Zennio ZPDEZTP Motion detector with luminosity sensor for ceiling mounting User Manual

June 6, 2024
Zennio

Zennio ZPDEZTP Motion detector with luminosity sensor for ceiling mounting User Manual
Zennio ZPDEZTP Motion detector with luminosity sensor for ceiling
mounting

DOCUMENT UPDATES


Version

| ****

Changes

| ****

Page(s)

---|---|---

[1.4]_a

| Changes in the application program:

  • Update of the Logic Functions, Heartbeat, Binary Inputs, and Presence Detector
  • Reorganisation of ETS parameters.

| ****



INTRODUCTION

EYEZEN TP

EyeZen TP from Zennio is a device that aims at, among other functions, the detection of motion, the measurement and control of the room luminosity and the detection of occupancy within the room where it has been installed. It has been designed for ceiling or false ceiling mounting by means of the bundled accessories.

The most outstanding features of EyeZen TP are:

  • Sensor with configurable sensitivity.
  • LED to indicate motion.
  • Two colours of lenses: white and black.
  • Motion detection:
    • 6 motion detection channels.
    • Luminosity-dependent motion detection (optional).
    • Periodic and delayed sendings (binary, scene, HVAC, percentage).
  • Occupancy detection:
    • 1x occupancy detection channel.
    • Master / slave configuration.
    • Trigger upon door opening or closing.
    • Periodic and delayed sendings (binary, scene, HVAC, percentage).
  • Luminosity measurement:
    • Configurable correction factor and offset.
    • Periodic sending or upon value change.
  • 2 constant light control channels with configurable setpoints.
  • Day / night configuration.
  • 10 customisable, multi-operation logic functions.
  • Heartbeat or periodical “still alive” notification.
INSTALLATION

EyeZen TP connects to the KNX bus through the on-board KNX connector.

Once the device is provided with power from the KNX bus, both the individual address and the associated application program may be downloaded.

This device does not need any additional external power since it is entirely powered
through the KNX bus.

Figure 1.
EyeZen TP. Elements

  1. Detection LED indicator.
  2. Retaining spring.
  3. Test/Prog. button.
  4. Test/Prog. LED.
  5. KNX connector.

The main elements of the device are described next.

  • Programming button (3): a short press on this button sets the device into the programming mode, making the associated LED (4) light in red.
    Note: if this button is held while plugging the device into the KNX bus, the device will enter the safe mode. In such case, the LED will blink in red every 0.5 seconds.

  • Detection notification LED (1): emits a red light flash when the sensor observes motion.

To get detailed information about the technical features of this device, as well as on the installation process and on security procedures, please refer to the corresponding Datasheet, bundled with the original packaging of the device and also available at www.zennio.com.

START-UP AND POWER LOSS

During the start-up of the device, the detection notification LED flashes red for one
minute before the motion sensor is ready.

Depending on the configuration, some specific actions will also be performed during the start-up. For example, the integrator can set whether the detection channels should start up enabled or disabled.

CONFIGURATION

After importing the corresponding database in ETS and adding the device into the topology of the desired project, the configuration process begins by entering the parameters tab of the device.

ETS PARAMETERISATION

From General screen it is possible to activate/deactivate all the required functionality.

Figure 2.
General

  • Lens Color [White / Black]: parameter to select the lens colour that EyeZen TP has installed, for correct sensor luminosity measurement.

  • Motion Detection [enabled]: enables the “Motion Detector” tab in the tree on the left. For more information, see section 2.2.

  • Logic Functions [enabled/disabled] enables or disables the “Logic Functions”
    tab in the tree on the left. For more information, see section 2.3.

  • Heartbeat (Periodic Alive Notification) [enabled/disabled]: incorporates a
    one-bit object to the project (“[Heartbeat] Object to Send ‘1’”) that will be sent
    periodically with a value of “1” to notify that the device is still working (still alive).

CONFIGURATION
Figure 3.
Heartbeat

Note: the first sending after download or bus failure takes place with a delay of up to 255 seconds, to prevent bus overload. The following sendings match the period set.

MOTION DETECTOR

EyeZen TP incorporates six independent motion detection channels, two more for constant light control and one for occupancy detection.

  • Motion detection consists in sending objects to the bus whenever the device observes a moving body (or no longer observes it) in the environment of the room where it has been installed.
  • Constant light control consists in sending KNX orders to the dimmer device that controls the in-room luminaries so the ambient light level remains constant even if other light sources are present.
  • Occupancy detection is an algorithm that allows determining whether a particular space is under occupation no matter if the occupant moves or not (i.e., no matter if the device is detecting motion in the room or not).

It also allows setting different luminosity setpoints or object types for daytime and night time as well as activating or deactivating the motion indicator LEDs.

EyeZen TP can also set custom sensitivity of the motion sensor and measure the
luminosity of the room by making certain adjustments. This measurement will be made according to the color of lens selected.

Please refer to the specific manual “Presence Detector” available in EyeZen TP product section at the Zennio website (www.zennio.com) for detailed information about the functionality and the configuration of the related parameters. Please note that references to presence detection in this manual in this case correspond to motion detection.

LOGIC FUNCTIONS

This module makes it possible to perform numeric and binary operations to incoming values received from the KNX bus, and to send the results through other communication objects specifically enabled for this purpose.

EyeZen TP can implement up to 10 different and independent functions, each of them entirely customisable and consisting of up to 4 consecutive operations.

The execution of each function can depend on a configurable condition, which will be evaluated every time the function is triggered through specific, parameterisable communication objects. The result after executing the operations of the function can also be evaluated according to certain conditions and afterwards sent (or not) to the KNX bus, which can be done every time the function is executed, periodically or only when the result differs from the last one.

Please refer to the “Logic Functions” user manual available under the EyeZen TP product section at the Zennio homepage (www.zennio.com) for detailed information about the functionality and the configuration of the related parameters.

ANNEX I. COMMUNICATION OBJECTS

“Functional range” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a particular meaning because of the specifications or restrictions from both the KNX standard or the application program itself.

Number

| Size| I/O| Flags| Data type (DPT)| Functional Range| Name| Function
---|---|---|---|---|---|---|---

1

| 1 Bit| | C – – T –| DPT_Trigger| 0/1| [Heartbeat] Object to Send ‘1’|

Sending of ‘1’ Periodically

2

| 1 Byte|

I

| C – W – –|

DPT_SceneNumber

| 0 – 63| Scene Input| Scene Value

3

| 1 Byte| | C – – T –| DPT_SceneControl|

0-63; 128-191

|

Scene Output

|

Scene Value

4

| 2 Bytes| I/O| C R W – –| 1.xxx|

0/1

|

Correction Factor – Internal Sensor

|

[0, 80] x0.1

5

| 2 Bytes| I/O| C R W – –|

1.xxx

|

0/1

|

Offset – Internal Sensor

|

[-200, 200] Luxes

6

| 2 Bytes| O| C R – T –| DPT_Value_Lux| |

LuminCosity – Internal Sensor

|

Luxes

1 Byte| O| C R – T –| DPT_Scaling| 0% – 100%|

Luminosity – Internal Sensor

|

%

7

| 2 Bytes| I/O| C R W – –|

1.xxx

|

0/1

|

Correction Factor – Additional Sensor

|

[0, 80] x0.1

8

| 2 Bytes| I/O| C R W – –| 1.xxx| 0/1| Offset – Additional Sensor| [-200, 200] Luxes
9| 2 Bytes| O| C R – T –| DPT_Value_Lux|

|

Luminosity – Additional Sensor

|

Luxes

1 Byte| O| C R – T –| DPT_Scaling| 0% – 100%| Luminosity – Additional Sensor|

%

10

| 1 Bit| I| C – W – –| DPT_DayNight| 0/1| Day/Night| 0 = Day; 1 = Night
1 Bit| I|

C – W – –

|

DPT_DayNight

|

0/1

|

Day/Night

|

0 = Night; 1 = Day

11

|

1 Bit

| I| C – W – –| DPT_Enable| 0/1|

Detection LED

|

0 = Disable; 1 = Enable

1 Bit

| I| C – W – –| DPT_Enable| 0/1| Detection LED| 0 = Disable; 1 = Enable Only During the Day

12

|

1 Bit

| O|

C R – T –

| DPT_Switch| 0/1| Occupancy: Output (Binary)|

Binary Value

1 Bit

| |

C – – T –

| DPT_Start| 0/1| Occupancy: Slave Output|

1 = Motion Detected

13

|

1 Byte

| O|

C R – T –

| DPT_Scaling| 0% – 100%| Occupancy: Output (Scaling)|

0-100%

14

|

1 Byte

|

O

|

C R – T –

|

DPT_CHVACMode

|

1=Comfort 2=Standby 3=Economy 4=Building Protection

|

Occupancy: Output (HVAC)

|

Auto, Comfort, Standby, Economy, Building Protection

15

|

1 Bit

| I|

C – W – –

|

DPT_Window_Door

|

0/1

|

Occupancy: Trigger

|

Binary Value to Trigger the Occupancy Detection

16

|

1 Bit

| I|

C – W – –

| DPT_Start| 0/1|

Occupancy: Slave Input

|

1 = Detection from slave device

17

|

2 Bytes

| I|

C – W – –

| DPT_TimePeriodSec| 0 – 65535|

Occupancy: Waiting Time

|

0-65535 s.

18

|

2 Bytes

| I|

C – W – –

| DPT_TimePeriodSec| 0 – 65535| Occupancy: Listening Time|

1-65535 s.

19

| 1 Bit| I| C – W – –| DPT_Enable| 0/1| Occupancy: Lock| 0 = Unlock; 1 = Lock
---|---|---|---|---|---|---|---
1 Bit|

I

|

C – W – –

| DPT_Enable|

0/1

|

Occupancy: Lock

|

0 = Lock; 1 = Unlock

20

|

1 Bit

|

O

|

C R – T –

|

DPT_Occupancy

|

0/1

|

Occupancy: Occupancy State

|

0 = Not Occupied; 1 = Occupied

21

|

1 Byte

|

I

|

C – W – –

|

DPT_Scaling

|

0% – 100%

|

Sensor Sensitivity

|

1-100%

22| 1 Byte| I| C – W – –| DPT_Scaling| 0% – 100%| Sensor 2 Sensitivity|

1-100%

23

|

1 Byte

|

I

| C – W – –|

DPT_Scaling

|

0% – 100%

|

Sensor 3 Sensitivity

|

1-100%

24| 1 Byte| I| C – W – –| DPT_Scaling| 0% – 100%| Sensor 4 Sensitivity|

1-100%

25, 35, 45, 55, 65, 75

| 1 Bit| I|

C – W – –

| DPT_Start|

0/1

|

[Cx] External Motion Detection

|

1 = Motion detected by an external sensor

26, 36, 46, 56, 66, 76

|

1 Bit

|

O

|

C R – T –

|

DPT_Switch

|

0/1

|

[Cx] Output (Binary)

|

Binary Value

27, 37, 47, 57, 67, 77

| 1 Byte|

O

| C R – T –|

DPT_Scaling

|

0% – 100%

|

[Cx] Output (Scaling)

|

0-100%

28, 38, 48, 58, 68, 78

| 1 Byte| O| C R – T –| DPT_HVACMode| 1=Comfort 2=Standby 3=Economy
4=Building Protection| [Cx] Output (HVAC)| Auto, Comfort, Standby, Economy, Building Protection
29, 39, 49, 59, 69, 79| 1 Bit|

I

|

C – W – –

|

DPT_Enable

|

0/1

|

[Cx] Lock Status

|

0 = Unlock; 1 = Lock

1 Bit| I| C – W – –|

DPT_Enable

|

0/1

|

[Cx] Lock Status

|

0 = Lock; 1 = Unlock

30, 40, 50, 60, 70, 80

| 1 Bit| I| C – W – –| DPT_Start| 0/1| [Cx] Force State| 0 = No Detection; 1 = Detection

31, 41, 51, 61, 71, 81

| 1 Bit| I| C – W – –|

DPT_Start

|

0/1

|

[Cx] External Switch

| 0 = No Detection; 1 = Detection

32, 42, 52, 62, 72, 82

| 2 Bytes| I/O| C R W – –|

DPT_TimePeriodSec

|

0 – 65535

|

[Cx] Length of Detection

| 1-65535 s.

33, 43, 53, 63, 73, 83

| 2 Bytes|

O

| C R – T –|

DPT_Value_Lux

| |

[Cx] Luminosity

| Luxes
1 Byte|

O

| C R – T –|

DPT_Scaling

|

0% – 100%

|

[Cx] Luminosity

| %

85, 101

| 1 Bit|

I

| C – W – –|

DPT_Start

|

0/1

|

[CLCx] External Motion Detection

| 1 = Motion detected by an external sensor

86, 102

| 1 Bit| I| C – W – –| DPT_Enable| 0/1| [CLCx] Lock Status| 0 = Unlock; 1 = Lock

1 Bit

|

I

| C – W – –| DPT_Enable| 0/1| [CLCx] Lock Status| 0 = Lock; 1 = Unlock

87, 103

|

1 Bit

|

I

|

C – W – –

|

DPT_Start

|

0/1

|

[CLCx] Force State

| 0 = No Detection; 1 = Detection

88, 104

|

1 Bit

|

I

|

C – W – –

|

DPT_Start

|

0/1

|

[CLCx] External Switch

|

0 = No Detection; 1 = Detection

89, 105

|

2 Bytes

|

I

|

C – W – –

|

DPT_Value_Lux

| |

[CLCx] Setpoint

|

Setpoint Value (1-2000)

2 Bytes

|

I

| C – W – –| DPT_Value_Lux| |

[CLCx] Setpoint During Day

|

Setpoint Value (1-2000)

1 Byte

|

I

|

C – W – –

|

DPT_Scaling

|

0% – 100%

|

[CLCx] Setpoint

|

Setpoint Value (1-100)%

1 Byte

|

I

| C – W – –| DPT_Scaling| 0% – 100%| [CLCx] Setpoint During Day| Setpoint Value (1-100)%

90, 106

|

2 Bytes

|

I

|

C – W – –

|

DPT_Value_Lux

| |

[CLCx] Setpoint During Night

|

Setpoint Value (1-2000)

1 Byte

|

I

|

C – W – –

|

DPT_Scaling

|

0% – 100%

|

[CLCx] Setpoint During Night

|

Setpoint Value (1-100)%

91, 107

|

1 Byte

|

O

|

C R – T –

|

DPT_Scaling

|

0% – 100%

|

[CLCx] Dimming Value

|

Dimming Value (%)

92, 108

|

2 Bytes

|

I/O

|

C R W – –

|

DPT_TimePeriodSec

|

0 – 65535

|

[CLCx] Length of Detection

|

1-65535 s.

93, 109

|

2 Bytes

|

O

| C R – T –|

DPT_Value_Lux

| | [CLCx] Luminosity| Luxes
1 Byte|

O

|

C R – T –

|

DPT_Scaling

| 0% – 100%| [CLCx] Luminosity| %
94, 110| 1 Bit| I| C – W – –|

DPT_Switch

| 0/1|

[CLCx] Manual Control: On/Off (Input)

| 1-Bit Control

95, 111

|

4 Bit

|

I

|

C – W – –

|

DPT_Control_Dimming

| 0x0 (Stop)

0x1 (Dec. by 100%)

0x7 (Dec. by 1%) 0x8 (Stop)

0xD (Inc. by 100%)

0xF (Inc. by 1%)

|

[CLCx] Manual Control: Relative Dimming (Input)|

4-Bit Control

---|---|---|---|---|---|---|---
96, 112| 1 Byte| I| C – W – –| DPT_Scaling| 0% – 100%| [CLCx] Manual Control: Absolute Dimming (Input)| 1-Byte Control
97, 113| 1 Bit| O| C R – T –| DPT_Switch| 0/1| [CLCx] Manual Control: On/Off (Output)| 1-Bit Control

98, 114

|

4 Bit

|

O

|

C R – T –

|

DPT_Control_Dimming

| 0x0 (Stop)

0x1 (Dec. by 100%)

0x7 (Dec. by 1%) 0x8 (Stop)

0xD (Inc. by 100%)

0xF (Inc. by 1%)

|

[CLCx] Manual Control: Relative Dimming (Output)|

4-Bit Control

99, 115| 1 Bit| I| C – W – –| DPT_Enable| 0/1| [CLCx] Manual Control| 0 = Disable; 1 = Enable
100, 116| 1 Bit| O| C R – T –| DPT_Enable| 0/1| [CLCx] Manual Control (Status)| 0 = Disabled; 1 = Enabled

117, 118, 119, 120, 121, 122,

123, 124, 125, 126, 127, 128,

129, 130, 131, 132, 133, 134,

135, 136, 137, 138, 139, 140,

141, 142, 143, 144, 145, 146,

147, 148

|

1 Bit

|

I

|

C – W – –

|

DPT_Bool

|

0/1

|

[LF] (1-Bit) Data Entry x|

Binary Data Entry (0/1)

149, 150, 151, 152, 153, 154,

155, 156, 157, 158, 159, 160,

161, 162, 163, 164

|

1 Byte

|

I

|

C – W – –

|

DPT_Value_1_Ucount

|

0 – 255

|   [LF] (1-Byte) Data Entry x|

1-Byte Data Entry (0-255)

165, 166, 167, 168, 169, 170,

171, 172, 173, 174, 175, 176,

177, 178, 179, 180

|

2 Bytes

|

I

|

C – W – –

|

1.xxx

|

0/1

|   [LF] (2-Byte) Data Entry x|

2-Byte Data Entry

181, 182, 183, 184, 185, 186,

187, 188

| 4 Bytes| I| C – W – –| DPT_Value_4_Count| -2147483648 – 2147483647| [LF] (4-Byte) Data Entry x| 4-Byte Data Entry

189, 190, 191, 192, 193, 194,

195, 196, 197, 198

| 1 Bit| O| C R – T –| DPT_Bool| 0/1| [LF] Function x – Result| (1-Bit) Boolean
1 Byte| O| C R – T –| DPT_Value_1_Ucount| 0 – 255| [LF] Function x – Result| (1-Byte) Unsigned
2 Bytes| O| C R – T –| DPT_Value_2_Ucount| 0 – 65535| [LF] Function x – Result| (2-Byte) Unsigned
4 Bytes| O| C R – T –| DPT_Value_4_Count| -2147483648 – 2147483647| [LF] Function x – Result| (4-Byte) Signed
1 Byte| O| C R – T –| DPT_Scaling| 0% – 100%| [LF] Function x – Result| (1-Byte) Percentage
2 Bytes| O| C R – T –| DPT_Value_2_Count| -32768 – 32767| [LF] Function x – Result| (2-Byte) Signed
2 Bytes| O| C R – T –| 9.xxx| -671088.64 – 670433.28| [LF] Function x – Result| (2-Byte) Float

95, 111

| 4 Bit| I| C – W – –|

DPT_Control_Dimmi

| 0x0 (Stop)

0x1 (Dec. by 100%)…0x7 (Dec. by 1%) 0x8 (Stop) 0xD (Inc. by 100%)

…0xF (Inc. by 1%)

|

[CLCx] Manual Control: Relative Dimming (Input)

|

4-Bit Control

---|---|---|---|---|---|---|---

96, 112

|

1 Byte

|

I

|

C – W – –

|

DPT_Scaling

|

0% – 100%

|

[CLCx] Manual Control: Absolute Dimming (Input)

|

1-Byte Control

97, 113

|

1 Bit

|

O

|

C R – T –

|

DPT_Switch

|

0/1

|

[CLCx] Manual Control: On/Off (Output)

|

1-Bit Control

98, 114

|

4 Bit

|

O

|

C R – T –

|

DPT_Control_Dimmin

|

0x0 (Stop)0x1 (Dec. by 100%)…0x7 (Dec. by 1%) 0x8 (Stop)0xD (Inc. by 100%)

…0xF (Inc. by 1%)

|

[CLCx] Manual Control: Relative Dimming (Output)

|

4-Bit Control

99, 115| 1 Bit| I|

C – W – –

|

DPT_Enable

|

0/1

|

[CLCx] Manual Control

| 0 = Disable; 1 = Enable
100, 116| 1 Bit| O|

C R – T –

|

DPT_Enable

| 0/1| [CLCx] Manual Control (Status)| 0 = Disabled; 1 = Enabled

117, 118, 119, 120, 121, 122,

123, 124, 125, 126, 127, 128,

129, 130, 131, 132, 133, 134,

135, 136, 137, 138, 139, 140,

141, 142, 143, 144, 145, 146,

147, 148

|

1 Bit

|

I

|

C – W – –

|

DPT_Bool

|

0/1

|

[LF] (1-Bit) Data Entry x

|

Binary Data Entry (0/1)

149, 150, 151, 152, 153, 154,

155, 156, 157, 158, 159, 160,

161, 162, 163, 164

|

1 Byte

|

I

|

C – W – –

|

DPT_Value_1_Ucount

|

0 – 255

|

[LF] (1-Byte) Data Entry x

|

1-Byte Data Entry (0-255)

165, 166, 167, 168, 169, 170,

171, 172, 173, 174, 175, 176,

177, 178, 179, 180

|

2 Bytes

|

I

|

C – W – –

|

1.xxx

|

0/1

|

[LF] (2-Byte) Data Entry x

|

2-Byte Data Entry

181, 182, 183, 184, 185, 186,

187, 188

| 4 Bytes| I| C – W – –|

DPT_Value_4_Count

|

-2147483648 – 2147483647

|

[LF] (4-Byte) Data Entry x

|

4-Byte Data Entry

189, 190, 191, 192, 193, 194,

195, 196, 197, 198

|

1 Bit

|

O

|

C R – T –

|

DPT_Bool

|

0/1

|

[LF] Function x – Result

|

(1-Bit) Boolean

1 Byte

|

O

|

C R – T –

|

DPT_Value_1_Ucount

| 0 – 255|

[LF] Function x – Result

|

(1-Byte) Unsigned

2 Bytes

|

O

|

C R – T –

|

DPT_Value_2_Ucount

| 0 – 65535|

[LF] Function x – Result

|

(2-Byte) Unsigned

4 Bytes

| O| C R – T –|

DPT_Value_4_Count

| -2147483648 – 2147483647|

[LF] Function x – Result

|

(4-Byte) Signed

1 Byte

|

O

| C R – T –|

DPT_Scaling

| 0% – 100%|

[LF] Function x – Result

| (1-Byte) Percentage

2 Bytes

|

O

| C R – T –|

DPT_Value_2_Count

| -32768 – 32767|

[LF] Function x – Result

|

(2-Byte) Signed

2 Bytes

|

O

|

C R – T –

|

9.xxx

|

-671088.64 – 670433.28

|

[LF] Function x – Result

|

(2-Byte) Float

Join and send us your inquiries about Zennio devices:
https://support.zennio.com

Zennio Avance y Tecnología S.L.
C/ Río Jarama, 132. Nave P-8.11
45007 Toledo (Spain).
Tel. +34 925 232 002.

www.zennio.com
info@zennio.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals