Honeywell Genetron AZ-20 Gases Refrigerantes User Guide
- June 7, 2024
- Honeywell
Table of Contents
- Introduction
- Applications
- Servicing Considerations
- Physical Properties
- Product Specifications
- Pressure vs. Temperature
- Transport Properties
- Heat Transfer and Pressure
- Electrical Properties
- Lubricants
- Safety
- Storage and Handling
- Maintenance
- Retrofitting Existing Systems
- Charge Optimization
- Environmental Considerations
- Refrigerant Recovery, Recycling and Reclamation
- Packaging
- Available Literature/Technical Assistance
- Thermodynamic Table — English Units
- Thermodynamic Table — English Units — continued
- Thermodynamic Table — SI Units
- Thermodynamic Table — SI Units — continued
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell Genetron® AZ-20
Properties, Uses,
Storage, and Handling
Introduction
Genetron® AZ-20® (an azeotropic mixture of HFC-32/HFC-125, assigned R-410A by
ASHRAE), has been developed by Honeywell to serve as a long-term, non-ozone-
depleting replace ment for HCFC-22 in a variety of new-equipment
applications. Genetron AZ-20 has a significantly higher capacity and pressure
than HCFC-22 and intrinsically low toxicity. Because it behaves like an
azeotrope, Genetron AZ-20 is easy to service in the field.
Genetron AZ-20 is patented and has been recognized by Underwriters’ Laboratory
as practically non-flammable.
Applications
Unitary Air Conditioning
Genetron AZ-20 is the ideal non-ozone-depleting, long-term replacement for
HCFC-22 in new residential and light commercial unitary air conditioning
systems. In new unitary systems optimized for its use, with either scroll or
reciprocating compres sors, Genetron AZ-20 has shown in tests to have a
5-to-6 percent higher Energy Efficiency Rating (EER) than HCFC-22.
Genetron AZ-20 also has a higher capacity and pressure than HCFC-22, enabling
the design of smaller, more compact air conditioning equipment.
Chillers
Genetron AZ-20 serves as an excellent replacement for HCFC-22 in new chillers, particularly positive displacement chillers. It also may serve as a retrofit fluid for replacing HCFC-22 in some existing chillers with components approved for high pressure, especially those with flooded heat exchangers. Honeywell recommends contacting the original chiller equipment manufacturer before carrying out any retrofit.
Commercial Refrigeration
Genetron AZ-20 may be used as a replacement for HCFC-22 in new medium- temperature commercial refrigeration systems, including supermarket display cases and reach-in coolers.
Servicing Considerations
Genetron AZ-20 is a 50/50 (wt. %) mixture of HFC-32/125.
Genetron AZ-20 exhibits azeotropic behavior with temperature glides that are
less than 0.3°F (0.2°C) over the operating range.
When compared with azeotrope, an azeotropic mixture such as Genetron AZ-20
will not suffer significant segregation in a system and will not materially
change its composition due to a leak. As a result, servicing a system that
uses an azeotropic mixture is similar to servicing a system that uses a pure
fluid.
Physical Properties
Chemical Name | Difluoromethane/ Pentafluoroethane |
---|---|
Molecular Formula | CH2F2/CHF2CF3 |
Appearance | Colorless |
Molecular Weight | 73. |
Boiling Point © 1 ATM (101.3 kPa) | -60.6°F |
-51.5°C
Freezing Point| -247°F -155°C
Critical Temperature’| 160.444°F 71.358°C
Critical Pressure’| 711.06 (Psia) 49.03 (bar)
Critical Volume’| 0.0349 (ftilb) 0.0022 (m’/kg)
Critical Density’| 28.69 (Ion
459.53 (kg/m³)
Vapor Density at Boiling Point| 0.26 (1b/ft’) 4.17 (kg/m³)
Liquid Density’| 66.09 (1b/h’) 1059 (kg/m³)
Liquid Heat Capacity
(at constant pressure)| 0.41 (Btu/lb°F)
1.71 (kJ/kg•K)
Vapor Heat Capacity’© 1 ATM| 0.17 (Btu/lb°F)
0.70 (kJ/kg•K)
Heat of Vaporization at Boiling Point ©1 ATM (101.3 kPa)| 117.43 (Btu/lb)
272.97 (kJ/kg)
Vapor Pressure’| 239.59 (Psia) 16.52 (bar)
Liquid Thermal Conductivity’| 0.0534 (Btu/hr ft°F) 0.0924 (W/m•K)
Vapor Thermal Conductivity’| 0.0091 (Btuftir ft°F) 0.0157 (W/m•K)
Liquid Viscosity’| 0.2825 (Ibm/ft hr)
116.73 (Ibm/ft hr)
Vapor Viscosity’| 0.0351 (Ibm/ft hr) 14.50 (Ibm/ft hr)
% Volatiles by Volume| 100.
Solubility of Water in AZ-20 (wt. %)| 0.28
Flammability Limits in Air (vol. %)’| None
Ozone Depletion Potential (ODP)| 0.00
ASHRAE Safety Group Classification| A1/A1
aRefprop v7.01 (NIST)
- ASTM E681-85 match ignition, ambient conditions
†All measurements are at 77° (25°C) unless otherwise noted.
Product Specifications
Assay (Min. Wt % of HFC-32/125) | 99.70% |
---|---|
Moisture (Max. Wt. %) | 0.001 |
Non-Volatile Residue (Max. Vol. %) | 0.01 |
Chloride (Max. Wt. %) | 0.0001 |
Total Acidity (Max. mg KOH/gm) | 0.0015 |
Non-condensible in vapor phase (Max. Vol. %) | 1.5 |
Pressure vs. Temperature
Temp.
°F| Pressure
Psig| Temp.
°C| Pressure
bar-gauge
---|---|---|---
-40| 10.7| -40| 0.74
-35| 14| -37.5| 0.95
-30| 17.7| -35| 1.17
-25| 21.8| -32.5| 1.42
-20| 26.2| -30| 1.68
-15| 31| -27.5| 1.97
-10| 36.3| -25| 2.28
-5| 42| -22.5| 2.62
0| 48.2| -20| 2.98
5| 54.9| -17.5| 3.37
10| 62.2| -15| 3.79
15| 70| -12.5| 4.24
20| 78.4| -10| 4.72
25| 87.4| -7.5| 5.23
30| 97| -5| 5.77
35| 107.3| -2.5| 6.35
40| 118.4| 0| 6.97
45| 130.1| 2.5| 7.63
50| 142.6| 5| 8.32
55| 156| 7.5| 9.06
60| 170.1| 10| 9.84
65| 185.1| 12.5| 10.66
70| 201.1| 15| 11.53
75| 217.9| 17.5| 12.45
80| 235.8| 20| 13.42
85| 254.6| 22.5| 14.44
90| 274.5| 25| 15.51
95| 295.5| 27.5| 16.64
100| 317.6| 30| 17.83
105| 340.9| 32.5| 19.07
110| 365.4| 35| 20.37
115| 391.2| 37.5| 21.74
120| 418.3| 40| 23.18
125| 446.8| 42.5| 24.68
130| 476.8| 45| 26.25
135| 508.3| 47.5| 27.9
140| 541.4| 50| 29.62
145| 576.3| 52.5| 31.42
150| 613| 55| 33.3
| | 57.5| 35.27
| | 60| 37.33
| | 62.5| 39.49
| | 65| 41.75
Transport Properties
Thermal Conductivity and Viscosity
Temp. °F| Thermal Conductivity
Btu/hr ft °F| Viscosity
Ibitift hr
---|---|---
Liquid| Vapor| Liquid-Vapor
45| 0.0590| 0.0076| 0.3549 0.0316
77| 0.0534| 0.0091| 0.2825 0.0351
110| 0.0477| 0.0120| 0.2196 0.0398
| Thermal Conductivity
mW/m•K , ..,| Viscosity
mp•s
Temp. °C| Liquid| Vapor| Liquid| Vapor
5| 103.4| 12.8| 150.87| 12.92
25| 92.4| 15.7| 116.73| 14.50
50| 79.1| 24.1| 81.80| 17.43
English (T in °F)
Liquid Thermal Conductivity, (Btu/hr ft °F)
λAZ-20 = 0.0002T + 0.0675 Vapor Thermal Conductivity, (Btu/hr ft °F) λAZ-20 =
5.0 x 10 -11 T 4 – 4.0 x 10 -9 T 3 – 5.0 x 10 -8 T 2 + 4.0 x 10 -5 T + 0.0064
Liquid Viscosity, (lb m /ft hr) η= 0.502e – 0.0078T
Vapor Viscosity, (lbm/ft hr) η = 4.0 x 10 -9 3 T –7.0 x 10 -8 2
T + 6.0 x 10 -5 T+ 0.0283–
SI (T in °C)
Liquid Thermal Conductivity, (mW/m•K)
λAZ-20 _ 0.5529T + 106.7
Vapor Thermal Conductivity, (mW/m•K)
λAZ-20 = 1.0 x 10 -6 T 4 + 6.0 x 10 -6 T 3 – 0.0007T 2+ 0.1037T + 12.658
Liquid Viscosity, (mPa•s)
η = 0.0122T 2 – 2.2759T + 163.33
Vapor Viscosity, (mPa•s)
η = 1.0 x 10 -5 T 3 + 0.0003T 2 + 0.0523T + 12.632
Surface Tension
Temp. °C | Temp. °F | s, dyne/cm |
---|---|---|
-40 | -40 | 15.622 |
-35 | -31 | 14.754 |
-30 | -22 | 13.895 |
-25 | -13 | 13.046 |
-20 | -4 | 12.208 |
-15 | 5 | 11.38 |
-10 | 14 | 10.564 |
-5 | 23 | 9.76 |
0 | 32 | 8.969 |
5 | 41 | 8.192 |
10 | 50 | 7.429 |
15 | 59 | 6.681 |
20 | 68 | 5.949 |
25 | 77 | 5.235 |
30 | 86 | 5.539 |
35 | 95 | 3.864 |
40 | 104 | 3.212 |
45 | 113 | 2.585 |
50 | 122 | 1.987 |
55 | 131 | 1.423 |
60 | 140 | 0.901 |
s = -51.226T/Tc +49.826
T in Kelvin or °Rankine
Heat Transfer and Pressure
Drop Characteristics
A number of researchers from tubing, system, and refrigerant manufacturers and
universities have conducted studies on the heat transfer and pressure drop
characteristics of Genetron® AZ-20® R-410A. The table below summarizes results
from seven different sources. The results indicate a consistent increase in
the evaporation heat transfer coefficient averaging 40% higher than R-22.
Condensation values are similar to R-22. The pressure drop is significantly
less than R-22 in both evaporation and condensation, averaging close to 40%
lower in both cases.
For additional information on these results, please contact Genetron
Refrigerants Technical Service.
Heat Transfer Information — Inside Tube
Electrical Properties
Breakdown Voltage and
Dielectric Strength
Breakdown Voltage
volts| Temp.
°F| Pressure
psia| d (Gap)
inches
---|---|---|---
9580| 45| 145| 0.02
17000| 77| 239| 0.02
28100| 110| 380| 0.02
55400| 45| 145| 0.1
92500| 77| 239| 0.1
148300| 110| 380| 0.1
9580| 45| 145| 0.02
---|---|---|---
17000| 77| 239| 0.02
28100| 110| 380| 0.02
55400| 45| 145| 0.1
92500| 77| 239| 0.1
148300| 110| 380| 0.1
8600| 5| 931| 0.05
16700| 25| 1649| 0.05
32600| 50| 3058| 0.05
50700| 5| 931| 0.25
91200| 25| 1649| 0.25
170900| 50| 3058| 0.25
English
Dielectric Strength 50.8 kV/inch @ 1 atm, 77°F
Breakdown Voltage, volts = -1876 + 3952 P (psia) d (inches)
SI
Dielectric Strength 20.0 kV/cm@101.3 kPa, 25°C
Breakdown Voltage, volts = -1876 + 226 P (kPa) d (cm)
*equations derived from measurements per ASTM D2477
Materials Compatibility
The stability of Genetron ® AZ-20 ® R-410A with metals is excellent.
Laboratory testing has shown that Genetron AZ-20 is compatible with steel,
copper, aluminum, and brass. The stability of refriger ant/oil mixtures is
determined using the ASHRAE 97 sealed tube method. AZ-20 was studied with
several lubricants. The tests were conducted in the presence of steel, copper,
and aluminum. The time of the exposure was two weeks, with the temperature of
the exposure being 400°F (204°C). The stability was judged by both visual
observation and measuring the fluoride concentration in the tubes.
A typical example of the results of such tests with three different lubricants
is shown. The visual appearance of the metals and the lubricant is unchanged.
In addition, the amount of fluoride produced in the tube is just barely above
the background con centration. This indicates that the lubricant, metals, and
refrig errant are compatible under the extreme conditions of the tests.
Stability with Polyol Ester
Lubricants and Metals
Lubricant| Lubricant Appearance| Copper| Aluminum|
Steel| Fluoride AZ-20 (p.g) , Purity
---|---|---|---|---|---
Mobil Eal 22| No Change| No Chang| No Change| No Change| No Change
Mobil Eal 32| No Change| No Chang| No Change| No Change 6| No Change
Castro!
SW 32| No Change| No Chang| No Change| No
Change 10| No Change
Note: Test performed at 400°F (204°C) for 14 days.
Chlorinated Materials and Refrigerants
Honeywell does not recommend the use of chlorinated solvents to clean refrigeration systems or components.
Desiccants
Desiccant driers compatible with Genetron AZ-20 are commercially available
from several drier manufacturers.
Individual drier manufacturers should be contacted for specific
recommendations.
Solubility of Water in Genetron® AZ-20®
Compatibility with Plastics and Elastomers
The table below is a summary of materials compatibility data resulting from
tests performed by Honeywell and other worldwide organizations.
Since there are many different grades and formulations of these materials, we
recommend that compatibility testing be per formed on the specific grade of
materials under consideration when designing new systems.
This data should be used only as a guide to the compatibility of materials
with Genetron® AZ-20® R-410A.
The rankings in the table below should be used with caution since they are
judgments based on limited samplings. Customers should consult with the
manufacturer or conduct further independ ent testing.
Summary of Materials Compatibility:
Plastics and Elastomers
Material | AZ-20 |
---|---|
Ethylene-Propylene Diene Terpolymer | S |
Ethylene-Propylene Copolymer | S |
Chlorosulfonated Polyethylene | S |
Chlorinated Polyethylene | D |
Neoprene (Chloroprene) | S |
Epichlorohydrin | D |
Fluorinated Rubbers | U |
Silicone Polyurethane | D |
Nitriles | D |
H-NBR | D |
Butyl Rubber | D |
Polysulfide | S |
Nylon | S |
Polytetrafluoroethylene | S |
PEEK | S |
ABS | U |
Polypropylene | D |
Polyphenyl Sulfide | U |
Polyethylene Terephthalate | D |
Polysulfone | D |
Polyimide | S |
Polyetherimide | S |
Polyphthalamide | D |
Polyamide-imide | S |
Acetal | D |
Phenolic | S |
S: Suitable
D: Suitability dependent on the formulation
U: Unsuitable
Lubricants
As with other HFCs, miscible lubricants such as polyol ester lubricants are
recommended for use with Genetron AZ-20. Many polyol ester lubricants are
commercially available. Castrol SW 32 and Mobil EAL 32 are two polyol ester
lubricants that were test ed by Honeywell. Within a temperature range of
-40°F to 140°F (-40°C to 60°C) and a concentration up to 50% lubricant, these
two lubricants exhibited complete miscibility with Genetron AZ-20.
Honeywell does not recommend specific lubricants. The compres sor and
lubricant manufacturers should be consulted for a specific recommendation.
Safety
Honeywell recommends reading the MSDS before using Genetron AZ-20. Any Genetron MSDS can be obtained through our MSDS request line at 1-973-455-3680 or downloaded from www.genetron.com.
Toxicity
Genetron AZ-20 can be safely used in all of its intended applica tions when
handled in accordance to the Material Safety Data Sheet (MSDS). This is based
on data developed by the Program for Alternative Fluorocarbon Toxicity Testing
(PAFTs, III and V), an international consortium of which Honeywell is a
charter member.
The conclusion was reached after a review of all toxicity results, which
confirmed the intrinsically low toxicity of the components.
Honeywell recommends reading the MSDS before using Genetron AZ-20.
Inhalation
Honeywell has established an occupational exposure limit (8-hour time-weighted
average) of 1000 ppm for Genetron AZ-20.
Inhalation of the product’s vapor may cause irritation. Vapor inhalation at
high concentrations may result in asphyxiation or the heart may become
sensitized, causing the cardiac arrhythmia.
Because of possible disturbances of cardiac rhythm, cate choline drugs, such
as epinephrine, should be used with spe cial caution only in situations of
emergency life support. Treatment of overexposure to Genetron AZ-20 should be
directed at the con control of symptoms.
When concentrations of Genetron AZ-20 reach levels that reduce oxygen to
14-16% by displacement, symptoms of asphyxiation will occur. An individual
exposed to high concentra tions of Genetron AZ-20 must be given medical
attention imme diately. Adequate ventilation must be provided at all times.
Skin and Eye Contact
Genetron® AZ-20® R-410A vapors can irritate the skin and eyes. In liquid form, it can freeze skin or eyes on contact. If contact with the skin should occur, flush the exposed area with lukewarm water until all of the chemicals is removed. If there is evidence of frost bite, bathe in lukewarm water. Should eye contact occur, immedi Italy flush with large amounts of lukewarm water for at least 15 minutes, lifting eyelids occasionally to facilitate irrigation? Seek medical attention as soon as possible.
Leaks
If a large release of Genetron AZ-20 vapor occurs, the area should be evacuated immediately. Protected personnel should de-energize or remove any ignition sources and address leaks, if without risk. Vapors may concentrate near the floor, displacing available oxygen. Once the area is evacuated, it must be venti late using blowers or fans to circulate the air at floor-level. Unprotected personnel should not return to the area until the air has been tested and determined safe. Leak checking should never be done with a mixture of Genetron AZ-20 and air, oxygen or other oxidizers. Leak checking can be performed safely using a mixture of Genetron AZ-20 and nitrogen.
Flammability
According to ASHRAE Standard 34, Genetron AZ-20 is classified in safety group
A1, i.e., it is non-flammable at 1 Atm. pressure (101.3 kPa) and 64°F (18°C).
As defined by the U.S. Department of Transportation (DOT) regulations, flash-
point determinations do not apply to Genetron AZ-20. It has no flame limits,
and DOT considers it non-flammable (Green Label).
In addition, Underwriters’ Laboratory has recognized Genetron AZ-20 as
practically non-flammable. Since Genetron AZ-20 does not have a flash point
and is non-flammable, Honeywell believes that standard industrial-type
electrical installations may be used. It is essential to review and comply
with all local building codes and other applicable regulations and laws when
using Genetron AZ-20 or any other similar product.
Combustibility
Although Genetron AZ-20 is non-flammable at ambient tempera tures and
atmospheric pressures, it can become combustible under pressure when mixed
with air.
Because of this combustibility potential under pressure, Genetron AZ-20 and
air, oxygen or other oxidizers should never be mixed in tanks or supply lines,
or allowed to accumulate in storage tanks. Leak-checking should never be done
with a mixture of Genetron AZ-20 and air, oxygen or other oxidizers.
Leak-checking can be performed safely with a mixture of Genetron AZ-20 and
nitrogen.
Thermal Stability
It is important to avoid exposing Genetron AZ-20 to very high temperatures.
When exposed to high temperatures, such as those found in flames, Genetron
AZ-20 vapors will decompose.
This will produce toxic and irritating compounds. Pungent odors released will
irritate the nose and throat and generally force evacuation of the area.
Genetron AZ-20 is stable under normal operating conditions.
Contact with certain red-hot metals may result in exothermic or explosive
reactions and yield toxic and/or corrosive decomposi tion products. Specific
materials to avoid include freshly abrad ed aluminum surfaces and active
metals such as sodium, potas sodium, calcium, powdered aluminum, magnesium,
and zinc.
Storage and Handling
Bulk and Cylinder
Genetron AZ-20 has a higher vapor pressure compared to most of the current
refrigerants, particularly Genetron 22 (HCFC-22). For this reason, Genetron
AZ-20 must be handled with careful attention to the design pressure rating of
the handling equipment. All storage shipping containers — cylinders, storage
tanks, tank trailers or tank cars — must be specifically designed to handle
Genetron AZ-20.
Another important handling practice that must be followed for Genetron AZ-20
is to ensure that all transfers be executed by using liquid charging instead
of vapor charging. This practice will help minimize compositional changes.
Genetron AZ-20 cylinders must be clearly marked and kept in a cool, dry and
properly ventilated storage area away from heat, flames, corrosive chemicals,
fumes, explosives and be otherwise protected from damage. Disposable Jugs™
should be discarded in an environmentally safe manner in accordance with all
laws and regulations.
Empty cylinders should be returned to Honeywell or your Genetron Wholesaler.
Under no circumstance should anything be put into the empty cylinder? Prior to
disposal, cylinder con tents should be recovered to an internal pressure of 0
psig or less. Once empty, properly close the cylinder valve and replace the
valve cap.
Keep cylinders of Genetron® AZ-20® R-410A out of direct sun light, especially
in warm weather. Genetron AZ-20 expands signif icantly when heated, reducing
the amount of vapor space left in the cylinder. Once the cylinder becomes
liquid-full, any further rise in temperature can cause it to burst,
potentially resulting in serious personal injury. NEVER ALLOW A CYLINDER TO
GET WARMER THAN 125°F (52°C).
Always store cylinders above dirt or damp floors to prevent rust ing, using a
platform or parallel rails . SECURE CYLINDERS IN PLACE BY MEANS OF A RACK,
CHAIN, OR ROPE TO PREVENT THEM FROM TIPPING, FALLING, ROLLING OR CCIDENTALLY
STRIKING EACH OTHER OR ANY OTHER OBJECT. If the cylinder valve is broken
off, rapid escape of the high-pressure contents will propel the cylinder,
which could potentially result in serious injury. Keep cylinder caps in place
until the cylinder is in use.
The storage area should be away from corrosive chemicals or fumes to avoid
damaging effects on the cylinder and threaded areas of the valve. Follow
similar precautions for bulk storage and transport systems, ensuring that
proper design and operation satisfies the required pressure rating and also
avoids external corrosive conditions, overheating or overfilling.
If a cylinder leak is detected, contact Honeywell for guidance.
Maintenance
A thorough pre-job review must be done to determine respirato ry protection
requirements, as well as any other safety equipment needed. Maintenance in
areas where Genetron AZ-20 has accu emulated should be performed only after
confirming that work area concentrations are below the permissible exposure
level (PEL). This may be determined using a vapor-in-air analyzer capable of
measuring the amount of airborne Genetron AZ-20.
These vapors are heavier than air and can accumulate at floor level. When
vapor concentrations are above the PEL, the area should be ventilated to
reduce the vapor concentration to below the PEL before entry. Ventilate the
area using fans and other air movers as necessary. If the entry must be made
to areas where vapor concentrations are above the PEL, appropriate respiratory
protection should be used.
Federal occupational health and safety agencies often have legal requirements
and guidelines for proper selection and use of respiratory protection. It is
often the responsibility of the employer to ensure the safety of the employees
performing the maintenance. Be sure to comply with applicable laws and
guidelines for proper selection and use of respiratory protection. If the
airborne concentration of refrigerant is unknown or at a par particular
threshold, the law may require the use of supplied air res pirates.
Particular work team and work zone entry procedures may also apply. Vessels,
containers, transfer lines, pumps, and other equipment should not be exposed
to high-temperature sources (such as welding, brazing, and open flames) until
they have been thoroughly cleaned and found free of vapors.
Exposure to these circumstances can cause fire, explosion, and decomposition
of refrigerant. This may result in the formation of toxic or corrosive
compounds. Potential sources for further vapor releases should also be
eliminated if possible.
When possible, maintenance or cleaning of equipment should be performed
without entering the vessel. A tank or storage ves sel may be a confined
space. These spaces may have a config uration that can hinder activities
and/or expose personnel to the risk of physical injury from entrapment,
engulfment, or hazardous atmospheres. Depending on conditions and applicable
regula tions, a permit may be required to enter such vessels. If a tank must
be entered, personnel should be required to use a formal tank entry procedure
based on recognized safety principles and comply with all applicable
regulations. The procedure would provide guidance for critical items such as
but not limited to respiratory protection, safety equipment, work practice,
and communication. Among the possible requirements of these
procedures is the use of a fully qualified work team and placement of a
confined space entry permit at the job site.
Leak Detection
Use leak detectors for pinpointing leaks or for monitoring an entire room on a
continual basis. Leaks detectors are important for refrigerant conservation,
equipment protection, and performance, reduction of emissions, and protection
of those coming in contact
with the system.
Leak testing should not be performed using mixtures of air and Genetron®
AZ-20®. There are two types of leak detectors — leak pinpointers and area
monitors. Before purchasing either type, several equipment factors should be
considered, including detec tion limits, sensitivity, and selectivity.
Regarding selectivity, there are three categories: non-selective, halogen-
selective, and com pound selective. In general, the complexity and cost of a
leak detec tor increase as the specificity increases. Fluorescent dye
approved by the equipment manufacturer can be added to sys tem to help
pinpoint leaks.
New installations should be checked for leaks prior to complete charging.
Whenever a leak inspection is performed, check all factory and field joints
throughout the system. For a system that has been in operation for some time,
check for oil at joints and connections, as this may serve as an indication of
a refrigerant leak at that location. This approach would not commonly be con
considered when leak checking a new system installation since it is much less
likely that oil will have found its way to the leak.
If a system has lost all or most of its refrigerant charge, the sys tem must
be pressurized to about 150 psig in order to perform a leak check. Pressure
can be restored for leak checking by adding Genetron AZ-20 R-410A using normal
charging procedures or by using dry nitrogen. DO NOT USE AIR TO LEAK CHECK
THE SYSTEM. (At pressures above atmospheric, mixtures of air and Genetron
AZ-20 R-410A, like R-22, will become combustible.) For a system containing
either all refrigerant or a mixture of refrigerant and nitrogen, an electronic
leak detector can be used. The leak detector must be capable of detecting a
hydrofluorocarbon (HFC) refrigerant. Older leak detectors designed for R-22
will not be sensitive enough to effectively detect HFC refrigerants. Halide
torches can not effectively detect
HFC refrigerant leaks. NITROGEN IS A HIGH-PRESSURE GAS, REMEMBER TO USE A
PRESSURE REGULA TOR COMING OFF THE NITROGEN TANK TO AVOID ANY RISK OF SEVERE
PERSONAL INJURY.
A simple way to test for leaks is to use a solution of soap and water.
Commercial soap solutions for leak detection tend to be more effective. Apply
the solution to joints and connections.
The generation of bubbles will indicate a pinhole leak. Several min utes may
be required to generate a bubble in the case of a very small leak. When it is
suspected that essentially no refrigerant remains in the system, the above
method can be used to detect leaking nitrogen gas. However, the most
convenient and effective means to detect a leak when Genetron® AZ-20® is in
the system is to use an electronic leak detector designed for HFC
refrigerants.
When a leak is found, the refrigerant must be recovered and the leak repaired
prior to final charging and operation. If the refriger ant charge is 50
pounds or more, the system is subject to leak repair requirements under the
Refrigerant Recycling Regulations of Section 608 of the Clean Air Act
Amendments of 1990. In this case, the equipment owner must keep a record of
the date and type of service performed and the amount of refrigerant added.
Retrofitting Existing Systems
Genetron AZ-20 is the long-term non-ozone-depleting replace ment for HCFC-22
in new equipment due to its many favorable performance characteristics.
However, the performance proper ties which make it the replacement for
HCFC-22 in new equipment — higher capacity and higher pressure — make it
difficult to be used in existing systems designed for HCFC-22. In most cases,
mandatory changes would include compressors and thermostat ic expansion
valves. Condensers and other high-pressure-side components may also require
replacement. Depending on the applicable design standard for pressure-
containing components and the particular design, even low-pressure-side
components may require changing. Provided local building codes permit, and
equipment manufacturers approve, it may be possible to retain the indoor coil
and inter-connecting lines.
When converting an existing R-22 residential air-conditioning system to
Genetron AZ-20 R-410A, the condensing unit will have to be replaced with one
designed for R-410A. If the expansion device is a short tube orifice, it can
typically be modified using a kit available from the manufacturer. An R-22
thermostatic expan sion valve (TXV) must be replaced with an R-410A TXV. It
is also important to install a compatible liquid-line filter drier. If water
or acid needs to be removed, consult the equipment manufacturer’s application
information or service manual. Confirm with the equipment manufacturer that
the existing indoor coil is suitable–some existing indoor coils (capillary
tube or pre-1980’s design) are not acceptable for use with Genetron AZ-20.
Indoor sections must be UL approved for appropriate service pressure ratings.
The service pressure rating for Genetron AZ-20 is 235 psig. Indoor coils
listed for R-22 heat pump
applications would meet or exceed this rating. In most cases, existing line
sets can be used.
Be certain to follow the equipment manufacturer’s procedures for pump-down and
recovery of the original R-22 charge and for instal location of the new
condensing unit, expansion device, and liquid-line filter drier. For a
residential air-conditioning retrofit where indoor coil and lines stay, it is
important to drain residual mineral oil or alkylben zene oil from the system.
Systems charged with R-410A can tolerate a small mineral oil residual. Pay
particular attention to low spots in the suction line and evaporator where oil
may have accumulated. Never leave a system open to the atmosphere for more
than 15 minutes.
A miscible lubricant such as polyol ester (POE) lubricant must be used with
Genetron AZ-20 R-410A refrigerant. Refer to the equipment manufacturer for a
list of approved lubricants since lubricants are not always interchangeable.
POE lubricant readily absorbs moisture; therefore, care should be taken to
minimize exposure of the lubricant to the atmosphere. Use a pump to trans fer
lubricant; do not pour. In an air-conditioning system, a filter drier can be
used to effectively remove moisture from POE lubricant; A VACUUM PUMP WILL NOT
WORK.
After the new condensing unit, expansion device, and liquid-line filter drier
have been installed, evacuate the system to 500 microns to ensure that air and
liquid water are effectively removed from the system. Once a system is under a
vacuum, does not open to the atmosphere. Break vacuum using Genetron AZ-20 or
if a triple evacuation method is being used, break vacuum using 2-3 psig dry
nitrogen. Once certain that there are no leaks, weigh in the refrigerant
charge using a dial-a-charge designed for Genetron AZ-20 or a digital scale.
Charge Optimization
Standard superheat and subcooling procedures can be used to optimize the
refrigerant charge. Fixed restrictor-type metering devices require charge
optimization using the superheat method. A system charged with Genetron AZ-20
and equipped with an R-410A TXV (thermostatic expansion valve) requires use of
the subcooling method for refrigerant charge optimization. Do not use an R-22
TXV with Genetron AZ-20.
For a typical 3/8-inch outer diameter liquid line, long line applications will
require approximately 0.50 oz. of refrigerant per foot of additional length.
Charging units with long refrigerant lines must be done carefully since
pressure and temperature changes occur more slowly. Add or remove refrigerant
in small increments (about 5% by weight of the original system charge) and
allow the system to stabilize between each.
LIQUID CHARGE USING A COMMERCIAL METERING DEVICE IN THE MANIFOLD HOSE.
CHARGE INTO THE SUCTION LINE.
Consult Honeywell’s Genetron® AZ-20® (R-410A) Air-Conditioning System Charging
and Recovery Guidelines (publication
G-525-083) for more detailed information on charge optimization.
Filter Driers
Liquid-line filter driers must have rated working pressures of no less than
600psig. Honeywell recommends the use of a liquid-line filter
drier. Be certain not to install a suction-line drier in the liquid line.
The filter drier should be approved for R-410A refrigerant. Remove a filter
drier from the system by using a tubing cutter. Do not unsweat a filter drier
since heat will release moisture and contami nants from the drier into the
system.
Environmental Considerations
Genetron AZ-20 is a halogenated hydrocarbon. Treatment or disposal of wastes
generated by use of this product may require special consideration, depending
on the nature of the wastes and the means of discharge, treatment or disposal.
For more information, refer to the Material Safety Data Sheet (MSDS).
If discarded unused, Genetron AZ-20 is not considered a “haz arduous waste”
by the Resource Conservation and Recovery Act (RCRA). Because Genetron AZ-20
is considered to have mini mum biodegradability, care should be taken to
avoid releases to the environment.
The disposal of Genetron AZ-20 may be subject to federal, state and local
regulations. Users should conduct disposal operations in compliance with
applicable federal, state, and local laws and regulations. Appropriate
regulatory agencies also should be consulted before discharging or disposing
of waste materials.
Refrigerant Recovery, Recycling and Reclamation
In the United States, amendments to the 1990 Clean Air Act require mandatory
recycling and reclamation of refrigerants during maintenance, servicing, or
repair of air-conditioning or refrigeration equipment. This includes HFC
(hydrofluorocarbon) refrigerants such as Genetron AZ-20. The venting of
refrigerants to the atmos here is prohibited. The recovery or recycling
device must be EPA-approved. Recycled refrigerant may only be returned to the
equip ment from which it was removed or used in other equipment owned
by the same person.
IT IS VERY IMPORTANT TO MAKE CERTAIN THAT THE RECYCLE OR RECOVERY EQUIPMENT
USED IS DESIGNED FOR R-410A. The pressure of the Genetron AZ-20 refrigerant
is approximately 60% (1.6 times) greater than that of R 22. Pressure gauges
require a range up to 800 psig high-side and 250 PSIG low-side with a 550 psig
low-side retard. Hoses need an 800 psig service pressure rating. Recovery
cylinders require a 400 psig service pressure rating — DO NOT PUT GENETRON®
AZ 20® R-410A IN A 300 PSIG RATED CYLINDER. DOT 4BA400 and DOT 4BW400 vessels
are acceptable.
The refrigerant that is too contaminated for reuse must be properly disposed
of or reclaimed. Reclamation can only be performed at an EPA (Environmental
Protection Agency) approved reclamation facility. Most Genetron refrigerant
wholesalers will accept recov ered Genetron AZ-20 for reclamation.
Packaging
Genetron AZ-20 is available in a variety of containers. They include 25-lb disposable Jugs™, 100-lb returnable cylinders, and one ton (1450-lb) returnable tanks. Bulk tank trailers and so tanks are available. Consult your Genetron Sales Representative if a larger container is required.
Available Literature/Technical Assistance
Honeywell has a wide range of literature available for all of its
environmentally safer Genetron products, covering such topics as reclamation,
retrofitting guidelines, product specifications, and physical properties. In
addition, Honeywell technical specialists are available to assist you in all
aspects of using Genetron AZ-20 — handling and storage and applications
assistance. For further information, please write us at:
Honeywell Genetron Refrigerants
P.O. Box 1053
Morristown, NJ 07962-1053
Or call us at 1-800-631-8138
Thermodynamic Table — English Units
Temp
°F| Pressure
Asia| Liquid Density
3 lb/ft| Vapor volume
3 ft /lb| Enthalpy Cliq
Btu/lb| Enthalpy Dh Btu/lb| Enthalpy Hvap
Btu/lb| Entropy Sliq
Btu/lb °F| Entropy Swap
Btu/lb °F
---|---|---|---|---|---|---|---|---
-60| 14.9| 84.1928| 3.7914| -6.6| 117.29| 110.69| -0.0161| 0.2775
-58| 15.8| 83.974| 3.5965| -5.95| 116.89| 110.94| -0.0144| 0.2766
-56| 16.7| 83.7544| 3.4136| -5.29| 116.47| 111.18| -0.0128| 0.2758
-54| 17.6| 83.5341| 3.2418| -4.63| 116.06| 111.43| -0.0112| 0.275
-52| 18.6| 83.313| 3.0803| -3.97| 115.64| 111.67| -0.0096| 0.2742
-50| 19.7| 83.0912| 2.9285| -3.31| 115.23| 111.92| -0.008| 0.2734
-48| 20.7| 82.8686| 2.7856| -2.65| 114.81| 112.16| -0.0064| 0.2726
-46| 21.8| 82.6452| 2.6511| -1.99| 114.38| 112.39| -0.0048| 0.2718
-44| 23| 82.421| 2.5243| -1.33| 113.96| 112.63| -0.0032| 0.271
-42| 24.2| 82.1959| 2.4048| -0.66| 113.53| 112.87| -0.0016| 0.2703
-40| 25.5| 81.97| 2.2921| 0| 113.1| 113.1| 0| 0.2696
-38| 26.8| 81.7432| 2.1857| 0.67| 112.66| 113.33| 0.0016| 0.2688
-36| 28.1| 81.5155| 2.0853| 1.33| 112.23| 113.56| 0.0031| 0.2681
-34| 29.5| 81.2869| 1.9903| 2| 111.79| 113.79| 0.0047| 0.2674
-32| 31| 81.0573| 1.9006| 2.67| 111.35| 114.02| 0.0063| 0.2667
-30| 32.5| 80.8268| 1.8157| 3.34| 110.91| 114.25| 0.0078| 0.266
-28| 34.1| 80.5952| 1.7353| 4.01| 110.46| 114.47| 0.0094| 0.2653
-26| 35.7| 80.3627| 1.6592| 4.68| 110.01| 114.69| 0.0109| 0.2646
-24| 37.4| 80.1291| 1.587| 5.36| 109.55| 114.91| 0.0125| 0.264
-22| 39.2| 79.8945| 1.5187| 6.03| 109.1| 115.13| 0.014| 0.2633
-20| 41| 79.6588| 1.4538| 6.71| 108.63| 115.34| 0.0155| 0.2627
-18| 42.9| 79.4219| 1.3923| 7.39| 108.17| 115.56| 0.0171| 0.262
-16| 44.9| 79.1839| 1.3339| 8.07| 107.7| 115.77| 0.0186| 0.2614
-14| 46.9| 78.9447| 1.2784| 8.75| 107.23| 115.98| 0.0201| 0.2608
-12| 49| 78.7044| 1.2256| 9.43| 106.75| 116.18| 0.0216| 0.2601
-10| 51.2| 78.4628| 1.1755| 10.11| 106.28| 116.39| 0.0231| 0.2595
-8| 53.4| 78.2199| 1.1278| 10.8| 105.79| 116.59| 0.0246| 0.2589
-6| 55.7| 77.9757| 1.0823| 11.48| 105.31| 116.79| 0.0261| 0.2583
-4| 58.1| 77.7302| 1.0391| 12.17| 104.82| 116.99| 0.0276| 0.2577
-2| 60.6| 77.4834| 0.9979| 12.86| 104.33| 117.19| 0.0291| 0.2571
0| 63.1| 77.2351| 0.9587| 13.55| 103.83| 117.38| 0.0306| 0.2566
2| 65.8| 76.9854| 0.9213| 14.25| 103.32| 117.57| 0.0321| 0.256
4| 68.5| 76.7342| 0.8856| 14.94| 102.82| 117.76| 0.0336| 0.2554
6| 71.3| 76.4816| 0.8516| 15.64| 102.31| 117.95| 0.0351| 0.2548
8| 74.2| 76.2273| 0.8191| 16.34| 101.79| 118.13| 0.0366| 0.2543
10| 77.1| 75.9715| 0.788| 17.04| 101.27| 118.31| 0.0381| 0.2537
12| 80.2| 75.714| 0.7584| 17.74| 100.75| 118.49| 0.0395| 0.2532
14| 83.3| 75.4549| 0.73| 18.45| 100.21| 118.66| 0.041| 0.2526
16| 86.6| 75.194| 0.7029| 19.15| 99.68| 118.83| 0.0425| 0.2521
18| 89.9| 74.9314| 0.677| 19.86| 99.14| 119| 0.044| 0.2516
20| 93.4| 74.6669| 0.6522| 20.57| 98.6| 119.17| 0.0454| 0.251
22| 96.9| 74.4006| 0.6285| 21.29| 98.04| 119.33| 0.0469| 0.2505
24| 100.5| 74.1324| 0.6057| 22| 97.49| 119.49| 0.0484| 0.25
26| 104.3| 73.8621| 0.584| 22.72| 96.93| 119.65| 0.0498| 0.2494
28| 108.1| 73.5899| 0.5631| 23.44| 96.36| 119.8| 0.0513| 0.2489
30| 112.1| 73.3156| 0.5431| 24.16| 95.79| 119.95| 0.0527| 0.2484
32| 116.1| 73.0391| 0.5239| 24.89| 95.21| 120.1| 0.0542| 0.2479
34| 120.3| 72.7604| 0.5055| 25.62| 94.62| 120.24| 0.0557| 0.2474
36| 124.6| 72.4794| 0.4878| 26.35| 94.03| 120.38| 0.0571| 0.2469
38| 129| 72.1961| 0.4708| 27.08| 93.43| 120.51| 0.0586| 0.2463
40| 133.5| 71.9104| 0.4546| 27.82| 92.83| 120.65| 0.06| 0.2458
42| 138.1| 71.6223| 0.4389| 28.56| 92.21| 120.77| 0.0615| 0.2453
44| 142.9| 71.3315| 0.4239| 29.3| 91.6| 120.9| 0.0629| 0.2448
46| 147.7| 71.0382| 0.4094| 30.04| 90.98| 121.02| 0.0644| 0.2443
48| 152.7| 70.7422| 0.3955| 30.79| 90.34| 121.13| 0.0658| 0.2438
Thermodynamic Table — English Units — continued
Temp
°F| Pressure
Asia| Liquid Density³
lb/ft| Vapor volume³ **ft /lb| Enthalpy Cliq
Btu/lb| Enthalpy Dh
Btu/lb| Enthalpy Hvap
Btu/lb| Entropy Sliq
Btu/lb °F| Entropy Swap
Btu/lb °F**
---|---|---|---|---|---|---|---|---
50| 157.9| 70.4433| 0.3821| 31.54| 89.7| 121.24| 0.0673| 0.2433
52| 163.1| 70.1416| 0.3693| 32.3| 89.04| 121.34| 0.0687| 0.2428
54| 168.5| 69.837| 0.3569| 33.05| 88.4| 121.45| 0.0702| 0.2423
56| 174| 69.5293| 0.345| 33.82| 87.72| 121.54| 0.0716| 0.2418
58| 179.6| 69.2184| 0.3335| 34.58| 87.05| 121.63| 0.0731| 0.2413
60| 185.4| 68.9043| 0.3224| 35.35| 86.37| 121.72| 0.0745| 0.2408
62| 191.3| 68.5869| 0.3117| 36.12| 85.68| 121.8| 0.076| 0.2402
64| 197.4| 68.266| 0.3014| 36.9| 84.97| 121.87| 0.0774| 0.2397
66| 203.6| 67.9415| 0.2915| 37.68| 84.26| 121.94| 0.0789| 0.2392
68| 210| 67.6134| 0.2819| 38.46| 83.54| 122| 0.0803| 0.2387
70| 216.5| 67.2814| 0.2727| 39.25| 82.81| 122.06| 0.0818| 0.2382
72| 223.1| 66.9454| 0.2638| 40.04| 82.07| 122.11| 0.0833| 0.2376
74| 229.9| 66.6054| 0.2552| 40.84| 81.31| 122.15| 0.0847| 0.2371
76| 236.9| 66.2611| 0.2469| 41.64| 80.54| 122.18| 0.0862| 0.2366
78| 244| 65.9125| 0.2388| 42.44| 79.77| 122.21| 0.0876| 0.236
80| 251.2| 65.5593| 0.2311| 43.25| 78.98| 122.23| 0.0891| 0.2355
82| 258.7| 65.2013| 0.2235| 44.07| 78.18| 122.25| 0.0906| 0.2349
84| 266.3| 64.8385| 0.2163| 44.89| 77.36| 122.25| 0.092| 0.2344
86| 274| 64.4705| 0.2092| 45.72| 76.53| 122.25| 0.0935| 0.2338
88| 282| 64.0972| 0.2024| 46.55| 75.69| 122.24| 0.095| 0.2332
90| 290.1| 63.7184| 0.1959| 47.38| 74.84| 122.22| 0.0965| 0.2327
92| 298.3| 63.3338| 0.1895| 48.23| 73.96| 122.19| 0.098| 0.2321
94| 306.8| 62.9431| 0.1833| 49.08| 73.07| 122.15| 0.0995| 0.2315
96| 315.4| 62.5461| 0.1773| 49.93| 72.17| 122.1| 0.101| 0.2309
98| 324.2| 62.1424| 0.1715| 50.8| 71.25| 122.05| 0.1025| 0.2303
100| 333.2| 61.7317| 0.1659| 51.67| 70.3| 121.97| 0.104| 0.2296
102| 342.4| 61.3136| 0.1604| 52.54| 69.35| 121.89| 0.1055| 0.229
104| 351.8| 60.8878| 0.1551| 53.43| 68.37| 121.8| 0.107| 0.2283
106| 361.4| 60.4537| 0.15| 54.32| 67.37| 121.69| 0.1085| 0.2277
108| 371.2| 60.0109| 0.145| 55.22| 66.35| 121.57| 0.1101| 0.227
110| 381.1| 59.5588| 0.1401| 56.13| 65.31| 121.44| 0.1116| 0.2263
112| 391.3| 59.0968| 0.1354| 57.05| 64.24| 121.29| 0.1132| 0.2256
114| 401.7| 58.6242| 0.1308| 57.98| 63.14| 121.12| 0.1147| 0.2248
116| 412.3| 58.1402| 0.1263| 58.92| 62.02| 120.94| 0.1163| 0.2241
118| 423.1| 57.6438| 0.1219| 59.88| 60.86| 120.74| 0.1179| 0.2233
120| 434.1| 57.1341| 0.1176| 60.84| 59.68| 120.52| 0.1195| 0.2225
122| 445.3| 56.6098| 0.1135| 61.82| 58.45| 120.27| 0.1212| 0.2217
124| 456.8| 56.0697| 0.1094| 62.82| 57.19| 120.01| 0.1228| 0.2208
126| 468.5| 55.5121| 0.1055| 63.83| 55.89| 119.72| 0.1245| 0.2199
128| 480.4| 54.9352| 0.1016| 64.85| 54.55| 119.4| 0.1261| 0.219
130| 492.6| 54.3368| 0.0978| 65.9| 53.16| 119.06| 0.1278| 0.218
132| 505| 53.7142| 0.0941| 66.97| 51.71| 118.68| 0.1296| 0.217
134| 517.7| 53.0645| 0.0904| 68.07| 50.2| 118.27| 0.1314| 0.2159
136| 530.6| 52.3837| 0.0868| 69.19| 48.62| 117.81| 0.1332| 0.2148
138| 543.8| 51.6673| 0.0833| 70.34| 46.97| 117.31| 0.135| 0.2136
140| 557.2| 50.9094| 0.0798| 71.53| 45.23| 116.76| 0.1369| 0.2124
142| 570.9| 50.1027| 0.0763| 72.76| 43.39| 116.15| 0.1389| 0.211
144| 584.9| 49.2375| 0.0729| 74.05| 41.41| 115.46| 0.1409| 0.2096
146| 599.2| 48.3009| 0.0694| 75.39| 39.3| 114.69| 0.1431| 0.208
148| 613.7| 47.2751| 0.0659| 76.81| 37.01| 113.82| 0.1453| 0.2062
150| 628.6| 46.1339| 0.0624| 78.34| 34.48| 112.82| 0.1477| 0.2043
Thermodynamic Table — SI Units
Temp
°F| Pressure
kPa| Liquid Density kg/m³| Vapor volume
m /kg³| Enthalpy Hliq
kJ/kg| Enthalpy Δh
kJ/kg| Enthalpy Hvap
kJ/kg| Entropy Sliq
kJ/kg °C| Entropy Svap
kJ/kg ° C
---|---|---|---|---|---|---|---|---
-30| 270| 1280| 0.0948| 156.17| 253.58| 409.75| 0.8318| 1.8749
-29| 282| 1276| 0.0912| 157.58| 252.62| 410.2| 0.8376| 1.8725
-28| 293| 1273| 0.0877| 159| 251.65| 410.65| 0.8433| 1.87
-27| 305| 1270| 0.0843| 160.42| 250.67| 411.09| 0.8491| 1.8677
-26| 318| 1266| 0.0812| 161.84| 249.69| 411.53| 0.8548| 1.8653
-25| 331| 1263| 0.0781| 163.27| 248.7| 411.97| 0.8605| 1.8629
-24| 344| 1259| 0.0752| 164.7| 247.7| 412.4| 0.8662| 1.8606
-23| 357| 1256| 0.0725| 166.13| 246.7| 412.83| 0.8719| 1.8583
-22| 371| 1252| 0.0698| 167.56| 245.69| 413.25| 0.8776| 1.856
-21| 386| 1249| 0.0673| 169| 244.67| 413.67| 0.8833| 1.8538
-20| 401| 1245| 0.0649| 170.44| 243.64| 414.08| 0.8889| 1.8516
-19| 416| 1242| 0.0626| 171.88| 242.61| 414.49| 0.8945| 1.8493
-18| 432| 1238| 0.0603| 173.33| 241.57| 414.9| 0.9002| 1.8471
-17| 448| 1234| 0.0582| 174.78| 240.52| 415.3| 0.9058| 1.845
-16| 465| 1231| 0.0562| 176.23| 239.47| 415.7| 0.9114| 1.8428
-15| 482| 1227| 0.0542| 177.69| 238.4| 416.09| 0.917| 1.8407
-14| 499| 1223| 0.0523| 179.15| 237.32| 416.47| 0.9226| 1.8386
-13| 517| 1220| 0.0505| 180.61| 236.25| 416.86| 0.9282| 1.8365
-12| 536| 1216| 0.0488| 182.08| 235.15| 417.23| 0.9337| 1.8344
-11| 555| 1212| 0.0472| 183.55| 234.05| 417.6| 0.9393| 1.8323
-10| 575| 1209| 0.0456| 185.02| 232.95| 417.97| 0.9449| 1.8303
-9| 595| 1205| 0.0441| 186.5| 231.83| 418.33| 0.9504| 1.8282
-8| 615| 1201| 0.0426| 187.99| 230.69| 418.68| 0.9559| 1.8262
-7| 637| 1197| 0.0412| 189.47| 229.56| 419.03| 0.9615| 1.8242
-6| 658| 1193| 0.0398| 190.96| 228.41| 419.37| 0.967| 1.8222
-5| 681| 1190| 0.0385| 192.46| 227.25| 419.71| 0.9725| 1.8202
-4| 703| 1186| 0.0373| 193.96| 226.08| 420.04| 0.978| 1.8182
-3| 727| 1182| 0.0361| 195.46| 224.91| 420.37| 0.9835| 1.8162
-2| 751| 1178| 0.0349| 196.97| 223.72| 420.69| 0.989| 1.8143
-1| 775| 1174| 0.0338| 198.48| 222.52| 421| 0.9945| 1.8123
0| 801| 1170| 0.0327| 200| 221.31| 421.31| 1| 1.8104
1| 827| 1166| 0.0317| 201.52| 220.08| 421.6| 1.0055| 1.8084
2| 853| 1162| 0.0307| 203.05| 218.85| 421.9| 1.011| 1.8065
3| 880| 1158| 0.0297| 204.58| 217.6| 422.18| 1.0164| 1.8046
4| 908| 1154| 0.0288| 206.12| 216.34| 422.46| 1.0219| 1.8027
5| 936| 1150| 0.0279| 207.66| 215.07| 422.73| 1.0274| 1.8007
6| 965| 1145| 0.027| 209.21| 213.78| 422.99| 1.0328| 1.7988
7| 995| 1141| 0.0262| 210.77| 212.48| 423.25| 1.0383| 1.7969
8| 1025| 1137| 0.0254| 212.33| 211.16| 423.49| 1.0438| 1.795
9| 1057| 1133| 0.0246| 213.89| 209.84| 423.73| 1.0492| 1.7931
10| 1088| 1128| 0.0239| 215.46| 208.5| 423.96| 1.0547| 1.7912
11| 1121| 1124| 0.0231| 217.04| 207.14| 424.18| 1.0602| 1.7893
12| 1154| 1120| 0.0224| 218.63| 205.76| 424.39| 1.0656| 1.7874
13| 1188| 1115| 0.0218| 220.22| 204.37| 424.59| 1.0711| 1.7855
14| 1223| 1111| 0.0211| 221.81| 202.98| 424.79| 1.0765| 1.7836
15| 1258| 1106| 0.0205| 223.42| 201.55| 424.97| 1.082| 1.7816
16| 1295| 1102| 0.0199| 225.03| 200.11| 425.14| 1.0875| 1.7797
17| 1332| 1097| 0.0193| 226.64| 198.67| 425.31| 1.0929| 1.7778
18| 1370| 1092| 0.0187| 228.27| 197.19| 425.46| 1.0984| 1.7758
19| 1408| 1088| 0.0181| 229.9| 195.7| 425.6| 1.1039| 1.7739
20| 1448| 1083| 0.0176| 231.54| 194.19| 425.73| 1.1094| 1.7719
21| 1488| 1078| 0.0171| 233.19| 192.66| 425.85| 1.1148| 1.77
22| 1529| 1073| 0.0166| 234.85| 191.1| 425.95| 1.1203| 1.768
23| 1571| 1069| 0.0161| 236.51| 189.53| 426.04| 1.1258| 1.766
24| 1614| 1064| 0.0156| 238.18| 187.94| 426.12| 1.1313| 1.764
Thermodynamic Table — SI Units — continued
Temp
°F| Pressure
kPa| Liquid Density
kg/m³| Vapor volume
m³ /kg| Enthalpy Hliq
kJ/kg| Enthalpy Δh
kJ/kg| Enthalpy Hvap
kJ/kg| Entropy Sliq
kJ/kg °C| Entropy Svap
kJ/kg °C
---|---|---|---|---|---|---|---|---
25| 1657| 1059| 0.0152| 239.86| 186.33| 426.19| 1.1368| 1.7619
26| 1702| 1054| 0.0147| 241.55| 184.7| 426.25| 1.1424| 1.7599
27| 1747| 1048| 0.0143| 243.25| 183.03| 426.28| 1.1479| 1.7578
28| 1794| 1043| 0.0139| 244.96| 181.35| 426.31| 1.1534| 1.7558
29| 1841| 1038| 0.0135| 246.68| 179.64| 426.32| 1.159| 1.7537
30| 1889| 1033| 0.0131| 248.41| 177.9| 426.31| 1.1645| 1.7515
31| 1939| 1027| 0.0127| 250.15| 176.14| 426.29| 1.1701| 1.7494
32| 1989| 1022| 0.0123| 251.9| 174.35| 426.25| 1.1757| 1.7472
33| 2040| 1016| 0.012| 253.66| 172.54| 426.2| 1.1813| 1.745
34| 2092| 1011| 0.0116| 255.43| 170.69| 426.12| 1.1869| 1.7428
35| 2145| 1005| 0.0113| 257.22| 168.81| 426.03| 1.1925| 1.7405
36| 2199| 999| 0.0109| 259.01| 166.91| 425.92| 1.1982| 1.7382
37| 2254| 993| 0.0106| 260.82| 164.97| 425.79| 1.2038| 1.7359
38| 2310| 988| 0.0103| 262.65| 162.98| 425.63| 1.2095| 1.7335
39| 2367| 981| 0.01| 264.48| 160.98| 425.46| 1.2152| 1.7311
40| 2426| 975| 0.0097| 266.33| 158.93| 425.26| 1.221| 1.7286
41| 2485| 969| 0.0094| 268.2| 156.84| 425.04| 1.2267| 1.7261
42| 2545| 963| 0.0091| 270.08| 154.71| 424.79| 1.2325| 1.7235
43| 2607| 956| 0.0088| 271.98| 152.54| 424.52| 1.2383| 1.7209
44| 2670| 950| 0.0086| 273.9| 150.31| 424.21| 1.2442| 1.7182
45| 2734| 943| 0.0083| 275.84| 148.04| 423.88| 1.2501| 1.7155
46| 2799| 936| 0.0081| 277.8| 145.72| 423.52| 1.256| 1.7127
47| 2865| 929| 0.0078| 279.77| 143.35| 423.12| 1.2619| 1.7098
48| 2932| 922| 0.0076| 281.77| 140.92| 422.69| 1.268| 1.7069
49| 3001| 914| 0.0073| 283.8| 138.42| 422.22| 1.274| 1.7038
50| 3071| 907| 0.0071| 285.85| 135.87| 421.72| 1.2801| 1.7007
51| 3142| 899| 0.0069| 287.93| 133.24| 421.17| 1.2863| 1.6975
52| 3214| 891| 0.0066| 290.03| 130.54| 420.57| 1.2926| 1.6941
53| 3288| 883| 0.0064| 292.17| 127.75| 419.92| 1.2989| 1.6906
54| 3363| 874| 0.0062| 294.35| 124.87| 419.22| 1.3053| 1.6871
55| 3439| 865| 0.006| 296.57| 121.89| 418.46| 1.3118| 1.6833
56| 3517| 856| 0.0058| 298.83| 118.81| 417.64| 1.3184| 1.6794
57| 3596| 847| 0.0056| 301.13| 115.61| 416.74| 1.3251| 1.6753
58| 3676| 837| 0.0054| 303.5| 112.27| 415.77| 1.3319| 1.6711
59| 3758| 826| 0.0052| 305.92| 108.79| 414.71| 1.339| 1.6666
60| 3842| 815| 0.005| 308.41| 105.13| 413.54| 1.3461| 1.6618
61| 3927| 804| 0.0048| 310.99| 101.28| 412.27| 1.3535| 1.6567
62| 4013| 792| 0.0046| 313.66| 97.2| 410.86| 1.3612| 1.6513
63| 4101| 778| 0.0044| 316.44| 92.86| 409.3| 1.3691| 1.6455
64| 4191| 764| 0.0042| 319.35| 88.21| 407.56| 1.3775| 1.6392
65| 4282| 748| 0.004| 322.43| 83.17| 405.6| 1.3862| 1.6322
Notes
Worldwide Sales Offices
For more information contact your
Honeywell Refrigerants representative
United States
Honeywell Chemicals
101 Columbia Road
Morristown, NJ 07962-1053
Phone: 800-631-8138
Fax: 973-455-6395
G 525-013
Printed in the U.S.A.
© 2006 Honeywell International Inc.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>