resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer Instruction Manual

June 6, 2024
resideo

resideo logo

Braukmann
FK74CS/FKN74CS
Filter combination
with pressure reducing valve and reverse rinsing fine filter

resideo FKN74CS 1A Primus Plus Filter Combination Pressure
Reducer

APPLICATION

The filter combinations comprise a reverse rinsing filter and pressure reducing valve in one appliance. They ensure a continuous supply of filtered water. The fine filter stops the
ingress of foreign bodies, for example, rust particles, strands of hemp, and grains of sand, and thus reduces the probability of corrosion. The pressure- reducing valve prevents pressure damage and reduces water consumption.
The filter combinations are fitted in systems where a pressure-reducing valve is required. Both horizontal and vertical installation is possible.

APPROVALS

  • DVGW
  • SVGW

approval for all filters with 100 μm mesh sizes and with a rotatable connection piece

SPECIAL FEATURES

  • Integral pressure reducing valve with a balanced seat
  • Inlet pressure balancing – no influence on outlet pressure by fluctuating inlet pressure
  • Filtered water supplied even during reverse rinsing
  • Patented reverse rinsing system – fast and thorough cleaning of the filter with a small amount of water
  • Memory ring indicates when the next manual reverse rinsing is due
  • Automatic reverse rinsing actuator with bayonet the connector can be retrofitted
  • Large filter surface
  • Shock-resistant clear synthetic material filter bowl enables easy checking of filter contamination
  • Filter insert fully replaceable
  • Standardized discharge connection
  • All materials are ACS approved
  • All materials are KTW approved
  • Approved by TÜV LGA for low noise, Group 1 without limitations

TECHNICAL DATA

Media


Medium:| Drinking water

Connections/Sizes

Connection sizes:| 1/2″ – 1 1/4″ (with rotatable connector piece)

Pressure values

Max. operating pressure:| 1.5 – 16.0 bar
Max. inlet pressure:| 16 bar (up to 12.0 bar long*-term)
Outlet pressure:| 1.5 – 6.0 bar adjustable

Operating temperatures

Max. operating temperature medium:| 1.5 – 6.0 bar adjustable

Specifications

Installation position:| Horizontal or vertical, with filter bowl downwards

  • For maintaining the measuring accuracy of the manometer, a continuous maximum pressure load of 12.0 bar is permitted.
    Note:
    The filter is constructed for drinking water installations. In the case of a process water application, the filter has to be proven individually.

CONSTRUCTION

Overview

resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer -
fig1

| Components|

Materials

---|---|---
1| Adjustment handle with cover cap| High-quality synthetic material
2| Spring bonnet with internal adjustment screw| High-quality synthetic material
3| Housing with pressure gauge| High-quality synthetic material
4| Rotatable connector piece, flange sealings, connecting nuts and fittings (FK74CS only)| Dezincification-resistant brass
5| Clear filter bowl| Shock-resistant, clear transparent synthetic material
6| Fine filter| Stainless steel
7| Ball valve with drain connection| Brass (Ball Valve body), Stainless steel (ball), Plastic- duration (drain adapter)

Not depicted components

Memory ring| Plastic
Allen key WS6| Stainless steel
Valve insert complete with diaphragm and valve seat| High-quality synthetic material
Wrench for filter bowl and spring bonnet| Plastic
Covers and reverse rinsing handle| Synthetic material
Diaphragm| Fiber-reinforced NBR
Sealing washers| EPDM

METHOD OF OPERATION

The filter combination combines reverse rinsing filter and pressure reducing valve in one appliance.
The filter insert comprises an upper part and a lower combination section. When in the „filtering“ position, the small upper filter is closed so that the water can only pass through the main filter from outside to inside. When the ball valve is opened for reverse rinsing, the filter is pushed downwards until the water supply to the outer side of the
main filter is stopped. Simultaneously, the water flow is opened to the upper part of the filter. The water needed for cleaning the filter passes through the upper sieve, the rotating impeller, and the main filter from inside to outside.
By this means, the filter is fully cleaned over its whole surface area at the full inlet pressure. The filter automatically switches over to the operating position when the ball valve is
closed again.
The integral pressure reducing valve functions on a balanced force principle whereby the force exerted by a diaphragm is balanced against the force of an adjustment spring. The inlet pressure has no influence on the opening or closing of the valve. Inlet pressure fluctuation does not, therefore, affect the outlet pressure.

TRANSPORTATION AND STORAGE

Keep parts in their original packaging and unpack them shortly before use.
The following parameters apply during transportation and storage:

Parameter Value
Environment: clean, dry, and dust-free
Min. ambient temperature: 5 °C
Max. ambient temperature: 55 °C
Min. ambient relative humidity: 25 % *
Max. ambient relative humidity 85 % *

INSTALLATION GUIDELINES

Setup requirements

  • The installation site has to be frost-proof and the protection of the device from chemicals, paints, detergents, solvents, and their vapors and environmental influences must be guaranteed

  • Install in horizontal or vertical pipework with filter bowl downwards
    This position ensures optimum filter efficiency

  • Install shut-off valves

  • These filters are armatures that need to be maintained regularly

  • Ensure good access
    Pressure gauge can be read off easily
    Degree of contamination can be easily seen with a clear filter bowl
    Simplifies maintenance and inspection

  • It is recommended that a straight section of pipework at At least five times the nominal valve size is provided after the filter (according to DIN EN 806-2)

  • Fit immediately after the water meter

  • Related to the EN 806-2 it is recommended to install the filter immediately after the water meter

  • In order to avoid flooding, it is recommended to arrange a permanent professionally dimensioned wastewater connection

Installation Example

resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer -
Installation

TECHNICAL CHARACTERISTICS

kvs-Values

Connection sizes: 15 20 25 32
kvs-value (m3/h): 4.5 5.8 6.2 6.5

Pressure drop characteristics

resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer -
graph

DIMENSIONS

Overview

resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer -
Overview

Parameter Values
Connection sizes: R
Nominal sizes: DN
Weight: kg
Dimensions: H
h 298
L 150
I 90
B 178
b 150
t 92
ØT 50
DVGW registration number: NW-9311 CM 0032

Note  All dimensions in mm unless stated otherwise.

ORDERING INFORMATION

The following tables contain all the information you need to make an order of an item of your choice. When ordering, please always state the type, the ordering, or the part number.
Options
The filter combination is available in the following sizes: 1 /2″,3 /4″, 1″ and 1 1 /4″.

  • standard
    – not available

| FK74CS- …AA| FK74CS-…AC| FK74CS- …AD| FKN74CS- 1A| FKN74- 1C
---|---|---|---|---|---
Connection type:| With rotatable connector piece, filter mesh size 100 μm|

| | | |

With rotatable connector piece, filter mesh size 50 μm|

| | | |

With rotatable connector piece, filter mesh size 200 μm|

| | | |

Retrofit version without rotatable connector the piece, filter mesh size 100 μm|

| | | |

Retrofit version without rotatable connector the piece, filter mesh size 50 μm|

| | | |

Note: … = space holder for connection size

Accessories

|

Description

| Dimension|

Part No.

---|---|---|---
resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer -
parts1|

DA74 R

| Rotatable connector piece
For connection of retrofit filters and filter combinations
| D74CS| 1/2″| DA74CS-1/2A
D74C| 3/4″| DA74C-3/4A
D74C| 1″| DA74C-1A
D74C| 1 1/4″| DA74C-11/4A
|

Z74S-AN

| Automatic reverse rinsing actuator
For automatic filter cleaning at presettable intervals
| | | Z74S-AN
resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer -
parts3|

VST06B

| Connection set
Solder connections
| | 3/4″| VST06-3/4B
1″| VST06-1B
1 1/4″| VST06-11/4B
resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer -
parts4|

ZR74CS

| Double ring wrench for removing the filter bowl
| | 1/2″ + 1/4″| ZR74CS

Spare Parts
Filter combinations FK74CS / FKN74CS from 2010 onwards
Overview

resideo FKN74CS 1A Primus Plus Filter Combination Pressure Reducer -
parts5

| Description| Dimension|

Part No.

---|---|---|---

1

| Valve insert complete
| 1/2″ – 1 1/4″| D06FA-1B

2

| Filter insert complete
100 μm| 1/2″ – 1 1/4″| AF74-1A
50 μm| 1/2″ – 1 1/4″| AF74-1C
200 μm| 1/2″ – 1 1/4″| AF74-1D

3

| Clear filter bowl

4

| Pressure gauge
| 0 – 16 bar| M74CS-A16

5

| Connection set threaded connection
| 3/4″| VST06-3/4A
1″| VST06-1A
1/4″| VST06-11/4A

6

| Union seal washer (10 pcs.)
| 3/4″| 0901444
1″| 0901445
1 1/4″| 0901446

7

| Flange seal
| 3/4″ – 1 1/4″| 5975900

resideo logo Ademco 1 GmbH
Hardhofweg 40
74821 Mosbach
Phone: +49 1801 466 388
info.de@resideo.com
homecomfort.resideo.com
@2020 Resideo Technologies, Inc.
All rights reserved.
This product is manufactured by Resideo Technologies, Inc and its affiliates.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals