful.
2. BEFORE PROCEEDING
2.1 CHECK THE SW REL. OF THE EC3-XM678D 1. Look at the SW rel. of EC3-XM678D printed on the label of the controller.
Figure 1c
5. WIRING DIAGRAM AND CONNECTIONS
5.1 IMPORTANT NOTE
XM device is provided with disconnectable terminal block to connect cables
with a cross section up to 1.6 mm2 for all the low voltage connection: the
RS485, the LAN, the probes, the digital inputs and the keyboard. Other inputs,
power supply and relay connections are provided with screw terminal block or
fast-on connection (5.0 mm). Heat-resistant cables have to be used. Before
connecting cables make sure the power supply complies with the instrument’s
requirements. Separate the probe cables from the power supply cables, from the
outputs and the power connections. Do not exceed the maximum current allowed
on each relay, in case of heavier loads use a suitable external relay. Note:
Maximum current allowed for all the loads is 16 A. The probes shall be mounted
with the bulb upwards to prevent damages due to casual liquid infiltration. It
is recommended to place the thermostat probe away from air streams to
correctly measure the average room temperature. Place the defrost termination
probe among the evaporator fins in the coldest place, where most ice is
formed, far from heaters or from the warmest place during defrost, to prevent
premature defrost termination.
5.2 EC3-XM678D
2. If the SW release is 5.4 proceed with this manual otherwise contact
Emerson to get the right manual.
3. GENERAL DESCRIPTION
The EC3-XM678D are high level microprocessor-based controllers for multiplexed
cabinets suitable for applications on medium or low temperature. They can be
inserted in a LAN of up to 8 different sections which can operate, depending
on the programming, as standalone controllers or following the commands coming
from the other sections. The EC3-XM678D are provided with 4 and 6 relay
outputs respectively to control the solenoid valve, defrost – which can be
either electrical or hot gas – the evaporator fans, the lights, an auxiliary
output and an alarm output and with one output to drive stepper electronic
expansion valves. The devices are also provided with four probe inputs, one
for temperature control, one to control the defrost end temperature of the
evaporator, the third for the display and the fourth can be used for
application with virtual probe or for inlet/outlet air temperature
measurement. In addition, they are provided by other two probes that have to
be used for superheat measurement and regulation. Finally, they are equipped
with the three digital inputs (free contact) fully configurable by parameters.
The instruments are equipped with the HOTKEY connector that permits to be
programmed in a simple way. Direct serial output RS485 ModBUS-RTU compatible
permits a simple XWEB interfacing. RTC are available as options. The HOTKEY
connector can be used to connect X-REP display (Depending on the model).
4. INSTALLATION AND MOUNTING
This device can operate without any user interface, but normal application is
with Emerson CH660 keyboard.
Figure 1a
Figure 1b
The CH660 keyboard shall be mounted on vertical panel, in a 29 x 71 mm hole, and fixed using the special bracket supplied as shown in Fig. 1a/1b. The temperature range allowed for correct operation is 0 – 60°C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity.
5.3 VALVE CONNECTIONS AND CONFIGURATION
5.3.1 Valve connections !!! All the connections between EC3-XM678D and valve
has to be done with the controller NOT supplied.!!!
5.3.2 Type of cables and max length To connect the valve to the controller,
use only shielded cables with section greater than or equal to 0.823 mm²
(AWG18). A twisted shielded cable with the above specification is suggested.
Don’t connect the shield to any ground, live it floating.
The max distance between an XM controller and a valve must not exceed 10 m.
5.3.3 Valve selection To avoid possible problems, before connecting the valve
configure the driver by making the right changes on the parameters. a. Select
the kind of motor (tEU parameter) b. Check if the valve is present in tEP
parameter table reported here below.
CHECK THE FOLLOWING TABLE FOR A RIGHT SETTING
!!! In any case, the unique and valid reference has to be considered the datasheet made by valve manufacturer. Emerson cannot be considered responsible in case of valve damaging due to wrong settings!!!
tEP
Model
LSt
uSt
CPP
(steps10)(steps10) (mA*10)
0
Manual settings
Par
Par
Par
1
Danfoss ETS25/50
7
262
10
2
Danfoss ETS100
10
353
10
3
Danfoss ETS250/400
11
381
10
11
Emerson EX4/EX5/EX6
5
75
50
CHd (mA*10)
Par
10
10
10
10
Sr (step/s)
Par
300
300
300
500
tEu (bip/ unip) Par
bP
bP
bP
bP
HSF (Half/full)
Par
FUL
FUL
FUL
FUL
If you can see your valve on the table, please select the valve through tEP parameter. In this way, you can be sure of a right configuration. About the connection, please pay attention to the following table to have a quick reference on the connection mode for valves of different manufacturer
4 WIRES VALVES (BIPOLAR) Connection numbering 45 46 47 48
ALCO EX4/5/6/7/8
BLUE BROWN BLACK WHITE
DANFOSS ETS
BLACK WHITE
RED GREEN
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
1/12
5-6 WIRES VALVES (UNIPOLAR) Connection numbering 45 46 47 48 49 Common
SPORLAN
ORANGE RED
YELLOW BLACK GRAY
SAGINOMIYA
ORANGE RED
YELLOW BLACK GRAY
1. After selecting the valve, please switch off and on the controller to load
the new settings.
2. Switch off the controller, before connecting the valve. Do the connection
with controller off.
3. Switch the controller on
5.4 ABSOLUTE MAXIMUM POWER
EC3-XM678D is able to drive a wide range of stepper valves, on the following table are indicated the maximum values of current that the actuator can supply to the stepper wiring. The TF20D Emerson transformer has to be used.
NOTE:
The electrical power absorption of the valve can be unrelated to refrigeration power that valve has. Before using the actuator, please read the technical manual of the valve supplied by the manufacturer and check the maximum current used to drive the valve in order to verify that they are lower than those indicated below.
VALV E
BIPOLAR VALVES (4 wires)
UNIPOLAR VALVES (5-6 wires)
Maximum Current 0.5 A Maximum Current 0.33 A
5.5 KEYBOARD DISPLAY CH660
Polarity: Terminal [34] [-] Terminal [35] [+]
The EC3-XM678D board can operate also without keyboard.
Use twisted shielded cable AWG 18 or less in case of long distance. Max distance: 30 m
5.6 LAN CONNECTION
Follow next steps to create a LAN connection, which is a necessary condition
to perform synchronized defrost (also called master-slave functioning):
- connect a shielded cable between terminals [38] [-] and [39] [+] for a maximum of 8 sections;
- the Adr parameter is the number to identify each electronic board. Address duplication is not permitted, in this case the synchronized defrost and the communication with monitoring system is not guaranteed (the Adr is also the ModBUS address). For example, a correct configuration is the following:
If the LAN is well connected, the green LED will be ON. If the green LED
blinks then the connection is wrongly configured. The max distance allowed is
30 m 5.7 SENSORS FOR SUPERHEAT CONTROL
Temperature probe: Pb6 terminals [19] – [20] without any polarity. Select the
kind of sensor with P6C parameter. Pressure transducer: Pb5 terminals: [21] =
input of the signal; [22] = Power Supply for 4 20 mA transducer; [20] = GND;
[23] = +5 VDC power supply for ratiometric pressure transducer. Select the
configuration of the transducer with parameter P5C. 5.8 HOW TO USE ONLY ONE
PRESSURE TRANSDUCER ON MULTIPLEXED APPLICATIONS
A working LAN connection is required (green LED lit on all EC3-XM678D boards
of the same LAN). Connect and configure a pressure transducer only on one
EC3XM678D of the network. Afterwards, the value of pressure read by the unique
transducer connected will be available to each device connected to the same
LAN.
By pressing UP ARROW button, the user will be able to enter a fast selection menu and to read the value of the following parameters:
dPP = measured pressure (only on master device). dP5 = value of temperature obtained from pressure temperature conversion. rPP = pressure value read from remote location (only for slave devices).
Examples of error messages: dPP = Err the local transducer read a wrong value,
the pressure is out of the
bounds of the pressure transducer or the P5C parameter is wrong. Check all
these options and eventually change the transducer;
rPF the remote pressure transducer is on error situation. Check the status of
the onboard GREEN LED: if this LED is OFF the LAN is not working, otherwise
check the remote transducer.
LAST CHECKS ABOUT SUPERHEAT
On the fast access menu:
dPP is the value read by the pressure gauge.
dP6 is the value read by the temperature probe, temperature of the gas on
the outlet section of the evaporator.
SH
is the value of the superheat. The nA or Err messages mean that the
superheat has no sense in that moment and its value is not available.
5.9 HOW TO CONNECT MONITORING SYSTEM
- Terminals [36] [-] and [37] [+]. 2) Use shielded twisted cable. For
example Belden® 8762 o 8772 or cat 5 cables. 3) Maximum distance 1 Km. 4) Don’t connect the shield to the earth or to GND terminals of the device, avoid accidental contacts by using insulating tape.
Only one device for each LAN has to be connected to the RS485 connection.
The Adr parameter is the number to identify each electronic board. Address
duplication is not permitted, in this case the synchronized defrost and the
communication with monitoring system is not guaranteed (the Adr is also the
ModBUS address).
5.10 DIGITAL INPUTS
- The terminals from [30] to [33] are all free of voltage; 2) Use shielded
cable for distance higher than one
meter; For each input, has to be configured: the polarity of activation, the function of the input and the delay of signaling.
The parameters to perform this configuration are i1P, i1F, i1d respectively for
polarity, functioning and delay.
The i1P can be:
cL = active when closed;
oP = active when opened.
The i1F can be:
EAL = external alarm,
bAL = serious lock alarm,
PAL = pressure switch alarm,
dor = door switch,
dEF = external defrost,
AUS = auxiliary activation command,
LiG = light activation,
OnF = board On/OFF,
FHU = don’t use this configuration, ES = day/night,
HdY = don’t use this configuration.
Then there is i1d parameter for delay of activation.
For the others digital inputs there are a set of the same parameters: i2P, i2F, i2d,
i3P, i3F, i3d.
5.11 ANALOG OUTPUT
– Selectable between 4 20 mA and 0 10 VDC. – Use CABCJ15 to perform the connections
It’s located near the terminal [39] on a 2-pin connector. It’s possible to use the output to control anti-sweat heaters through a chopped phase controller XRPW500 (500 W) or family XV…D or XV…K.
6. QUICK REFERENCE GUIDE: HOW TO RUN THE SELF ADAPTIVE REGULATION IN 4 STEPS.
1. After wiring the EC3-XM678D, set the proper gas via Fty parameter 2. Set the proper gas via Fty parameter, among the following
CODE REFRIGERANT OPERATING RANGE
r22
R22
-50 – 60°C/-58 – 120°F
134
R134A
-50 -60°C/-58 – 120°F
290
R290 Propane -50 – 60°C/-58 – 120°F
404
R404A
-70 – 60°C/-94 – 120°F
47A
R407A
-50 – 60°C/-58 – 120°F
47C
R407C
-50 – 60°C/-58 – 120°F
47F
R407F
-50 – 60°C/-58 – 120°F
410
R410A
-50 – 60°C/-58 – 120°F
448
R448A
-45 – 60°C/-69 – 120°F
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
2/12
CODE REFRIGERANT
449
R449A
450
R450A
507
R507
513
R513A
CO2
R744 – Co2
Pre-set refrigerant is R448A.
OPERATING RANGE
-45 – 60°C/-69 – 120°F -45 – 60°C/-69 – 120°F -70 – 60°C/-94 – 120°F -45 – 60°C/-69 – 120°F -50 – 60°C/-58 – 120°F
3. Configure the probes: – Regulation and evaporator probe are preset as NTC. If another kind of sensors is used, set it via P1c and P2c parameters. – Superheat evaporator outlet probe is pre-set as Pt1000, if another kind of sensor is used, set it via P6c parameter. – The PP11 (-0.5 11 bar) is pre- set as pressure probe. It operates at relative pressure (Pru = rE). If you’re using a ratiometric transducer, set P5c = 0 – 5, then use parameters PA4 and P20 to set the range NOTE: Check the pressure gauge reading with the value of dPP, press the UP arrow once to enter the Fast Access Menu. If ok, proceed; otherwise solve the situation before proceeding acting on par. Pru, PA4 and P20.
4. Set the parameters for self-adaptive regulation of superheat NOTE: The parameters Pb (regulation band) and Int (integral time) are automatically calculated by the controller
– Set CrE = no, this disables the continuous regulation of the temperature.
Default is CrE = no.
– Set SSH, superheating setpoint: a value between 4 – 8 is acceptable. Default
is SSH = 6
– Set ATU = y to start the self-adaptive regulation. Default is ATU = y. – Set
AMS = y to start the search of the lowest stable superheat. Default
is AMS = n. This function reduces automatically the setpoint in order to
optimize the use of the evaporator, keeping, at the same time, the
superheating regulation stable. The minimum allowed SH set point is LSH+2°C. –
Set LSH, low superheating limit: a value between 2 – 4 is acceptable. Default
is LSH = 2 – Set AnP, pressure filter: Default is AnP = 3. The value can be
increased up to 10 in case of too fast response of the pressure variations.
5. Set the parameters for the temperature regulation – Set the temperature setpoint. Default is 2°C – Set the differential HY: Default is 2°C. – If the capacity of the valve is higher than requested, it can be reduced by the par. MnF (Default is 100). A proper setting of MnF will reduce the time that the algorithm takes to reach the stability. MnF value doesn’t affect the band width.
7. BATTERY BACK UP CONNECTION
7.1 CONNECTION OF EXD-PM SUPERCAP
EXD-PM Supercap is designed to be used with Emerson products (EC3-XM678D, EXD- SH1/2);
!!!!! IMPORTANT !!!!! EXD-PM Supercap and EC3-XM678D must be powered by two different transformers; the failure of the observance of this rule may result in damage to the EXD-PM Supercap and / or the connected EC3-XM678D.
Wiring connection EC3-XM678D Terminal 61 (+) Terminal 62 (-)
EXD-PM Terminal 4 (12 VDC)
Terminal 3 (gnd)
7.2 EMERSON ECP-024 CONNECTION
The Emerson ECP-024 rechargeable accumulator can be connected to the EC3XM678D to close the stepper valve in case of power interruption.
Wiring connection EC3-XM678D Terminal 61 (+) Terminal 62 (-)
ECP-024 Terminal + Terminal –
About conditions of use and limitation please refer to the ECP-024 manuals.
8. USER INTERFACE
8.1 ICONS
Light
Cooling output
Fan
With icon ON the output is active, while with blinking icon there is a delay.
Defrost
Energy saving
Generic alarm
AUX Auxiliary relay Multimaster Enabled Clock / time
MEASUREMENT UNIT
°C, bar and (time) are ON depending on the selection.
DURING PROGRAMMING: blink the measurement units of temperature and pressure
8.2 KEYBOARD COMMANDS
Single commands: LIGHT relay AUX relay Manual defrost ON/OFF Energy Saving
Press light button. Press down arrow. Press and hold for 3 s the defrost button Press for 3 s the ON/OFF button (if the function is enabled). Press for 3 s the ON/OFF button (if the function is enabled).
Double commands:
Press and hold for about 3 s to lock (Pon) or unlock (PoF) the keyboard.
Pressed together to exit from programming mode or from menu; on submenus rtC and EEV this combination allow to come back to previous level.
Pressed together for 3 s allow to access to first level of programming mode.
8.3 HOW TO MODIFY THE SET POINT FOR AIR TEMPERATURE REGULATION
The thermostat set point is the value that will be used to regulate the air
temperature. The regulation output is controlled by the electronic valve or by
the relay.
Action BEGIN
Button or display
Notes
Press SET button for 3 s, the measurement units will blink together.
Value modification
or
With the arrows it’s possible to change the value within the LS and US parameters value.
EXIT
By pressing SET it is possible to confirm the value that will blink for about 2 s.
In any case, it is possible to wait for about 10 seconds to exit. In order to show the air temperature set is sufficient to press and release the SET button, the value is displayed for about 60 sec.KEY COMBINATIONS.
9. HOW TO PROGRAM THE PARAMETERS (PR1 AND PR2)
The device provide 2 programming levels: Pr1 with direct access and Pr2
protected with a password (intended for experts).
Action
ACCESS to Pr1
Button or display
Notes
Press and hold for about 3 seconds to have access to the first programming
level (Pr1).
Select item
or
Select the parameter or submenu using the arrows.
Show value
Press SET button.
Modify
Confirm and store
EXIT
or
Use the arrows to modify the value.
Press SET key: the value will blink for 3 seconds, and then the display will
show the next parameter.
Instantaneous exit from the programming mode, otherwise wait for about 10
seconds (without press any button).
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
3/12
9.1 HOW TO HAVE ACCESS TO “PR2”
To enter Pr2 programming menu: 1. Access to a Pr1 menu by pressing both
SET+DOWN keys for 3 seconds, the first parameter label will be showed; 2.
Press DOWN key till the Pr2 label will be showed, then press SET; 3. The
blinking PAS label will be showed, wait some seconds; 4. Will be showed “0 –
-” with blinking 0: insert the password [321] using the keys UP and DOWN and
confirming with SET key.
GENERAL STRUCTURE: The first two item rtC and EEV are related to submenus with
other parameters.
Action
Enter menu
Waiting for action Enter section list
Button or display
SEC
Notes
Press UP arrow for about 3 s, the icon will be ON. The menu to change the
section will be entered. SEC label will be displayed. Press SET to confirm.
The following list will be available to select the proper network function.
Select proper function
Or
LOC GLb
To gain access only to the local device. To share global commands to all the devices connected to the LAN.
· SET+UP keys on rtC or EEV submenus allow coming back to parameter list, ·
SET+UP keys on parameter list allow immediate exit.
9.2 HOW TO MOVE PARAMETER FROM PR1 TO PR2 AND VICE VERSA
Enter on Pr2; select the parameter; press together [SET + DOWN]; a left side
LED ON gives to the parameter the presence on Pr1 level, a left side LED OFF
means that the parameter is not present on Pr1 (only Pr2).
10. FAST ACCESS MENU
This menu contains the list of probes and some values that are automatically
evacuate by the board such as the superheat and the percentage of valve
opening. The values: nP or noP stands for probe not present or value not
evacuate, Err value out of range, probe damaged not connected or incorrectly
configured.
Action Entering
fast access menu
Use
or
arrows to select an
entry, then press
to see the value or to go on with
other value.
Exit
Button or display Notes
By press and release the UP arrow. The duration of the menu in case of
inactivity is about 3 min. The values that will be showed depend on the
configuration of the board. MAP Current map (0÷3): it shows which map is used.
HM Access to clock menu or reset of the RTC alarm; An Value of analog output;
SH Value of superheat. nA = not Available; oPP Percentage of valve opening.
dP1 (Pb1) Value read by probe 1. dP2 (Pb2) Value read by probe 2. dP3 (Pb3)
Value read by probe 3. dp4 (Pb4) Value read by probe 4. dP5 (Pb5) Temperature
read by probe 5 or value obtained from pressure transducer. dP6 (Pb6) Value
read by probe 6. dPP Pressure value read by (Pb5) transducer. rPP Virtual
pressure probe, only on slave. rCP Value of P4 remote probe for heaters. It is
displayed only with P4C = LAn. If the value is not available “noP” label is
displayed. dPr Regulation probe value rSE Real thermoregulation set point: the
value includes the sum of SET, HES and/or the dynamic set point if the
functions are enabled. L°t Minimum room temperature; H°t Maximum room
temperature; tMd Time to next defrost (mins) LSn Number of devices in the LAN
LAn Address list of devices in the LAN GAL To see all the active alarms in
each device connected to the LAN Pressed together or wait the timeout of about
60 sec
11. MENU FOR MULTIMASTER FUNCTION: SEC
The function “section” SEC is enabled when icon
is lit. It allows share the
commands, from a keyboard not physically connected to the board, through the
LAN functionality.
Confirm
Select and confirm an entry by pressing SET button.
Exit menu
Press SET and UP together or wait about 10 seconds.
(*) The devices on the LAN are indexed by using the Adr parameter (in ascending
order).
EXAMPLE: To send a command to in all the devices connected to the LAN: enter multimaster menu. Select and confirm GLb. Exit from multimaster menu. Enter the programming menu and set the parameter of global commands (from LMd to ACE). The new setting will be shared among the controllers connected to the LAN.
AT THE END OF THE PROGRAMMING PROCEDURE, SELECT THE
SECTION “LOC”. IN THIS WAY THE ICON WILL BE SWITCHED OFF!!!
11.1 SYNCHRONIZED DEFROST
The synchronized defrost allow to manage multiple defrost from different
boards connected through the LAN connection. In this way, the boards can
perform simultaneous defrosts with the possibility to end them in a
synchronized way.
The Adr parameter cannot be duplicated because in this case the defrost cannot be correctly managed.
Action BEGIN
Find Adr Modify
Adr
EXIT
Button or display
or
Notes
Press for 3 seconds, the rtC or other will be showed. The measurement unit
blinks. Press more than once the DOWN arrow to find the Adr parameter, the
press SET.
Set the value of Adr parameter, then press SET to confirm the parameter. Press
the two keys together to exit from menu or wait for about 10 seconds.
The LSn and LAn parameter are only to show the actual settings (read only). The following example of configuration:
DAILY DEFROST FROM RTC: [cPb = y] & [EdF = rtC] IdF Parameter: for safety
reason force the value of Idf at +1 respect to the interval between two Ld
parameters. The IdF timer is reinitialized after defrost and at every power-
on.
DEFROST START: at the time selected by the parameters Ld1 to Ld6 or Sd1 to
Sd6.
DEFROST END: if the probes reach the dtE temperature or for maximum MdF time.
SAFETY and RtC or RtF ALARM: with clock alarm the device will use the
parameter IdF, dtE and MdF.
!!! WARNING: Don’t set [EdF = rtC] and [CPb = n].!!!
MULTIMASTER DEFROST: all the probes with clock Table for example
Par.
Adr EdF IdF MdF dtE Ld1 Ld2 Ld3
Unit A (RTC)
n rtC (clock) 9 hours safety 45 min safety 12°C safety 06:00 1° 14:00 2° 22:00
3°
Unit B (RTC)
N + 1 rtC (clock) 9 hours safety 45 min safety 12°C safety 06:00 1° 14:00 2°
22:00 3°
Unit C (RTC)
N + 2 rtC (clock) 9 hours safety 45 min safety 12°C safety 06:00 1° 14:00 2°
22:00 3°
12. COMMISSIONING
12.1 CLOCK SETTING AND RTC ALARM RESET
If the clock is present: [EdF = rtC] enable the defrost from rtc [Ld1 – Ld6].
Action BEGIN
Button or display
Notes
UP arrow (press once) to access the fast access menu
Display HM identify the clock RTC submenu; press
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
4/12
Display
EXIT Note: Warning:
HUr = hour press
to confirm/modify
Min = minutes press
to confirm/modify
…… don’t use others parameters if present.
Press for about 10 seconds. The operation resets
the RTC alarm.
The rtC clock menu is present also on the second level of parameters. If the board shows the rtF alarm, the device has to be changed.!!!
13.5 VALVE CAPACITY REDUCING MNF PARAMETER
Thanks to the parameter MnF it’s possible to reduce the capacity of the valve,
to fine tune the valve to the evaporator. The regulation band is not affected
from the modification of the MnF parameter. See below the behaviour of the
capacity of the valve, when the MnF parameter is adjusted.
12.2
ELECTRONIC VALVE SETTINGS
Some parameters have to be checked: [1] Superheat temperature probe: Ntc, Ptc,
Pt1000 with parameter P6C. The
sensor has to be fixed at the end of the evaporator. [2] Pressure transducer:
[4 20 mA] or ratiometric P5C = 420 or 5Vr with
parameter P5C. [3] Range of measurement: check the parameter of conversion PA4
and P20
that are related to the transducer. TRANSDUCER: [-0.5/7 bar] or [0.5/8 bar
abs] the correct setup is relative pressure with PA4 = -0.5 and P20 = 7.0. The
[0.5/12 bar abs] the correct setup is relative pressure with PA4 = -0.5 and
P20 = 11.00.
Example of virtual pressure with unique [4 20 mA] or [0 5 V] transducer:
Param. Adr
EC3-XM678D_1 without transducer
n
EC3-XM678D_2 + with transducer
n + 1
EC3-XM678D_3+ without transducer
n + 2
LPP
LPP = n
LPP = Y
LPP = n
P5C
LAN or not connect P5C= 4-20 mA or 0-
LAN or not
the probe
5 V
connect the probe
PA4
Not used
-0.5 bar
Not used
P20
Not used
11.0 bar
Not used
[4] From EEV submenu: select the correct kind of gas with FTY parameter. [5] Use the following parameters to setup the right valve driving, according to the valve datasheet from the manufacturer.
KIND OF REGULATION FOR SUPERHEAT: SELF
ADAPTIVE OR MANUAL OPERATING MODE
13.1 GENERAL CONSIDERATIONS: SELF ADAPTIVE OR MANUAL SH CONTROL
The controller is able to regulate the superheat in manual or self-adaptive
mode, according to the value of the parameter ATU, autotuing enabling.
· With ATU = n: the manual SH regulation is performed · With ATU = y: the
self-adaptive SH regulation is performed
13.2 MANUAL OPERATING MODE – ATU = NO
The temperature and SH regulation can be performed in 2 ways according to the
value of the parameter CrE: on/off or continuous. See below in details
Standard temperature regulation
13.2.1 ON/OFF TEMPERATURE REGULATION [CrE = n] 1. Temperature regulation is
ON/OFF and it depends on the SET point and HY
parameter (differential) Valve is closed when the temperature reaches the set
point and open when the temperature is higher than set point + differential.
2. The superheat is regulated to be closer to its set point. 3. With more
pauses normally also the humidity is bigger. 4. Regulation pauses can be
realized using Sti and Std parameters (during these pauses the valve is
closed).
13.2.2 COUNTINUOUS REGULATION OF THE TEMPERATURE [CrE = Y] (with superheat
regulation): 1. The HY parameter becomes temperature band for PI control. A
default good
value is 10°K. 2. The regulation of injection is continuous and the cooling
output is always on.
The icon
is always ON excluding the defrost phase.
3. The superheat is regulated following the SSH parameter. 4. Regulation
pauses can be realized using Sti and Std parameters (during
these pauses the valve is closed). 5. Increasing the Int integral time it is
possible to decrease the speed of reaction
of the regulator on the HY band.
13.3 SELF ADAPTIVE OPERATING MODE ATU = YES
Auto-adaptive means to find and maintain the condition of the lowest super
heating according to the load and environmental conditions present in a given
time on the evaporator. The parameter ATU enables the self-adaptive mode for
the superheat regulation. In this functioning the values of Pb and inC
parameter are automatically set by the controller according to the kind of
applications and the response of the system.
With the ATU = YES, CrE must be set at NO.
The self-adaptive algorithm does not affect, the functions related to the
forced opening of the valve in special situation such as:
· Forced opening of the valve at start of regulation, parameter SFP
(percentage) and SFd (time).
· Forced opening of the valve after defrost, parameter oPd (percentage) and
Pdd (time).
13.4 MINIMUM STABLE SUPERHEAT SEARCH – AMS = YES, AMS = YES
With the parameter AMS, the minimum stable superheat search function is
enabled.
With AMS = yES controllers start searching the minimum stable value for the
SH, the minimum admitted value in any case is LSH + 2°C (4°F).Please take it
in consideration, before setting LSH value.
NOTE: During the soft start phase (oPE, SFd), MnF parameter is not taken in consideration and the capacity of the valve is set by the parameters SFP and oPd, respectively.
13.6 PRESSURE FILTERING AnP PARAMETER
For a good SH regulation, it’s important to use a filtered value of the
pressure. This can be done by the parameter AnP. Suggested values: From 1-5
evaporators for each racks: AnP = 5-6
From 6-30 evaporators for each racks: AnP = 3-4 More than 30 evaporators for
each racks: AnP = 2-3
14. DISPLAY MESSAGES
Display Causes
Notes
KEYBOARD
No display: the keyboard is trying to Press for 3 seconds UP arrow,
1 nod work with another board that is not enter the SEC menu and select
working or not present
LOC entry.
2 Pon Keyboard is unlocked
3 PoF Keyboard is locked
4 rSt Alarm reset
Alarm output deactivated
5
noP, nP nA
Not present (configuration) Not available (evaluation)
The keyboard is not able to 6 noL communicate with the EC3-
XM678D
Verify the connection. Call the Service
ALARM FROM PROBE INPUT
6
P1 P2 P3 P4 P5
Sensor brake down, value out of range or sensor incorrectly configured P1C,
P2C to P6C.
PPF can be showed by slaves of pressure that don’t receive the
P1: the cooling output works with Con and COF, With defrost probe on error the defrost is performed only at interval.
P6 PPF CPF
value of pressure.
CPF is showed when the remote probe 4 is not working.
For P5, P6 and PPF: the percentage of the valve opening is fixed at PEO value.
TEMPERATURE ALARM
7
HA
Temperature alarm from parameter Outputs unchanged. ALU on probe rAL.
8
LA
Temperature alarm from parameter Outputs unchanged. ALL on probe rAL.
9 HA2 Second high temperature alarm
Outputs depends on setting.
10 LA2 Second low temperature alarm
Outputs depends on setting.
DIGITAL INPUT ALARM
Door open alarm from input i1F, i2F Cooling relay and fan follow the
13 dA or i3F = after delay d1d, d2d or
odc parameter. Cooling restart
d3d.
as specified on rrd parameter.
14 EA
Generic alarm from digital input i1F, i2F, i3F = EAL.
Severe alarm of regulation lock
15 CA from digital input i1F, i2F, i3F =
Regulation output OFF.
bAL.
16 PAL
Pressure switch lock i1F, i2F o i3F = PAL.
All the outputs are OFF.
ELECTRONIC VALVE ALARM
17 LOP
Minimum operating pressure threshold from LOP parameter.
The valve output increases its opening of dML quantity every second.
18 MOP
Maximum operating pressure threshold from MOP parameter.
The valve output decreases its opening of dML quantity every second.
19 LSH
Low superheating from LSH parameter and SHd delay.
The valve will be closed; the alarm will be showed after SHd delay.
20 HSH
High superheating from HSH parameter and SHd delay.
Only display.
CLOCK ALARM
Defrost will be performed with
21 rtC Clock settings lost.
IdF till restoring the settings of
RTC.
22 rtF Clock damaged.
Defrost will be performed with IdF.
OTHERS
23 EE 24 Err 25 End
EEPROM serious problem.
Error with upload/download parameters. Parameters have been correctly
transferred.
Output OFF. Repeat the operation.
26 dEF Defrost is progress
27 cLn Cleaning function active
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
5/12
14.1 ALLARM RECOVERY
Probe alarms P1, P2, P3 and P4 start some seconds after the fault in the
related probe; they automatically stop some seconds after the probe restarts
normal operation. Check connections before replacing the probe. Temperature
alarms HA, LA, HA2 and LA2 automatically stop as soon as the temperature
returns to normal values. Alarms EA and CA (with i1F = bAL) recover as soon as
the digital input is disabled. Alarm CA (with i1F = PAL) recovers only by
switching off and on the instrument.
15. ELECTRONIC EXPANSION VALVE MENU
1. Enter the Programming mode by pressing the SET and
DOWN key for few seconds (measurement unit starts
blinking). 2. Press arrows until the instrument shows EEU label;
3. Press SET. You are now in EEV function menu;
16. CONTROLLING LOADS
16.1 TEMPERATURE PROBE REFERENCE FOR REGULATION Up to 5 temperature probes can be used for the temperature regulation.
rPA
rPb
Reg.
rP3
rP4
Temperature reference function
Temp.
rP5
rPd
rPE
It’s possible to set the probes used for temperature regulation. Up to 5 Temperature inputs Pb1, Pb2, Pb3, Pb4, Pb6, can be used. To support above function, the parameters rPA, rPb, rP3, rP4, rP5 are used. Which temperature probe methods of combine is set by par. rPd among the following: Average, Minimum, Maximum, First, or Mix.
rPd = Avr rPd = Min rPd = MAS rPd = FrS rPd = rPE
Average average of all valid probes defined as Regulation Probe by par. (rPA, rPb, rP3, rP4, rP5) Minimum minimum of all valid probes defined as Regulation Probe by par. (rPA, rPb, rP3, rP4, rP5) Maximum maximum of all valid probes defined as Regulation Probe by par. (rPA, rPb, rP3, rP4, rP5) First first valid probe defined as Regulation Probe by par. (rPA, rPb, rP3, rP4, rP5) Mix this is currently done with “rPE” parameter.
16.1.1 Sensor’s failure In case of multiple temperature sensor regulation:
(rPd = Aur, Min, Max or rPE), and with sensor failure, the remaining sensors
are used for the regulation. In case of all sensors failure, the valve opens
at PEO percentage
16.2 DUAL TEMP MODE OPERATION
Controller can have up to 4 pre-set regulation. The preset regulation is set
in the parameter MAP. By digital input or supervising system is possible to
enable the second regulation mode, set in the parameter M2P. In this way a
dual temp case can be easily set and controlled.
16.2.1 Second map function by digital input configuration By setting on
digital input among i1F, i2F, i3F as the “nt” the map set in the parameter M2P
is loaded when the digital input is enabled.
16.3 THE SOLENOID VALVE
The regulation is performed according to the temperature measured by the
thermostat probe that can be physical probe or virtual probe obtained by a
weighted average between two probes (see parameters table description) with a
positive differential from the set point. If the temperature increases and
reaches set point plus differential the solenoid valve is opened and then it
is closed when the temperature reaches the set point value again. In case of
fault in the thermostat probe the opening and closing time of solenoid valve
is configured by “Con” and “CoF” parameters.
16.4 STANDARD REGULATION AND CONTINUOUS REGULATION
The regulation can be performed in two ways: the goal of the first way
(standard regulation) is reaching the best superheat via a classic temperature
regulation obtained using hysteresis. The second way, permits to use the valve
to realise an high performance temperature regulation with a good factor of
superheat precision. This second possibility, it can be used only in
centralized plants and it is available only with electronic expansion valve by
selecting CrE = Y parameter.
First kind of regulation: In this case, the Hy parameter is the differential
for standard ON/OFF regulation. During this phase the valve will maintain the
SH set point
Second kind of regulation Continuous regulation In this case, the Hy
parameter is the proportional band of PI in charge of room temperature
regulation and we advise to use at least Hy = 5.0°C/ 10°F. The int parameter
is the integral time of the same PI regulator. Increasing int parameter the PI
regulator become slow in reaction and of course is true vice versa. To disable
the integral part of regulation you should set int = 0.
16.5 PUMP DOWN BEFORE DEFROST
The following parameters has been added: Pdt pump down type (nu; FAn; F-C)
With Pdt = nu, the pump down is not enabled. With Pdt = Fan, when a defrost
trigger is given: a. Compressor relay will be open. b. EEV valve (if present):
– will be closed with CrE = n, y – will be open with CrE = EUP or EU5 c. Fan
will be forced on for Pdn time With Pdt = F – C, when a defrost trigger is
given: a. EEV valve (if present): – will be closed with CrE = n, y – will be
open with CrE = EUP or EU5 b. Compressor relay and Fan will be forced on for
Pdn time. Pdn pump down duration (0 – 255 min)
16.6 DEFROST
DEFROST STARTING In any case, the device check the temperature read by
configured defrost probe before starting defrost procedure, after that: – (If
RTC is present)Two defrost modes are available through the “tdF”
parameter: defrost with electrical heater and hot gas defrost. The defrost
interval is controlled by parameter “EdF”: (EdF = rtc) defrost is made in real
time depending on the hours set in the parameters Ld1 – Ld6 in workdays and in
Sd1 – Sd6 on holidays; (EdF = in) the defrost is made every “IdF” time; –
defrost cycle starting can be operated locally (manual activation by means of
the keyboard or digital input or end of interval time) or the command can come
from the Master defrost unit of the LAN. In this case the controller will
operate the defrost cycle following the parameters it has programmed but, at
the end of the drip time, will wait that all the other controllers of the LAN
finish their defrost cycle before to re-start the normal regulation of the
temperature according to dEM parameter; – Every time any of the controller of
the LAN begin a defrost cycle it issue the command into the network making all
the other controllers start their own cycle. This allows a perfect
synchronisation of the defrost in the whole multiplexed cabinet according to
LMd parameter; – Selecting dPA and dPb probes and by changing the dtP and ddP
parameters the defrost can be started when the difference between dPA and dPb
probes is lower than dtP for all ddP time. This is useful to start defrost
when a low thermal exchange is detected. If ddP = 0 this function is disabled;
MINIMUM DEFROST TIME The “ndt” (0 – MnF) Minimum Defrost Time, set the minimum
defrost duration, when the defrost is ended by evaporator temperature probe.
The ndt time is taken in account everytime the defrost is trigged,
independently form the value of end defrost temperature probe and end defrost
digital input status.
DEFROST ENDING – When defrost is started via rtc, the maximum duration of
defrost is obtained
from Md parameter and the defrost end temperature is obtained from dtE
parameter (and dtS if two defrost probes are selected). – If dPA and dPb are
present and d2P = y the instrument stops the defrost procedure when dPA is
higher than dtE temperature and dPb is higher than dtS temperature;
At the end of defrost the drip time is controlled through the “Fdt” parameter.
16.6.1 Kind of defrost The kind of defrost is set by parameter tdF among the
following possibilities tdF = Air natural defrost.
Defrost is made by opening the compressor/solenoid relay. The fan during
defrost depends on the parameter Fnc. Defrost relay is off. The valve is
closed tdF = EL defrost with electrical heater: Defrost is made by opening the
compressor/solenoid relay. The fan during defrost depends on the parameter
Fnc. Defrost relay is on. The valve is closed tdF = in hot gas defrost.
Defrost is made by closing the compressor/solenoid relay. The fan during
defrost depends on the parameter Fnc. Defrost relay is on. The valve opening
percentage during the defrost is set by the par. oPd.
16.7 ON DEMAND DEFROST
CONCEPT Controller can perform on demand defrost. It is based on the behavior
of evaporator temperature. Controller monitors the evaporator temperature and
triggers a defrost if some conditions are satisfied. For defrost efficiency
its’ important to place the “end defrost probe”, usually P2, in the coldest
place of the evaporator, usually immediately after the expansion valve.
NOTE: Because of different type of evaporators and consequentially behaviors,
it’s warmed suggested to test and validate this algorithm in a climatic
chamber before applying it in the field.
PARAMETES & SETTINGS The «On Demand Defrost» can be activated with the
following settings: CrE = “n” , EdF =”Aut” cdt: evaporator temperature
differential to trigger a defrost (default
cdt = 4°K) nbd: minimum compressor run before automatic defrost (or minimum
time of activation of solenoid valve) it has to be set properly. It prevents
defrost from starting (default nbd = 4.0h) Mbd: max compressor run before
automatic defrost (or max time of activation of solenoid valve): it has to be
set properly. If reached a defrost is triggered (default Mbd = 16.0h) nct:
minimum evap. temperature, it has to be set properly. a defrost is triggered
when this temperature reached (default nct = -30°C)
NOTE: With CrE = “y” or CrE = “EUP” or CrE = EU5 only «RTC defrost» and
«interval defrost» are allowed. With EdF = “Aut” & CrE = “y” or CrE = “EUP” or
CrE = EU5 the «interval defrost» will be performed, as with EdF = in
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
6/12
EXCEPTIONS: 1. A defrost cannot be triggered if the compressor has not ran
more than
minimum time (nbd parameter) since the last defrost or initial power up.
(Resolution hh.m) 2. If the compressor has ran for more than maximum time
since the last defrost or initial power up (Mbd parameter), a defrost is
triggered regardless of coil temperature. 3. If the coil temperature reaches
very low temperature, (nct parameter), a defrost is triggered regardless of
cdt value.
16.8 FANS
CONTROL WITH RELAY The fan control mode is selected by means of the “FnC”
parameter:
C – n = running with the solenoid valve, OFF during the defrost; C – y =
running with th1e solenoid valve, ON during the defrost; O – n = continuous
mode, OFF during the defrost; O – y = continuous mode, ON during the defrost;
An additional parameter “FSt” provides the setting of temperature, detected by
the evaporator probe, above which the fans are always OFF. This can be used to
make sure circulation of air only if his temperature is lower than set in
“FSt”.
CONTROL WITH ANALOG OUTPUT (if present)
The modulating output (trA=rEG) works in proportional way (excluding the first
AMt seconds where the fans speed is the maximum). The regulation set point is
relative to regulation set point and is indicated by ASr, the proportional
band is always located above SET+ASr value and its value is PbA. The fan are
at minimum speed (AMi) when the temperature read by fan probe is SET+ASr and
the fan is at maximum speed (AMA) when the temperature is SET+ASr+PbA.
16.9 ANTI SWEAT HEATERS
The anti-sweat heater regulation can be performed with on board relay (if OA6
= AC) or with the analog output (if present by setting trA = AC). However the
regulation can be performed in two ways:
· Without real dew-point information: in this case the default value for dew-
point is used (SdP parameter).
· Receiving dew-point from XWEB5000 system: the SdP parameter is overwritten
when valid value for dew-point is received from XWEB. In case of XWEB link is
lost, SdP is the value that will be used for safety.
The best performance can be obtained using probe 4. In this case, the
regulation follows the chart:
Probe 4 should be placed on the showcase glass. For each cabinet can be used only one probe 4 (P4) sending its value to the others section that are connected to the LAN.
HOW TO WORK WITH PROBE 4 THROUGH THE LAN:
Param.
EC3-XM6x8D_1 EC3-XM6x8D_2 + with EC3-XM6x8D_3+
Without probe 4
probe 4
Without probe 4
Adr
n
n + 1
n + 2
LCP
LCP = n
LCP = Y
LCP = n
P4C
LAN or not connect P4C = NTC, PtC or
the probe
PtM
LAN or not connect the probe
trA
trA = AC if the device has the analog output
OA6
OA6 = AC if the device will use the AUX relay for regulation
In case of P4 error or if P4 is absent the output is at AMA value for the AMt time then the output is at 0 value for the time [255 AMt] time performing a simple PWM modulation.
16.10 CLEANING MODE FUNCTION BY DIGITAL INPUT CONFIGURATION
The “cLn” value is added to the functions of the digital input. The function
has the same basic features of the stand by function, but with the following
differences: a. By the parameter LcL (no, yES) it’s possible to set if the
light is on or off during
cleaning mode. This parameter LcL can be override by light button or by Light
on/off Modbus command. b. By the parameter FcL (no, yES) ) it’s possible to
set if the fan is on or off during cleaning mode.
In case of fan on, the FSt parameter (fan stop temperature) is override.
16.10.1 Display During the Cleaning Status, the display shows the “cLn” message.
16.11 AUXILIARY OUTPUT
The auxiliary output is switch ON and OFF by means of the corresponding digital input or by pressing and releasing the down arrow key.
17. PARAMETER LIST
REGULATION
Set rtC EEU Hy
Int CrE LS US OdS
AC CCt
CCS Con
CoF
Temperature set point (LS – US) Access to CLOCK submenu (if present); Access to EEV submenu Differential: (0.1 – 25,5°C; 1 – 45°F): Intervention differential for set point, always positive. Solenoid valve Cut IN is Set Point Plus Differential (Hy). Solenoid valve Cut OUT is when the temperature reaches the set point. Integral time for room temperature regulation: (0 – 255 s) integral time for room temperature PI regulator. 0= no integral action; Continuous regulation activation: (n – Y) n = standard regulation; Y = continuous regulation. Use it only in centralized plants; Minimum set point limit: (-55.0°C – SET; -67°F – SET) Sets the minimum acceptable value for the set point. Maximum set point limit: (SET – ÷150°C; SET – 302°F) Set the maximum acceptable value for set point. Outputs activation delay at start up: (0 – 255 min) This function is enabled at the initial start-up of the instrument and inhibits any output activation for the period of time set in the parameter. (AUX and Light can work) Anti-short cycle delay: (0 – 60 min) interval between the solenoid valve stop and the following restart. Compressor ON time during continuous cycle: (0.0 – 24.0 h; resolution 10min) Allows to set the length of the continuous cycle: compressor stays on without interruption for the CCt time. Can be used, for instance, when the room is filled with new products. Set point for continuous cycle: (-55 – 150°C / -67 – 302°F) it sets the set point used during the continuous cycle. solenoid valve ON time with faulty probe: (0÷255 min) time during which the solenoid valve is active in case of faulty thermostat probe. With Con =0 solenoid valve is always OFF. solenoid valve OFF time with faulty probe: (0 – 255 min) time during which the solenoid valve is off in case of faulty thermostat probe. With COF = 0 solenoid valve is always active.
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit. !!! WARNING
!!! When the measurement unit is changed the parameters with temperature
values have to be checked.
PrU Pressure mode: (rEL or AbS) it defines the mode to use the pressure. !!!
WARNING !!! the setting of PrU is used for all the pressure parameters. If PrU
= rEL all pressure parameters are in relative pressure unit, if PrU = AbS all
pressure parameters are in absolute pressure unit.
PMU Pressure measurement unit: (bAr – PSI – MPA) it selects the pressure
measurement units. MPA = the value of pressure measured by kPA10.
PMd Way of displaying pressure: (tEM – PrE) it permits showing the value
measured by pressure probe with tEM= temperature or by PrE = pressure
rES Resolution (for °C): (in = 1°C; dE = 0.1°C) allows decimal point display
rEP Resolution for % value: (in = integer; dE = with decimal point) allows
decimal point display for percentage values Lod Instrument display: (nP; P1;
P2, P3, P4, P5, P6, tEr, dEF) it selects which
probe is displayed by the instrument. P1, P2, P3, P4, P5, P6, tEr = virtual
probe for thermostat, dEF = virtual probe for defrost. rEd Remote display:
(nP; P1; P2, P3, P4, P5, P6, tEr, dEF) it selects which probe is displayed by
the X-REP. P1, P2, P3, P4, P5, P6, tEr = virtual probe for thermostat, dEF =
virtual probe for defrost. dLy Display delay: (0 – 24.0 m; resolution 10s)
when the temperature increases, the display is updated of 1 °C/1°F after this
time. rPA Regulation probe A: (nP; P1; P2, P3, P4, P6) first probe used to
regulate room temperature. If rPA = nP the regulation is performed with real
value of rPb. rPb Regulation probe B: (nP; P1; P2, P3, P4, P5) second probe
used to regulate room temperature. If rPb = nP the regulation is performed
with real value of rPA rP3 Regulation probe 3: (nP; P1; P2, P3, P4, P6) third
probe used to regulate room temperature, with rPd = Aur or Min or MA or FrS
rP4 Regulation probe 4: (nP; P1; P2, P3, P4, P6) fourth probe used to regulate
room temperature, with rPd = Aur or Min or MA or FrS rP5 Regulation probe 5:
(nP; P1; P2, P3, P4, P6) fifth probe used to regulate room temperature, with
rPd = Aur or Min or MA or FrS rPd Temperature Regulation Strategy: (Aur, Min,
MAS, FrS, rPE)
Aur: average of all valid probes defined as Regulation Probe
Min: minimum value of all valid probes defined as Regulation Probe MaS:
maximum of all valid probes defined as Regulation Probe FrS: first valid probe
defined as Regulation probe rPE: mix between rPA and rPb deifned by rPE
parameter rPE Regulation virtual probe percentage: (0 – 100%) it defines the
percentage of the rPA respect to rPb. The value used to regulate room
temperature is obtained by:
value_for_room = (rPArPE + rPb*(100-rPE))/100
ELECTRONIC EXPANSION VALVE SUBMENU FtY Kind of gas:
CODE
r22 134 290 404 47A 47C 47F
REFR. OPERATING RANGE CODE REFR. OPERATING RANGE
R22 R134A R290 R404A R407A R407C R407F
-50 – 60°C/-58 – 120°F -50 -60°C/-58 – 120°F -50 – 60°C/-58 – 120°F -70 – 60°C/-94 – 120°F -50 – 60°C/-58 – 120°F -50 – 60°C/-58 – 120°F -50 – 60°C/-58 – 120°F
410 448 449 450 507 513 CO2
R410A R448A R449A R450A R507 R513A R744
-50 – 60°C/-58 – 120°F -45 – 60°C/-69 – 120°F -45 – 60°C/-69 – 120°F -45 – 60°C/-69 – 120°F -70 – 60°C/-94 – 120°F -45 – 60°C/-69 – 120°F -50 – 60°C/-58 – 120°F
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
7/12
ATU Self-adaptive SH regulation enabling (No; yES) This parameter enables the
self-adaptive regulation of the superheat. CrE = no must to be set, when this
function is enabled.
AMS Minimum STABLE superheat search (No; yES). This parameter enables the
search of the minimum stable superheat. The lowest admitted value is LSH+2°C
SSH Superheat set point: (0.1 – 25.5°C; 1 – 45°F) used to regulate superheat
SHy Differential for low superheat function: this value is used by X-WEB with
XeCO2 function. When the monitoring system enable the low superheat Shy is
subtracted to the SSH set point (-12.0 – 12.0°C) Pb Proportional band: (0.1 –
60.0 / 1 – 108°F) PI proportional band PbH Dead band for superheat regulation:
it’s a band across the SH set point, inside this band the valve opening
percentage is not updated. rS Band Offset: (-12.0 – 12.0°C; -21 – 21°F) PI
band offset inC Integration time: (0 255 s) PI integration time dFC
Derivative time: (0 255 s) PID derivative time Ped Probe error delay before
stopping regulation: 0 – 239 seconds On (240) PEO Probe Error opening
percentage: (0÷100%) if a probe error occurs, valve opening percentage is PEo;
SFd Start Function duration: (0.0 – 42.0 min: resolution 10 s) It sets start
function duration and post-defrost duration. During this phase the SH alarms
are overridden; SFP Start opening Percentage: (0 – 100 %) Opening valve
percentage when start function is active. This phase duration is SFd time; OHg
Opening Percentage during hot gas defrost: (0 100 %) Opening valve
percentage when hot gas defrost is active. Pdd Post Defrost Function duration:
(0.0 – 42.0 min: resolution 10 s) It sets start function duration and post-
defrost duration. During this phase the alarms are overridden; OPd Opening
Percentage after defrost phase: (0 – 100%) Opening valve percentage when after
defrost function is active. Phase duration is Pdd time; LnF Minimum opening
percentage at normal Functioning: (0 100 %) during regulation it sets the
minimum valve opening percentage; (0 MnF %) MnF Maximum opening percentage
at normal Functioning: (LnF – 100 %) during regulation it sets the maximum
valve opening percentage dCL Regulation off delay, when the set point is
reached (0 255 s) Fot Forced opening percentage: (0 100 % – nu) it permits
to force the valve opening to the specified value. This value overwrites the
value calculated by PID algorithm. !!! WARNING !!! to obtain the correct
superheat regulation you have to set Fot = nu LPL Lower Pressure Limit for
superheat regulation: (PA4 – P20 bar / psi / kPA10) when suction pressure
comes down to LPL the regulation is performed with a LPL fixed value for
pressure, when pressure comes back to LPL the normal pressure value is used.
(related to PrM parameter) MOP Maximum Operating Pressure threshold: (PA4 –
P20 bar / psi / kPA10) if suction pressure exceeds maximum operating pressure
value, instrument signals situation with MOP alarm. (related to PrM parameter)
dMP Delay for Maximum Operating Pressure threshold alarm signalling: (0 ÷
255s) when a MOP alarm occurs it’s signalled after dMP time LOP Minimum
Operating Pressure threshold: (PA4 – P20 bar / psi / kPA*10) if the suction
pressure comes down to this value a low-pressure alarm is signalled with LOP
alarm. (related to PrM parameter) dLP Delay for Minimum Operating Pressure
threshold alarm signalling: (0 255 s) when a LOP alarm occurs it’s signalled
after dMP time dML Opening steps variation during MOP and LOP: (0 – 100%) when
a MOP alarm occurs valve will close of the dML percentage every cycle period
until MOP alarm is active. When LOP occurs valve will open of the dML
percentage every cycle period until LOP alarm is active. AAS Low superheat
alarm with “XeCO2 function active: n = no superheat alarm, Y = Low superheat
alarm is still signalled HSH High Superheat alarm: (LSH – 80.0°C / LSH –
144°F) when superheat exceeds this value an high superheat alarm is signalled
after interval SHd LSH Low Superheat alarm: (0 – HSH °C / 0 – HSH °F) when
superheat goes down to this value a low superheat alarm is signalled after
interval SHd dHS High superheat alarm activation delay: (0 – 42 min:
resolution 10 s) when high superheat alarm occurs, the time dHS must pass
before alarm signalling. dLS Low superheat alarm activation delay: (0 – 42
min: resolution 10 s) when low superheat alarm occurs, the time SHd must pass
before alarm signalling. LSA Opening percentage decrease with low Superheat
alarm: (0 100 %) FrC Fast-recovery Constant: (0 – 100 s) permits to increase
integral time when SH is below the set-point. If FrC = 0 fast recovery
function is disabled. AnP Pressure filter (0 – 100) It uses the last average
values of the pressure to calculate the superheat. E.I. with AnP = 5
controller uses the average pressure in the last 5 seconds to calculate the
SH. NOTE: avoid values higher than 10 Ant Temperature filter (0 – 100) It uses
the last average values of the temperature to calculate the superheat. E.I.
with Ant = 5 controller uses the average temperature in the last 5 seconds to
calculate the SH. NOTE: avoid values higher than 10 SLb Reaction time (0 – 255
s): time to update the valve open percentage. EI. With SLb = 24: the valve
open percentage is updated every 24 seconds. tEP Predefined valve selection:
(0 10) if (tEP = 0) the user has to modify all the parameters of
configuration in order to use the valve. If tEP is different from 0 the device
performs a fast configuration of the following parameters: LSt, uSt, Sr, CPP,
CHd. To select the right number please use the following table:
tEP
Model
LSt
uSt
(steps10) (steps10)
CPP CHd Sr (mA10) (mA10) (step/s)
tEu (bip/ unip)
HSF (Half/ full)
0
Manual settings
Par
Par
Par
Par
Par Par Par
1
Danfoss ETS-25/50
7
262
10
10 300 bP FUL
2
Danfoss ETS-100
10
353
10
10 300 bP FUL
3
Danfoss ETS-250/400
11
381
10
10 300 bP FUL
11
Emerson EX4 – 6
5
75
50
10 500 bP FUL
If tEP is different from 0 previous configuration of LSt, uSt, Sr, CPP and CHd are overwritten.
tEU Type of Stepper motor: [uP-bP] it permits to select the kind of valve. uP
= 5 – 6 wires unipolar valves; bP = 4 wires bipolar valves; !!!WARNING!!! by
changing this parameter the valve must be reinitialized.
bdM bipolar valve piloting: [“UAM”(0 = Wave Mode) – “noM”(1 = Normal Mode)]
Bipolar valve pilot mode: Wave Mode – Normal Mode
HFS Kind of motor movement: (HAF; FUL) HAF = half step. Use this setting for
the unipolar valve. FUL = half step. Use this setting for the bipolar valve.
LSt Minimum number of steps: [0 – USt] it permits to select the minimum number
of steps. At this number of steps the valve should be closed. So it’s
necessary the reading of manufacturer datasheet to set correctly this
parameter. It’s the minimum number of steps to stay in advised range of
functioning. !!! WARNING !!! By changing this parameter the valve has to be
reinitialized. The device performs this procedure automatically and restarts
its normal functioning when the programming mode ends.
USt Maximum number of steps: [LSt – 80010] it permits to select the maximum
number of steps. At this number of steps the valve should be completely
opened. Read the datasheet provided by manufacturer of the valve to set
correctly this parameter. It’s the maximum number of steps to stay in advised
range of functioning.
!!! WARNING !!! By changing this parameter the valve has to be reinitialized.
The device performs this procedure automatically and restarts its normal
functioning when the programming mode ends.
ESt Extra step during closing phase: (0 – 255 (10)) it sets the number of
extra steps the controller performs, when the valve is closed at start up, and
during the pauses of regulation, to force the closure of the valve. NOTE: To
set ESt the following steps has to be done: 1. Set the kind of valve by the
parameter tEP. This pre-set the parameters related to the valve 2. Set the
right value of ESt
Sr Step rate [10 – 600 step/sec] it’s the maximum speed to change step without
losing precision (means without losing steps). It’s advised to stay under the
maximum speed.
CPP Current per phase (only bipolar valves): [0 – 10010 mA] it’s the maximum
current per phase used to drive valve. It’s used only with bipolar valves.
CHd Holding current per phase (only bipolar valves): [0 t- 10010 mA] it’s the
current per phase when the valve is stopped for more than 4 min. It’s used
only with bipolar valves.
GtC Minimum Interval to enable calibration cycles with extra steps ESt: [0
GtH (h)] Indicates the number of hours after which the valve calibration is
enabled (with extra steps ESt) when the regulation closes the valve at 0 %.
GtH Interval between automatic valve calibration cycles: [GtC – 255 (ore)] Dty
Pilot duty: (20 – 100%) with dtY = 100, the valve is moved without
interruption, with dtY = 60 the valve is moved with a pilot duty of 60 %: for
0.6 s on and then for 0.4 s off till the final position is reached.
DEFROST
dPA dPb tdF EdF Srt Hyr tod d2P
dtE dtS IdF idE
ndt MdF dSd dFd dAd Fdt
dPo dAF
defrost Probe A: (nP; P1; P2, P3, P4, P6) first probe used for defrost. If
rPA=nP the regulation is performed with real value of dPb.
defrost Probe B: (nP; P1; P2, P3, P4, P6) second probe used for defrost. If
rPB=nP the regulation is performed with real value of dPA.
value_for_defrost= (dPAdPE + dPb(100-dPE))/100
Defrost type: (Air, EL, in)
Air = Air defrost (defrost relay is not switched on during defrost)
EL = defrost with electrical heater;
in = hot gas defrost;
Defrost mode: (rtc in- Aut) (only if RTC is present) rtc= defrost activation
via RTC; in= defrost activation with idf; AUt = on demand defrost.
Heater set point during defrost: (-55 – 150°C; -67 – 302°F) if tdF = EL during
the defrost the defrost relay perform an ON/OFF regulation with Srt as set point.
Differential for heater: (0.1- 25.5°C, 1 – 45°F) the differential for heater
Time out for heater: (0 – 255 min.) if the defrost probe temperature is bigger
than Srt for all tod time the defrost ends altough the defrost probe temperature
is lower than dtE or dtS. It permits to reduce defrost duration;
Defrost with two probes: (n – Y) n= only the dPA probe is used to defrost
management; Y= defrost is managed with dPA probe and dPb probe. Defrost
can performed only if both probe value are lower than dtE for dPA probe and
dtS for dPb probe;
Defrost termination temperature (Probe A): (-55 – 50°C; -67 – 122°F)
(Enabled only when the evaporator probe is present) sets the temperature
measured by the evaporator probe dPA which causes the end of defrost
Defrost termination temperature (Probe B): (-55 – 50°C; -67 – 122°F)
(Enabled only when the evaporator probe is present) sets the temperature
measured by the evaporator probe dPb which causes the end of defrost
Interval between defrosts: (0 – 120h) Determines the time interval between
the beginning of two defrost cycles
Time to next defrost log into not volatile memory
no: time to next defrost is not logged into no volatile memory, this means
controller will use the idF interval after a power off. E.I. idF = 8: controller
performs a defrost every 8h. If controller is switched off, independently from
when last defrost happened, at power on it will do the first defrost after 8 h.
yES: time to next defrost is logged into no volatile memory, this means
controller will use it after a power off. E.I. idF = 8: controller performs a defrost
every 8h. If controller is switched off 6 hours after last defrost, at power on it
will do the first defrost after 2 hours (6+2 = 8). It is useful in places subjected to
frequent power outages.
Minimum duration of defrost: (0 – MdF min) it sets the minimum defrost
duration, independently form the temperature reached by the end defrost probes;
Maximum duration of defrost: (ndt – 255 min) When dPA and dPb aren’t
present, it sets the defrost duration, otherwise it sets the maximum duration for
defrost;
Start defrost delay: (0 – 255 min) This is useful when different defrost start
times are necessary to avoid overloading the plant.
Display during defrost: rt = real temperature; it = temperature reading at the
defrost start; Set = set point; dEF = “dEF” label;
Defrost display time out: (0 – 255 min) Sets the maximum time between the
end of defrost and the restarting of the real room temperature display.
Drain down time: (0 – 255 min.) time interval between reaching defrost
termination temperature and the restoring of the control’s normal operation.
This time allows the evaporator to eliminate water drops that might have formed
due to defrost.
First defrost after start-up: y = Immediately; n = after the IdF time
Defrost delay after continuous cycle: (0 – 23.5 h) time interval between the
end of the fast-freezing cycle and the following defrost related to it.
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
8/12
PUMP DOWN
Pdt Pump down type (nu, FAn, F-C) nu: pump down disabled Fan: pump down
enabled. Fan is activated for pump down duration, compressor relay/solenoid
valve is switched off with CrE = n/Y o or activated with CrE=EUP or EU5. F –
C: pump down enabled. Fan and compressor relay are activated for pump down
duration. See above for solenoid valve behaviour.
Pdn Pump down duration (0 255 min)
ON DEMAND DEFROST
Ctd nbd Mdb nct
Differential for defrost start (0.1 – 25.5°C, 1 – 45°F) Minimum Compressor run time before defrost (0.0 – 24h 00 min) Maximum Compressor run time before defrost (0.0 24 h 00 min) Minimum coil temperature to trigger a defrost (-55 – 150°C; 67 – 302°F)
FAN
FPA Fan probe A: (nP; P1; P2, P3, P4, P5) first probe used for fan. If FPA =
nP the regulation is performed with real value of FPB
FnC Fan operating mode: C-n = running with the solenoid valve, OFF during the
defrost; C-y = running with the solenoid valve, ON during the defrost; O-n =
continuous mode, OFF during the defrost; O-y = continuous mode, ON during the
defrost
Fnd Fan delay after defrost: (0 – 255 min) The time interval between the
defrost end and evaporator fans start.
FCt Temperature differential avoiding short cycles of fans (0 – 50°C; 0 –
90°F) If the difference of temperature between the evaporator and the room
probes is more than the value of the Fct parameter, the fans are switched on;
FSt Fan stop temperature: (-50 – 110°C; -58 – 230°F) setting of temperature,
detected by evaporator probe, above which the fan is always OFF.
FHy Differential to restart fan: (0.1 – 25.5°C; 1 – 45°F) when stopped, fan
restarts when fan probe reaches FSt – FHy temperature
tFE Fan regulation by temperature during defrost (n, y) Fod Fan activation
time after defrost: (0 – 255 min.) it forces fan activation for
indicated time; Fon Fan ON time: (0 – 15 min) with Fnc = C_n or C_y, (fan
activated in parallel
with compressor). it sets the evaporator fan ON cycling time when the
compressor is off. With Fon = 0 and FoF 0 the fan are always off, with Fon = 0
and FoF = 0 the fan are always off. FoF Fan OFF time: (0 – 15 min) with Fnc =
C_n or C_y, (fan activated in parallel with compressor). it sets the
evaporator fan off cycling time when the compressor is off. With Fon = 0 and
FoF 0 the fan are always off, with Fon = 0 and FoF = 0 the fan are always off.
MODULATING OUTPUT (AnOUT) if present
trA Kind of regulation with PWM output: (UAL rEG AC) it selects the
functioning for the PWM output. UAL= the output is at FSA value; rEG = the
output is regulated with fan algorithm described in fan section; AC = anti-
sweat heaters control (require the XWEB5000 system);
SOA Fixed value for analog output: (0 100 %) value for the output if
trA=UAL; SdP Default value for Dew point: (-55 – 50°C; -67 – 122°F) default
value of dew
point used when there is no supervising system (XWEB5000). Used only when trA
= AC ASr Dew-point offset (trA = AC) / Differential for modulating fan
regulation (trA = rEG): (-25.5 – 25.5°C) (-45 – 45°F); PbA Differential for
anti-sweat heaters: (0.1 – 25.5°C) (1 – 45°F) AMi Minimum value for analog
output: (0 – AMA) AMA Maximum value for analog output: (Ami – 100) AMt Anti-
sweat heaters cycle period (trA = AC)/ Time with fan at maximum speed
(trA=rEG): (0 – 255 s) when the fan starts, during this time the fan is at
maximum speed
ALARMS
rAL ALC ALU
ALL
AHy ALd rA2 A2U A2L A2H Ad2
dAO
EdA
dot Sti Std tbA
Probe for temperature alarm: (nP – P1 – P2 – P3 – P4 – P5 tEr) it selects the probe used to signal alarm temperature Temperature alarm configuration: rE = High and Low alarms related to Set Point; Ab = High and low alarms related to the absolute temperature. High temperature alarm setting: (ALC = rE, 0 – 50°C or 90°F / ALC = Ab, ALL – 150°C or 302°F) when this temperature is reached and after the ALd delay time the HA alarm is enabled. Low temperature alarm setting: (ALC = rE , 0 – 50 °C or 90°F / ALC = Ab , – 55°C or – 67°F – ALU) when this temperature is reached and after the ALd delay time, the LA alarm is enabled. Differential for temperature alarm: (0.1 – 25.5°C; 1 – 45°F) Intervention differential for recovery of temperature alarm Temperature alarm delay: (0 – 255 min) time interval between the detection of an alarm condition and the corresponding alarm signalling. Probe for second temperature alarm: (nP – P1 – P2 – P3 – P4 – P5 tEr) it selects the probe used to signal alarm temperature Second high temperature alarm setting: (A2L – 150°C or 302°F) when this temperature is reached and after the A2d delay time; HA2 alarm is signalled. Second Low temperature alarm setting: (- 55°C or – 67°F – A2U) when this temperature is reached and after the A2d delay time, LA2 alarm is signalled. Differential for second temperature alarm: (0.1 – 25.5°C / 1 – 45°F) Intervention differential for recovery of second temperature alarm Second temperature alarm delay: (0 – 255 min) time interval between the detection of second temperature alarm condition and the corresponding alarm signalling. Delay of temperature alarm at start-up: (0 min 23 h 50 min) time interval between the detection of the temp. alarm condition after the instrument power on and the alarm signalling. Alarm delay at the end of defrost: (0 – 255 min) Time interval between the detection of the temp. alarm condition at the end of defrost and the alarm signalling. Temperature alarm exclusion after door open: (0 – 255 min.) Stop regulation interval: (0 – 24 h: tens of minutes) after regulating continuously Sti time, the valve closes for Std time in order to prevent ice creation. Stop duration: (0 – 60 min.) it defines stop regulation time after Sti. Disabling alarm relay by pressing a key: (n; Y)
OPTIONAL OUTPUT (AnOUT) if present
oA5 relay at term. 1-2-3 configuration: (nP CPr -CP2- -dEF-Fan-ALr-LiG- AUSHtr-OnF – AC): nP = not used; CPr = relay works as a compressor or solenoid valve relay; CP2 = relay works as second dEF = relay works as defrost relay; Fan = relay works as a Fan relay; ALr = activation with alarm conditions; LiG
oA6
CoM AOP iAU
= light activation; AUS = auxiliary relay, it can be switched ON/OFF also by
key; Htr = dead band regulation (not compatible with CrE = y); OnF = ON/OFF
functioning, AC = anti sweat heaters relay at term. 17-18 configuration: nP
CPr -CP2- -dEF-Fan-ALr-LiG-AUSHtr-OnF – AC): nP = not used; CPr = relay works
as a compressor or solenoid valve relay; CP2 = relay works as second dEF =
relay works as defrost relay; Fan = relay works as a Fan relay; ALr =
activation with alarm conditions; LiG = light activation; AUS= auxiliary
relay, it can be switched ON/OFF also by key; Htr = dead band regulation (not
compatible with CrE = y); OnF = ON/OFF functioning, AC = anti sweat heaters
Type of functioning modulating output: · For models with PWM / O.C. output
PM5= PWM 50 Hz; PM6 = PWM
60 Hz; OA7 = not set it; · For models with 4 – 20 mA / 0 – -10 V output Cur= 4
20 mA current
output; tEn = 0 10 V voltage output; Alarm relay polarity: cL = normally
closed; oP = normally opened; Auxiliary output is unrelated to ON/OFF device
status: n = if the instrument is switched off also the auxiliary output is
switched off; Y = the auxiliary output state is unrelated to the ON/OFF device
status
DIGITAL INPUTS
i1P Digital input 1 polarity: (cL oP) CL: the digital input is activated by
closing the contact; OP: the digital input is activated by opening the
contact.
i1F Digital input 1 function: (nu – EAL bAL PAL dor dEF AUS LiG
OnF Htr FHU ES Hdy) nu = not used; EAL = external alarm; bAL = serious
external alarm; PAL = pressure switch activation; dor = door open; dEF =
defrost activation; AUS = auxiliary activation; LiG = light activation; OnF =
switch on/off the instrument; FHU = not used; ES = activate energy saving; nt
= second map enabling; cLn = clean function dEn = defrost off, CP1 =
compressor 1 safety, CP2 = compressor 2 safety;
d1d Time interval/delay for digital input alarm: (0 – 255 min.) Time interval
to calculate the number of the pressure switch activation when i1F = PAL. If
I1F = EAL or bAL (external alarms), “d1d” parameter defines the time delay
between the detection and the successive signalling of the alarm. If i1F = dor
this is the delay to activate door open alarm
i2P Digital input 2 polarity: (cL oP) CL : the digital input is activated by
closing the contact; OP: the digital input is activated by opening the
contact.
i2F Digital input 2 function: (nu – EAL bAL PAL dor dEF AUS LiG
OnF Htr FHU ES Hdy) nu = not used; EAL = external alarm; bAL = serious
external alarm; PAL = pressure switch activation; dor = door open; dEF =
defrost activation; AUS = auxiliary activation; LiG = light activation; OnF =
switch on/off the instrument; FHU = not used; ES = activate energy saving; nt
= second map enabling; cLn = clean function dEn = defrost off, CP1 =
compressor 1 safety, CP2 = compressor 2 safety;
d2d Time interval/delay for digital input alarm: (0÷255 min.) Time interval to
calculate the number of the pressure switch activation when i2F = PAL. If I2F
= EAL or bAL (external alarms), “d2d” parameter defines the time delay between
the detection and the successive signalling of the alarm. If i2F = dor this is
the delay to activate door open alarm
i3P Digital input 3 polarity: (cL oP) CL : the digital input is activated by
closing the contact; OP: the digital input is activated by opening the
contact.
i3F Digital input 3 function: (nu – EAL bAL PAL dor dEF AUS LiG
OnF Htr FHU ES Hdy) nu = not used; EAL = external alarm; bAL = serious
external alarm; PAL = pressure switch activation; dor = door open; dEF =
defrost activation; AUS = auxiliary activation; LiG = light activation; OnF =
switch on/off the instrument; FHU = not used; ES = activate energy saving; nt
= second map enabling; cLn = clean function dEn = defrost off, CP1 =
compressor 1 safety, CP2 = compressor 2 safety;
d3d Time interval/delay for digital input alarm: (0 – 255 min.) Time interval
to calculate the number of the pressure switch activation when i3F = PAL. If
i3F = EAL or bAL (external alarms), “d3d” parameter defines the time delay
between the detection and the successive signalling of the alarm. If i3F = dor
this is the delay to activate door open alarm
nPS Pressure switch number: (0 – 15) Number of activations of the pressure
switch, during the “d#d” interval, before signalling the alarm event (I2F =
PAL). If the nPS activation in the did time is reached, switch off and on the
instrument to restart normal regulation.
odc Compressor and fan status when open door: no = normal; Fan = Fan OFF; CPr
= Compressor OFF; F_C = Compressor and fan OFF.
rrd Outputs restart after doA alarm: no = outputs not affected by the doA
alarm; yES = outputs restart with the doA alarm;
RTC SUBMENU (if present)
CbP Clock Presence (n – y): it permits to disable or enable the clock; Hur
Current hour (0 – 23 h) Min Current minute (0 59 min) dAY Current day (Sun –
SAt) Hd1 First weekly holiday (Sun – nu) Set the first day of the week which
follows the
holiday times. Hd2 Second weekly holiday (Sun – nu) Set the second day of the
week which
follows the holiday times. Hd3 Third weekly holiday (Sun – nu) Set the third
day of the week which follows
the holiday times. ILE Energy Saving cycle start during workdays: (0 23 h 50
min.) During the
Energy Saving cycle the set point is increased by the value in HES so that the
operation set point is SET + HES. dLE Energy Saving cycle length during
workdays: (0 24 h 00 min.) Sets the duration of the Energy Saving cycle on
workdays. ISE Energy Saving cycle start on holidays. (0 – 23 h 50 min.) dSE
Energy Saving cycle length on holidays (0 – 24 h 00 min.) HES Temperature
increase during the Energy Saving cycle (-30 – 30°C; -54 – 54°F) sets the
increasing value of the set point during the Energy Saving cycle. Ld1-Ld6:
Workday defrost start (0 – 23 h 50 min.) These parameters set the
beginning of the 6 programmable defrost cycles during workdays. Ex. When Ld2 =
12.4 the second defrost starts at 12.40 during workdays. Sd1-Sd6: Holiday
defrost start (0 – 23 h 50 min.) These parameters set the beginning of the 6
programmable defrost cycles on holidays. Ex. When Sd2 = 3.4 the second defrost
starts at 3.40 on holidays.
ENERGY SAVING
HES Temperature increase during the Energy Saving cycle: (-30 – 30°C; -54 –
54°F) sets the increasing value of the set point during the Energy Saving
cycle.
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
9/12
PEL Energy saving activation when light is switched off: (n – Y) n = function disabled; Y = energy saving is activated when the light is switched off and vice versa;
LAN MANAGEMENT
LMd dEM LSP LdS LOF LLi LAU LES
LSd
LPP LCP StM ACE
Desfrost synchronisation: y = the section sends a command to start defrost to oher controllers, n = the section doesn’t send a global defrost command Type of end defrost: n = the of the LAN defrost are indipendent; y = the end of the defrost are synchronisated; L.A.N. set-point synchronisation: y = the section set-point, when modified, is updated to the same value on all the other sections; n = the set-point value is modified only in the local section L.A.N. display synchronisation: y = the value displayed by the section is sent to all the other sections; n = set-point value is modified only in the local section L.A.N. On/Off synchronisation this parameter states if the On/Off command of the section will act on all the other ones too: y = the On/Off command is sent to all the other sections; n= the On/Off command acts only in the local section L.A.N. light synchronisation this parameter states if the light command of the section will act on all the other ones too: y = the light command is sent to all the other sections; n = the light command acts only in the local section L.A.N. AUX output synchronisation this parameter states if the AUX command of the section will act on all the other ones too: y = the light command is sent to all the other sections; n = light command acts only in the local section L.A.N. energy saving synchronisation this parameter states if the energy saving command of the section will act on all the other ones too: y = the Energy Saving command is sent to all the other sections; n = the Energy Saving command acts only in the local section Remote probe display: this parameter states if the section has to display the local probe value or the value coming from another section: y = the displayed value is the one coming from another section (which has parameter LdS = y); n = the displayed value is the local probe one. Remote pressure probe: n = the value of pressure probe is read from local probe; Y= the value of pressure probe is sent via LAN; P4 probe sent via LAN (n, y) Solenoid activation via LAN: n = not used; Y = a generic cooling requests from LAN activate the solenoid valve connected to compressor relay; Cold Calling in LAN always enabled even if the compressor block: (n, y)
PROBE CONFIGURATION
P1C Probe 1 configuration: (nP Ptc ntc PtM) nP= not present; PtC = Ptc
ntc = NTC; PtM = Pt1000;
OF1 Probe 1 calibration: (-12.0 – 12.0°C/ -21 – 21°F) allows to adjust
possible offset of the thermostat probe.
P2C Probe 2 configuration: (nP Ptc ntc PtM) nP= not present; PtC= Ptc;
ntc = NTC; PtM = Pt1000;
OE2 Probe 2 calibration: (-12.0 – 12.0°C/ -21 – 21°F) allows to adjust
possible offsets of the evaporator probe.
P3C Probe 3 configuration: (nP Ptc ntc PtM) nP= not present; PtC = Ptc;
ntc = NTC; PtM = Pt1000;
OF3 Probe 3 calibration: (-12.0 – 12.0°C/ -21 – 21°F) allows to adjust
possible offset of the probe 3.
P4C Probe 4 configuration: (nP Ptc ntc PtM) nP = not present; PtC = Ptc
ntc = NTC; PtM = Pt1000;
OF4 Probe 4 calibration: (-12.0 – 12.0°C/ -21 – 21°F) allows to adjust
possible offset of the probe 4.
P5C Probe 5 configuration: (nP Ptc ntc PtM 420 5Vr) nP = not
present; PtM= Pt1000; 420= 4 20 mA; 5 Vr = 0 – 5V ratiometric
OF5 Probe 5 calibration: (-12.0 – 12.0°C/ -21 – 21°F) allows to adjust
possible offset of the probe 5.
P6C Probe 6 configuration: (nP Ptc ntc PtM) nP= not present; PtC = Ptc
ntc = NTC; PtM = Pt1000;
OF6 Probe 6 calibration: (-12.0 – 12.0°C/ -21 – 21°F) allows to adjust
possible offset of the probe 6.
PA4 Probe value at 4 mA or at 0 V: (-1.0 – P20 bar / -14 – PSI / -10 – P20
kPA10) pressure value measured by probe at 4 mA or at 0 V (related to PrM
parameter) Referred to Pb5
P20 Probe value 20 mA or at 5 V: (PA4 – 50.0 bar / 725 psi / 500 kPA10)
pressure value measured by probe at 20 mA or at 5 V (related to PrM parameter)
Referred to Pb5
SERVICE OTHERS
LCL Light on during cleaning mode (n, y)
FCL Fan on during cleaning mode (n, y)
MAP Map used during standard operation (1°M, 2°M, 3°M, 4°M) It sets the map
used by the controller among the four possible maps
MP1 Alternate Map enabled by digital input or Modbus command (1°M, 2°M,
3°M, 4°M) It sets the alternate map enabled by digital input or Modbus
command among the four possible maps
CLt Coling time percentage: it shows the effective cooling time calculated by
EC3-XM678D during regulation
tMd Time to next defrost: time before the next defrost if interval defrost is selected;
LSn L.A.N. section number (1 – 8) number of sections available in the L.A.N.
Lan L.A.N. serial address (1 – LSn) Identifies the instrument address inside local
network of multiplexed cabinet controller.
Adr RS485 serial address (1 – 247) Identifies the instrument address when
connected to a ModBUS compatible monitoring system.
br It sets the baud rate among: (96 = 9.6 bit/s; 192 = 19.2 bit/s)
EMU Previous versions emulation (2V8 , 3V8 , 4V2). It allows the controller to be
used in a LAN of controllers with previous versions:
2V8 = it emulates version 2.8
3V8 = it emulates version 3.8
4V2 = it emulates version 4.2
rEL Release software: (read only) Software version of the microprocessor.
SrL Software subrelease: (read only) for internal use
Ptb Parameter table: (read only) it shows the original code of the parameter map.
Pr2 Access to the protected parameter list (read only).
18. DIGITAL INPUTS
The EC3-XM678D series can support up to 3 free of voltage contact configurable
digital inputs (depending on the models). They are configurable via i#F
parameter
18.1 GENERIC ALARM (EAL)
As soon as the digital input 1, 2, or 3 is activated the unit will wait for
“d1d” or “d2d” or “d3d”time delay before signalling the “EAL” alarm message.
The outputs status don’t change. The alarm stops just after the digital input
is de-activated.
18.2 SERIOUS ALARM MODE (BAL)
When the digital input is activated, the unit will wait for “d1d” or “d2d” or
“d3d” delay before signalling the “BAL” alarm message. The relay outputs are
switched OFF. The alarm will stop as soon as the digital input is de-
activated.
18.3 PRESSURE SWITCH (PAL)
If during the interval time set by “d1d” or “d2d” or “d3d” parameter, the
pressure switch has reached the number of activation of the “nPS” parameter,
the “CA” pressure alarm message will be displayed. The compressor and the
regulation are stopped. When the digital input is ON the compressor is always
OFF. If the nPS activation in the d#d time is reached, switch off and on the
instrument to restart normal regulation.
18.4 DOOR SWITCH INPUT (dor)
It signals the door status and the corresponding relay output status through
the “odc” parameter: no = normal (any change); Fan = Fan OFF; CPr =
CompressorOFF; F_C = Compressor and fan OFF. Since the door is opened, after
the delay time set through parameter “d#d”, the door alarm is enabled, the
display shows the message “dA” and the regulation restarts after rrd time. The
alarm stops as soon as the external digital input is disabled again. With the
door open, the high and low temperature alarms are disabled.
18.5 START DEFROST (DEF)
It executes a defrost if there are the right conditions. After the defrost is
finished, the normal regulation will restart only if the digital input is
disabled otherwise the instrument will wait until the “Mdf” safety time is
expired.
18.6 RELAY AUX ACTUATION (AUS)
This function allows to turn ON and OFF the auxiliary relay by using the
digital input as external switch.
18.7 RELAY LIGHT ACTUATION (LIG)
This function allows to turn ON and OFF the light relay by using the digital
input as external switch.
18.8 REMOTE ON/OFF (ONF)
This function allows to switch ON and OFF the instrument.
18.9 FHU NOT USED
This function allows to change the kind of regulation from cooling to heating
and viceversa.
18.10 ENERGY SAVING INPUT (ES)
The Energy Saving function allows to change the set point value as the result
of the SET+ HES (parameter) sum. This function is enabled until the digital
input is activated.
18.11 MAP SWITCHING (NT)
In this configuration, the digital input activates the map selected by the MP1
parameter. The “MAP CHANGE” ModBus command has higher priority compared to the
digital input.
18.12 CLEANING FUNCTION ACTIVATION (CLN)
In this configuration, the digital input activates the CLEANING function. It
can be activated only if the device is ON. This function has the following
characteristics: · the display visualizes the “CLn” label · The light status
depends on the LCL parameter (no/yes), however the light can
be modified both via button and ModBus command. · The fans status depends on
the FCL parameter (no/yes), furthermore they are
not thermo-regulated (par.FST). The “CLEANING MODE” ModBus command has higher
priority compared to the digital input.
18.13 DEFROST END (DEN)
The digital input ends the defrost cycle in progress. The drip time will
follow the defrost end. A further defrost request with the digital input
active won’t be managed.
18.14 DIGITAL INPUTS POLARITY
The digital inputs polarity depends on “I#P” parameters: CL: the digital input
is activated by closing the contact; OP: the digital input is activated by
opening the contact.
19. USE OF THE PROGRAMMING “HOT KEY”
The XM units can UPLOAD or DOWNLOAD the parameter list from its own E2
internal memory to the “Hot Key” and vice-versa through a TTL connector.
19.1 DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)
1. Turn OFF the instrument by means of the ON/OFF key ,insert the “Hot Key”
and then turn the unit ON.
2. Automatically the parameter list of the “Hot Key” is downloaded into the
controller memory, the “doL” message is blinking. After 10 seconds the
instrument will restart working with the new parameters. At the end of the
data transfer phase the instrument displays the following messages: “end” for
right programming. The instrument starts regularly with the new programming.
“err” for failed programming. In this case turn the unit off and then on if
you want to restart the download again or remove the “Hot key” to abort the
operation.
19.2 UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
1. When the XM unit is ON, insert the “Hot key” and push “UP” key. 2. The
UPLOAD begins; the “uPL” message is blinking. 3. Remove the “Hot Key”.
At the end of the data transfer phase the instrument displays the following
messages: “end ” for right programming. “err” for failed programming. In this
case push “SET” key if you want to restart the programming again or remove the
not programmed “Hot key”.
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
10/12
20. TECHNICAL DATA
CH660 keyboard
Housing:
self-extinguishing ABS.
Case:
CH660 facia 38×80 mm; depth 18mm
Mounting:
panel mounting in a 29×71 mm panel cut-out
Protection:
IP20; Frontal protection: IP65
Power supply:
from EC3-XM678D power module
Display:
3 digits, red LED, 14,2 mm high;
Optional output:
buzzer
Power modules
Case:
8 DIN
Connections:
Screw terminal block 1,6 mm2
heat-resistant wiring and 5.0 mm Faston
Power supply:
24 VAC ± 10%
Power absorption:
20 VA max.
Inputs:
up to 6 NTC/PTC/Pt1000 probes
Digital inputs:
3 free of voltage
Relay outputs:
Total current on loads MAX. 16A
Solenoid Valve:
relay SPST 5(3) A, 250 VAC
defrost:
relay SPST 16 A, 250Vac
fan:
relay SPST 8 A, 250Vac
light:
relay SPST 16 A, 250Vac
alarm:
SPDT relay 8 A, 250Vac
Aux:
SPST relay 8 A, 250Vac
Valve output:
A.C. output up to 30W
Optional output (AnOUT) DEPENDING ON THE MODELS:
· PWM / Open Collector outputs: PWM or 12 VDC max 40 mA
· Analog output: 4 – 20 mA or 0 10 V
Serial output:
RS485 with ModBUS – RTU and LAN
Data storing:
on the non-volatile memory (EEPROM).
Kind of action:
1 B
Pollution degree:
2
Software class:
A
Operating temperature: 0 – 60 °C.
Storage temperature: -25- 60 °C.
Relative humidity:
20 – 85% (no condensing).
Measuring and regulation range:
NTC probe: -40 – 110°C (-58 – 230°F).
PTC probe: -50 – 150°C (-67 – 302°F)
Pt1000 probe: -100 – 100°C (-148 – 212°F)
Resolution:
0.1 °C or 1 °C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0.5 °C ±1 digit
21. DEFAULT SETTING VALUES
CODE M1
rtc EEU SEt 2.0
M2 M3
– – – – 2.0 -18.0
SEC Hy 2.0
int 150 CrE LS -30 US 10 odS AC CCt CCS
Con
CoF
CF PrU PMU
PMd
rES Lod rEd dLy rPA rPb rP3 rP4 rP5 rPd
rPE Fty Atu n AMS n SSH 6.0
SHy 0.0
Pb 8
PbH 0.2
rS 0 inC 220
LOC 2.0 2.0
150 150
n -30 -30 10 10
1 0 0.0 2.0
5
10
°C
rE bAr
PrE
dE
P1 P1 0 P1 nP nP nP nP rPA
100
448
n
n
n
n
6.0 6.0
0
0
8
8
0.2 0.2
0.0 0.0 220 220
M4 -18.0 2.0 150 -30
10
n n 6.0 0 8 0.2 0.0 220
MENUE PARAMETER DESCRIPTION
Pr1 Access to RTC submenu
Pr1 Access to EEV submenu
– – – Set point
– – –
LAN mode selection: Local or Global
Pr1 Differential
Pr2
Integral time for room temperature regulation
Pr2 Continuous regulation activation
Pr2 Minimum set point
Pr2 Maximum set point
Pr2 Outputs activation delay at start up
Pr2 Anti-short cycle delay
Pr2 Continuous cycle duration
Pr2 Continuous cycle set point
Pr2
Compressor ON time with faulty probe
Pr2
Compressor OFF time with faulty probe
Pr2
Measurement unit: Celsius, Fahrenheit
Pr2 Pressure Mode
Pr2 Pressure measurement unit
Pr2
Pressure displaying mode: temperature or pressure
Pr2
Resolution (only C): decimal, integer
Pr2 Local display: default display
Pr1 Remote display: default display
Pr2 Display delay
Pr2 Regulation probe A
Pr2 Regulation probe B
Pr2 Regulation probe 3
Pr2 Regulation probe 4
Pr2 Regulation probe 5
Pr2 Temperature Regulation Strategy
Pr2
Virtual probe percentage (rPd = rAb)
Pr2 Refrigerant gas type
Pr2 Regulator auto tuning
Pr2 Min stable Superheat search
Pr2 Superheat set point
Pr2
Differential for low superheat function
Pr2 Regulation proportional band
Pr2
Death band for superheat regulation
Pr2 Band Offset
Pr2 PID integration time
CODE M1 dFC 1 PEd PEO SFd SFP
M2 M3
1
1
On
50 0.3
40.0
OHG 45.0 45.0 45.0
Pdd
0.4
OPd
50.0
LnF 10.0 10.0 10.0
MnF 100 100 100
dCL
0
Fot
nu
LPL
-0.5
MOP 4.5 4.5 4.5
dMP
10
LOP -0.5 -0.5 -0.5
dLP
10
dML 2.0 2.0 2.0
AAS
n
HSH
60
LSH
2
dHS
0.3
dLS
0.3
LSA
1.0
FrC
50
AnP 3 3
3
Ant 1 1
1
SLb 1 tEP tEU bdM HFS
1
1
nU bP
noM
FUL
LSt
0
USt
0
Est
0
Sr
10
CPP
CHd
GtC
GtH dtY dPA dPb
tdF EL
EdF Srt Hyr tod d2P n
dtE 8.0
dtS 8.0
idF 6 idE ndt 3 MdF 30 dSd dFd
dAd
Fdt 0
0
0
0
10 100 P2 nP
EL EL
in
150
2.0
255
n
n
8.0 8.0
8.0 8.0
6
6
y
3
3
30 30
0
it
30
0
2
M4 MENUE PARAMETER DESCRIPTION
1
Pr2 PID derivation constant time
Pr2
Delay before stopping regulation with probe error
Pr2 Probe Error opening percentage
Pr2 Duration of Soft Start phase
Pr2
Open percentage for soft start phase
45.0
Pr2
Open percentage for inversion defrost
Pr2 Duration for post defrost phase
Pr2
Open percentage for post defrost phase
10.0
Pr2
Minimum open percentage for stepper valve
100
Pr2
Maximum open percentage for stepper valve
Pr2
Regulation off delay, when the set point is reached 2
Pr2
Enable for forcing open valve to a fixed value
Pr2
Minimum value threshold of pressure for regulation
4.5
Pr2
Maximum value threshold of suction pressure
Pr2
Delay for high pressure alarm activation (MOP)
-0.5
Pr2
Minimum value threshold of suction pressure
Pr2
Delay for low pressure alarm activation (LOP)
2.0
Pr2
Opening steps variation during MOP and LOP
Pr2
Low superheat alarm with “XeCO2 function active
Pr2
Threshold for maximum superheat alarm
Pr2
Threshold for minimum superheat alarm
Pr2 Delay for high superheat alarm
Pr2 Delay for low superheat alarm
Pr2
Subtracting percentage with low superheat alarm
Pr2
Additional integration constant for fast recovery
3
Pr2
Number of average values for converted temperature (pressure)
1
Pr2
Number of average values for temperature
1
Pr2
Reaction time (interval for valve PID management)
Pr2 Predefined valve selection
Pr2 Kind of valve.
Pr2
Bipolar valve pilot mode: Wave Mode – Normal Mode
Pr2 Kind of motor movement
Minimum number of steps where
Pr2 the valve can be considered as completely closed.
Pr2
Maximum number of steps that can be performed.
Pr2 Extra steps in closing phase
Step rate: is the speed to change Pr2 step. A too high value causes a
wrong driving.
Pr2
Current per phase during bipolar valve driving.
Pr2
Current per phase to maintain the actual position (Holding current).
Pr2
Interval between cycles to reset the valve
Pr2 Autozero function
Pr2 Pilot duty
Pr2 Defrost probe A
Pr2 Defrost probe B
EL
Kind of defrost: air, resistors, Pr2 inversion
Pr2 Defrost mode: Clock or interval
Pr2 Differential for heater
Pr2 Time out for heater (if temp > Srt)
Pr2 Defrost with two probes
n
Pr2 Defrost with two probes
8.0
Pr2
First defrost termination temperature
8.0
Pr2
Second defrost termination temperature
6
Pr2 Interval between defrosts
Pr2 Storage in eeprom defrost interval
3
Pr2 Minimum Defrost Time
30
Pr2 Maximum defrost duration
Pr2 Delay for defrost on call
Pr2 Visualization during defrost
Pr2
Visualization delay for temperature after defrost
2
Pr2 Dripping time
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
11/12
CODE M1 M2 M3
dPo dAF Pdt Pdn Ctd 6
n
0.0
F-C
0
6
6
nbd 4.0 4
4
Mdb 16.0 16.0 16.0
nct -30 -30 -30
FAP FnC O-y Fnd 0
P2
o-y o-n
0
0
FCt
10
FSt 15.0 15.0 2.0
FHy
1.0
tFE
n
Fod
0
Fon
0
FoF
0
trA
UAL
SOA
0
SdP
30.0
ASr
1.0
PbA
5.0
AMi
0
AMA
100
AMt
3
rAL
tEr
ALC
Ab
ALU 10 10 10
ALL -30 -30 -30
AHy
1.0
ALd 15 15 15
rA2
nP
A2U 150 150 150
A2L -40 -40 -40
A2H
2
A2d 15 15 15
dAO 1.0 1.0 1.0
EdA
60
dot
30
Sti nu nu
nu
Std 10 tbA oA5 oA6 CoM AOP
3
3
n ALr AUS Cur CL
iAU
n
i1P
cL
i1F
dor
d1d
15
i2P
cL
i2F
LiG
d2d
5
i3P
cL
i3F
ES
d3d
0
nPS
15
OdC
F-C
rrd
30
CbP
y
Hur
– – –
Min
– – –
dAY
– – –
Hd1
nu
Hd2
nu
Hd3
nu
ILE
0.0
dLE
0.0
M4 MENUE PARAMETER DESCRIPTION
Pr2 Defrost at power ON
Pr2 Delay defrost after freezing
Pr2 Pump down type
Pr2 Pump down duration
6
Pr2 Differential for defrost start
Minimum Compressor run time
4
Pr2 before defrost
16.0
Maximum Compressor run time Pr2 before defrost
-30
Minimum coil temperature to trigger Pr2 a defrost
Pr2 Fan probe A
o-n Pr2 Fan operating mode
0
Pr2 Fan delay after defrost
Pr2
Temperature differential to avoid short cycles of fans
2.0
Pr2 Fan stop temperature
Pr2 Fan stop hysteresis
Pr2
Fan regulation by temperature in defrost
Pr2
Fan activation time after defrost (without compressor)
Pr2 Fan ON time
Pr2 Fan OFF time
Pr2 Kind of regulation with PWM output
Pr2 Fixed speed for fan
Pr2 Default Dew Point value
Pr2
Differential for fan / offset for antisweat heater
Pr2
Proportional band for modulating output
Pr2
Minimum output for modulating output
Pr2
Maximum output for modulating output
Pr2
1:Time with fan at maximum speed – 2:Tempo uscita on Cavi Caldi
Pr2 Probe for temperature alarm
Pr2
Temperature alarm configuration: relative / absolute
10
Pr2 High temperature alarm setting
-30 Pr2 Low temperature alarm setting
Pr2 Differential for temperature alarm
15
Pr2 Temperature alarm delay
Pr2 Probe for temperature alarm 2
150 Pr2 High temperature alarm 2 setting
-40 Pr2 Low temperature alarm 2 setting
Pr2 Differential for temperature alarm 2
15
Pr2 Temperature alarm delay 2
1.0
Pr2
Delay of temperature alarm at startup
Pr2 Alarm delay at the end of defrost
Pr2
Temperature alarm exclusion after door open
nu
Pr2
Time for compressor ON before regulation break
3
Pr2
Time for compressor OFF for regulation break
Pr2 Silencing alarm relay with buzzer
Pr2 Relay 5 configuration
Pr2 Relay 6 configuration
Pr2 Modulating output configuration
Pr2 Alarm relay polarity
Pr2
Auxiliary output independent from ON/OFF state
Pr2 Digital input 1 polarity
Pr2 Digital input 1 configuration
Pr2 Digital input 1 activation delay
Pr2 Digital input 2 polarity
Pr2 Digital input 2 configuration
Pr2 Digital input 2 activation delay
Pr2 Digital input 3 polarity
Pr2 Digital input 3 configuration
Pr2 Digital input 3 activation delay
Pr2 Pressure switch number
Pr2
Compressor and fan status when open door
Pr2
Outputs restart after door open alarm
Pr2 Clock presence
Pr1 Current hour
Pr1 Current minutes
Pr1 Current day
Pr1 First weekly day
Pr1 Second weekly day
Pr1 Third weekly day
Pr1
Energy saving cycle start during workdays
Pr1
Energy saving cycle length during workdays
CODE M1
ISE
dSE
HES
Ld1
Ld2
Ld3
Ld4
Ld5
Ld6
Sd1 Sd2 Sd3 Sd4 Sd5 Sd6
HES
PEL
LMd dEM LSP
LdS
LOF LLi LAU LES LSd LPP LCP
StM
ACE
P1C OF1 P2C OF2 P3C OF3 P4C OF4 P5C OF5 P6C OF6 PA4 P20 LCL FCL MAP
MP1 Adr
br
EMU
rEL SrL Ptb Pr2
M2 M3
0.0
0.0
0.0
6.0
13.0
21.0
nu
nu
nu
6.0 13.0 21.0 nu nu nu
0.0
n
y y n
n
n y n n n y n
n
n
ntC 0.0 ntC 0.0 nP 0.0 nP 0.0 420 0.0 PtM 0.0 -0.5 11.0 y y 1°M
1°M
1
96
nu
5.4 321
M4 MENUE PARAMETER DESCRIPTION
Pr1
Energy saving cycle start during holidays
Pr1
Energy saving cycle length during holidays
Pr2
Temperature increasing during Energy Saving
Pr1 Workdays First defrost start
Pr1
Workdays Second defrost start (minimum as Ld1)
Pr1
Workdays Third defrost start (minimum as Ld2)
Pr2
Workdays Fourth defrost start (minimum as Ld3)
Pr2
Workdays Fifth defrost start (minimum as Ld4)
Pr2
Workdays Sixth defrost start (minimum as Ld5)
Pr1 Holidays First defrost start
Pr1 Holidays Second defrost start
Pr1 Holidays Third defrost start
Pr1 Holidays Fourth defrost start
Pr1 Holidays Fifth defrost start
Pr1 Holidays Sixth defrost start
Pr2
Temperature increasing during Energy Saving
Pr2
Energy saving activation when Light switched off
Pr2 Defrost Synchronisation
Pr2 Defrost end Synchronisation
Pr2 SET-POINT Synchronisation
Pr2
Display Synchronisation (temperature sent via LAN)
Pr2 ON/OFF Synchronisation
Pr2 Light Synchronisation
Pr2 AUX Synchronisation
Pr2 Energy Saving Synchronisation
Pr2 Remote probe displaying
Pr2 Pressure value sent in LAN
Pr2 P4 probe sent via LAN
Pr2
Cooling request from LAN enable compressor relay
Pr2
Cold Calling in LAN always enabled even if the compressor block
Pr2 P1 configuration
Pr2 P1 calibration
Pr2 P2 configuration
Pr2 P2 calibration
Pr2 P3 configuration
Pr2 P3 calibration
Pr2 P4 configuration
Pr2 P4 calibration
Pr2 P5 configuration
Pr2 P5 calibration
Pr2 P6 configuration
Pr2 P6 calibration
Pr2 Probe value at 4 mA or/at 0 V (P5)
Pr2 Probe value at 20 mA or/at 5 V (P5)
Pr2 Light on during cleaning mode
Pr2 Fan on during cleaning mode
Pr2 Map selection
Pr2
Map selection loaded by digital input
Pr1 Modbus address
Pr2
Baud Rate selection for ModBus: 9600 or 19200
Pr2
Emulation previous version: 2V8, 3V8, 4V2
Pr2 Release code firmware (only read)
Pr2 Sub-release firmware (only read)
Pr2 Map EEPROM ID
Pr1 Password
Emerson Climate Technologies GmbH Am Borsigturm 31 I 13507 Berlin I Germany
www.climate.emerson.com/en-gb
EC3-XM678D_OI_EN_0521_R00_866931.docx
EC3-XM678D
12/12
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>