Honeywell Home TF428/TF228/TF223 Series BACnet Thermostat Driver Installation Guide
- June 7, 2024
- Honeywell Home
Table of Contents
TF428/TF228/TF223 Series
BACnet Thermostat Driver
INSTALLATION GUIDE
**When Installing This Product
**
Caution: Must be cut off the power before installation to prevent electric shock.
- Read this instruction carefully. Failure to follow the instruction might damage the product or cause a hazardous condition.
- Check ratings given in instruction and on the product label to ensure the product is suitable for your applica
- The installer must be a trained, experienced service tech
- After installation is completed, check out product operation as provided in the instruction.
- When the product working. the door of the control cabinet must be closed, or the protection cover installed.
Specifications
Communication | BACnet MS/TP |
---|---|
Power supply | 220/230VAC. 50/60Hz |
Ambient operating limits | -10°C to 48°C |
Ambient storage limits | -30°C to 65°C |
Humidity limits | 5-90% RH, non-condensing |
Internal power consumption | 6VA |
Protection class | IP20 |
BACnet Communications
The driver communicates with another module/component through the EIA-485 BACnet protocol.
Parameter | Definition |
---|---|
Cable Type | 18AWG-24AVVG (1-0.5mm) Twist pair, shielded |
Character impedance | 100-120 ohm |
Capacitance | <100pF/m |
Maximum communication distance | 1000m |
Network topology | Daisy Chain |
Recommended maximum node number | <40 |
Baud rate | 9600. 19200. 38400. 76800 (auto-detect ) |
-
Termination Resistors
**** Matched terminating resistors are required at each end of a segmented bus wired across (+) and (-).
Use matched precision resistors rated 1/4W. ±5%. 80 -130 Ohms. Ideally, the value of the terminating resistors should match the rated characteristic impedance of the installed cable. For example, if the installed EIA-485 BACnet cable has a listed characteristic impedance of 120 Ohm, install 120 Ohm matched precision resistors. -
Shield Terminating
Following proper EIA-485 BACnet cabling shield grounding procedures is important to minimize the risk of communication problems and equipment damage caused by capacitive coupling.
Capacitive coupling is caused by placing EIA-485 BACnet cabling close to lines carrying higher voltage. The shield should be grounded on only one end of the segment (typically the router end). Tie the shield by using the SHLD on the driver.
Sylk communication
The driver can be connected with one and only one wall module through
Syllabus.
The Sylk terminals are connected with two-core wire. The maximum connection
length is 60 meters.
LED indications
The driver has one 2-color LED to indicate device state as following:
LED Status
|
BAC not State Description
---|---
Green blinking off once in 2.5 sec| The processor is running, but there is no
MS/TP token
Green blinking off twice in 2.5 sec| The processor is running and there is an
MS/TP token
Green blinking off thrice in 2.5 sec| The processor is running and there is
MS/TP communicalion
Solid off| There is no power, my processor is not running. or the pro-cessor
is dead
Red blinking| Configuration data is an error
Terminal Definition
No
| Symbol|
Description
---|---|---
| RS| Remote Sensor Input (NTC20K)
2| COM| Common
3| PS| Pipe Sensor Input (NTC20K)
4| RSB1| Hotel Card (Dry Contact)
5| COM| Common
6| RSB2| Window Contact (Dry Contact)
7| VM| Valve Modulating Output
8| COM| Common
9| | Not Used
10| | Not Used
11| | Not Used
12| S-BUS| Syllabus
13| S-BUS| Syllabus
14| BAC+| BACnet+
15| BAC-| BACnet-
16| SOLD| BACnet Shield
17| | Protective Earthing Wire
18| N| Neutral Wire
19| L| Live Wire
20| FH| High-Speed Fan
21| FM| Medium Speed Fan
22| FL| Low-Speed Fan
23| vo1| Heating / Cooling Valve Open
24| vC1| Heating / Cooling Valve Close
25| vo2| Cooling Valve Open. 4 Pipes Only
26| vC2| Cooling Valve Close. 4 Pipes Only
Terminal Wiring
|
---|---
|
Dimensions (mm)
|
---|---
Before installation
Review the installation guide and datasheet before installing the driver.
- Make sure the devices are installed and used in physical security places and networks, only the authorized person could operate the devices and access the network.
- Make sure the security of installation and maintenance for the network and upper plant controllers, the detailed information could refer to the plant controllers’ instructions.
- Make sure the devices are all in the isolated internal
Mounting
The driver enclosure is constructed of a plastic base plate and two DIN rail
hooks. The cover does not need to be removed from the base plate for either
mounting or wiring.
The driver can be mounted in any orientation. Ventilation openings are
designed into the cover to allow proper heat dissipation, regardless of the
mounting orientation.
The terminal screws must be locked tightly after wiring.
NOTE: The driver must be mounted in a position that allows clearance for
wiring, servicing, and removal.
The driver mounts to DIN rail (standard EN50022; 7.5mm x 35mm).
- Holding the driver with its bottom tilted in towards the DIN rail, hook the two bottom tabs on the back of the driver onto the bottom of the DIN rail.
- Pull up and rotate the driver to make sure the two-tops snap of the driver onto the DIN rail.
Fuse exchange
Must cut off the power before replacing.
The driver has a built-in fuse, and the cover of the control module should be
removed when replacing.
Please wear insulating gloves during the replacement process to prevent damage
to the circuit board.
Hazardous Substances and Content in the Product.
Parts
|
Hazardous substances
---|---
Pb| Hg| Cd| COI)| PBB| PBDE
PCBA
| X| 0| 0| 0| 0| 0
This table is based on SJ/T 11364
O : the hazardous substances contained in the related part are less than
the limit in GB/T 26572 standard.
X : the hazardous substances contained in the related part are more than
the limit in GB/T 26572 standard.
Other parts all conform to China’s RoHS requirements.
WEEE Directive 2012/19/EU
At the end of the product, life disposes of the packaging and product in a
corresponding recycling center.
Do not dispose of the unit with the usual domestic refuse. Do not burn the
product.
www.resideo.com
Ademco 1 GmbH Hardhofweg 40
74821 Mosbach
Phone: +49 1801 466 388
info.de@resideo.com
homecomfort.resideo.com
@2020 Resideo Technologies, Inc.
All rights reserved.
The Honeywell Home trademark is used under license from Honeywell
International Inc.
This product is manufactured by Resideo Technologies, Inc and its affiliates.
32332763 001 Rev.A
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>