TRADE PRO UV 24 PRO Light for Clean Air Installation Guide

June 6, 2024
TRADE PRO

TRADE PRO - logo UV 24 PRO

**Installation Guide

**

UV 24 PRO is installed inside the air handling system to reduce biological contamination for reduced system maintenance and improved indoor air quality.TRADE PRO UV 24 PRO Light for Clean AirUS patent #7,704,463

IMPORTANT!

  • Only qualified technicians should install this product
  • Install in accordance with relevant building codes
  • Read instructions carefully including safety warnings

**Installation Notes

**

Before installing UV 24 PRO it is necessary to determine the optimal mounting location inside the air system. First, look for the area with the heaviest mold growth. Also, consider a location that will allow the germicidal UV light to shine on the greatest surface area. For enhanced antimicrobial effect 2 or more lamps can be installed in different parts of the air system.

Some typical mounting locations:

A. Supply-side duct
B . At the blower
C. Across the top of coils| D. Coil face
E . Coil “A” plate
F. Return-side duct
---|---

WARNING
PROTECT EYES FROM UV LIGHT TURN OFF UNIT OR DISCONNECT BEFORE SERVICING

Important : some materials inside the air system (including filter media, flex duct, wiring, etc.) may not be UV light-resistant. Use the optional UV shield (part #TUV-SHIELD-LPC) or cover the materials with reflective tape.TRADE PRO UV 24 PRO Light for Clean Air - figTRADE PRO UV 24 PRO Light for Clean Air -
fig1

Parts Included

UV 24 PRO Mounting Options

A. UV Lamp
B . Power Supply
C. UV Warning Sticker
D .”Z” Mounting Bracket| E. Self-Tapping Screws
F . Sight Glass
G. Tap-in Connector
H .Plastic Nuts
---|---

Air Handler Interior Surface Installation

  1. Determine the optimal position for placement of the UV lamp.TRADE PRO UV 24 PRO Light for Clean Air - fig3

  2. Use a utility knife to cut a slit in the insulation on the interior surface.
    TRADE PRO UV 24 PRO Light for Clean Air - fig4

  3. Place the magnetic “Z” bracket directly on the metal surface or remove the magnet and hard-mount the bracket using the self-tapping   screws provided. Use foil tape to close the cut in the insulation.

  4. Use plastic quick-nuts to attach the UV lamp to the “Z” bracket as shown.

Coil “A” plate Installation

TRADE PRO UV 24 PRO Light for Clean Air - fig5

  1. Snap the “Z” bracket apart by bending.TRADE PRO UV 24 PRO Light for Clean Air - fig6
  2. Drill a 1” hole in the “A”-plate then attach the smaller piece of the bracket using the self-tapping screws.
  3. Insert the UV lamp into the hole then use the plastic nuts to attach the UV lamp to the “Z” bracket as shown.

Power Supply Installation

IMPORTANT! Check which power supply is included with your UV 24 PRO before connecting to power. Turn off the main power source before installation.TRADE PRO UV 24 PRO Light for Clean Air -
fig7

UV 24 PRO Power Supply

  1. Find a suitable location for the power supply inside the control panel of the air handler. Install using the self-tapping screws.
  2. Use the wiring diagrams below to connect to power.

IMPORTANT
Turn off the main power source before installation.
IMPORTANT! Must be wired to constant power – do not connect to blower relay.

TRADE PRO UV 24 PRO Light for Clean Air - fig8

IMPORTANT!
Systems with high 24 VAC loads may require the installation of a separate 24 VAC transformer to power the UV light.
Always use a separate 24 VAC transformer with “communicating” air systems.
Draws 16 VA, may need to do load calculation: Volts under load X Amps under load.

UV Lamp Connection

  1. When all the other components are properly installed connect the UV Lamp cable to the Power supply cable.
  2. Make sure the clips are aligned and then push the connectors firmly together. A tight connection ensures a proper seal.TRADE PRO UV 24 PRO Light for Clean Air - fig9

Sight Glass InstallationTRADE PRO UV 24 PRO Light for Clean Air -
fig10

  1. Find a suitable location on the outside of the duct-work near the UV Lamp installation and apply the warning/lamp replacement sticker.
  2. Drill a ½” hole through the orange circle on the sticker. Press the UV safety viewport into the hole.
  3. Turn on the power and use the sight glass to confirm that the UV Lamp is operating.

Lamp Replacement

The germicidal UV lamp in UV 24 PRO needs to be replaced annually. Note: UV lamps will continue to emit visible light but lose germicidal effectiveness over time. TRADE PRO UV 24 PRO Light for Clean Air -
fig11UV Lamp (Part # TPUVL, TPUVL-OS)

CAUTION!
UV lamps contain small amounts of mercury – dispose of lamps in accordance with local environmental regulations. For more information visit www.lamprecycle.org
Note: Use of replacement UV lamps other than Part # TPUVL, TPUVL-OS voids warranty.